Description
Synthetic fiber filter cell, class G4 according to EN 779:2012 (Am ≥ 90%). The inner and outer frames of the filters
are made of galvanized steel. To ensure tightness, the filters pockets are locked to the outer frame. Correct
opening of the filter pockets is ensured by using distance holders sewn into the fabric; reliable and correct
functionally as well as high duct collecting efficiency.

Application Operation range


 Air Conditioning ventilation system  Maximum working temperature: 80⁰ C
 Low start pressure drop  Relative humidity : 90%
 High dust holding capacity  Recommended Pressure drop: 250 Pa
 Reduced operating costs
 Provides long service interval Filter stage and Class
 I stages and G3 & G4
Frame and Media Filter Class
 Synthetic Media( polyester ) & Frame: GI-  EN 779-2012
20mm , 25mm  ISO course

Width(mm) Height(mm) Bag Filte Bag Air Pressure drop


length(mm r flow
) Area m3/hr
287 287 360 0.7 3 800 40
287 287 580 1 3 850 30
287 592 360 1.3 3 1700 40
287 592 580 2 3 1700 30
592 287 360 1.3 6 1700 40
592 287 580 2 6 1700 30
592 430 600 3.5 6 2800 40
490 592 580 3.5 5 2800 30
592 592 360 2.6 6 3400 40
592 592 600 4.2 6 3400 30
Presurre & Air Flow velocity Graph
60

50

40
Pressure Pa

30

20

10

500 1000 1500 2000 2500 3000 3500 4000 4500


Airflow(m3/hr)

CLASSIFICATION STANDRAD FOR PRE AND FINE FILTERS

The ISO 16890 test standard has been valid for the classification of air filters since January 2017 and, since
August, also as DIN EN ISO 16890:2017. By mid-2018, it will completely replace the previous industry standard EN
779 in most countries.
Group classification according ISO16890
ISO ePM1 ePM1, min≥ 50% (Viruses, Nano particles, Exhaust gases)

ISO ePM2.5 ePM2.5, min≥ 50% (bacteria, fungal an mold spores, pollen, toner dust)

ISO ePM10 ePM10, min≥ 50% ( Pollen, desert duct)

ISO Course ePM10≤ 50% ( Sand, hair)

Table 1 - Classification of air filters


Group Class Final Pressure Average arrestance (Am) Average arrestance Minimum Efficiency
Drop Pa of synthetic dust % (Am) of 0.4 Um of 0.4 Um particle,
particle %
%
Course G1 250 50≤Am<65 - -
G2 250 65≤Am<80 - -
G3 250 80≤Am<90 - -
G4 250 90≤Am - -
Medium M5 450 - 40≤em<60 -
M6 450 - 60≤Am<80 -
Fine F7 450 - 80≤Am<90 35
F8 450 - 90≤Am<95 55
F9 450 - 95≤Am 70