Professional Documents
Culture Documents
variables. In fact, the measurements from the real time system For the solar emulation, the photovoltaic power profile
are stored in shared variables and can be read from the emulation (PPPE) software automatically calculates solar array
software interface for control and programming purposes. In voltage and current profiles based on user-defined parameters.
Fig.1, a view of hardware and software of the test bed system These profiles are sequentially sent to a Magna-Power
is shown. For this experiment, a 9-bus microgrid system is Electronics power supply, which emulates defined
designed. characteristics. The output from the power supply is then fed
to an IGBT inverter for grid integration. Fig.3 show the PV
integration setup.
210
G1
G2
200
G3
190
170
160
150
140
130
120
0 5 10 15 20 25
Time [sec]
Figure 6 Generators internal Voltage for fault on grid connected case
125
in Fig. 5 - 8. The results show that there was not much Time [sec]
transient difference before and after the fault and there was Figure 7. Generators bus Voltage for fault on grid connected case
only a small disturbance at the time when the fault was applied 60.4
and after that the system returned to its pre-fault state in about f2
60.35 f3
2 sec. Fig. 5 shows the load angles of the generators. After
small deviation at the time of fault, each generator’s angle 60.3
Mech Frequency [Hz]
returned to its initial level. Fig. 6 and 7 show the generators’ 60.25
internal and bus voltages respectively. There was a small sag
60.2
in the internal voltages, but the bus voltage dip for generator 1
was considerable because it is closer to the fault (see Fig. 7). 60.15
The change in bus voltages was about 8%, 4%, and 3% for 60.1
generators 1, 2, and 3 respectively.
60.05
60
-2 0 5 10 15 20 25
G1 Time [sec]
G2
-4 G3 Figure 8. Generators mech. Frequency for fault on grid connected case
Relative angle G [deg]
-6
B. Three phase to ground fault on the islanded case
-8
-5
experiencing the greatest change in values (see Fig. 12 and
G1
G2
13).
G3 Angle
-10 -4
G1
Relative angle G [deg]
G2
-6
G3
-15
-20 -10
-12
-25
-14
-30
0 5 10 15 20 25 -16
Time [sec]
Figure 9. Relative generator angles for fault on islanded case -18
0 5 10 15 20 25
Time [sec]
240
Figure 12 Relative generator angles on grid disconnected case
220
210
Internal Voltage E [V]
200
200
180
160
180
G1
140 G2
170 G3
G1
120 G2
G3 160
100
0 5 10 15 20 25 150
Time [sec]
Figure 10. Generators internal Voltage for fault on islanded case 140
0 5 10 15 20 25
Time [sec]
125
Figure 13 Generators internal Voltage on grid disconnected case
120
Generator Bus Voltage rms [V]
123
115 G1
122 G2
G3
110
Generator Bus Votage [V]
121
105
120
100 119
95 Vbus1 118
Vbus2 117
90
Vbus3
85 116
80
115
0 5 10 15 20 25
Time [sec] 114
0 5 10 15 20 25
Figure 11. Generators bus Voltage at fault on islanded case Time [sec]
Figure 14. Generators bus Voltage on grid-disconnected case
C. PCC main grid open switch fault D. Sever Three phase to ground fault on the islanded case
In this scenario, the main grid was suddenly disconnected from In this case, one of the generators was loaded to an angle of 35
the microgrid system. The results are presented in Fig. 12 – 14. degrees and then a fault was applied; the microgrid was
In this case, it can be observed that all the load angles, internal operating in an islanded mode. The system experiences a very
voltages, and bus voltages of the generators remained in stable low voltage profile during the fault. The results can be seen in
condition after the disconnection from the main grid. The Fig. 15 – 18. Fig. 15 shows a severe deviation in the angles of
microgrid can smoothly supply the loads in stand-alone the generators. The internal voltage of the generators
condition that explains why there was no deviation seen in the decreased drastically, for instance, Generator 1 endured more
plot of generation bus voltages (see Fig. 14). It could be seen than 50% of voltage drop during the fault (see Fig. 16). In
that after the disconnection all the generators’ load angle and addition, the bus voltages decreased sharply, e.g., the bus
internal voltages settled at a new value to make up for the voltage of Generator 1 decreased by about 63% of its initial
increase in demand on each of the generators with Generator 1 value; this is shown in Fig. 17. We noticed for this case that if
5
the fault in maintained and not cleared, the system starts IV. CONCLUSION
oscillating. This paper presents experimental results of transient stability
40 response of microgrids. The four scenarios are presented to
G1
20 G2 study the transient behavior of microgrids in different fault
G3
circumstances. The results prove that when a microgrid is
0
operating in islanded mode, it would be more vulnerable to
Relative Angle G [deg]
-20
faults and abnormal conditions. In two of case studies
-40 performed in this paper, a fault condition is applied when the
-60 microgrid was operated in islanded mode. In these cases, the
-80
system became unstable with high voltage drop and angle
deviation in the generators. On the other hand, in the two other
-100
scenarios implemented while the system was connected to the
-120 main grid, the voltage and angle of the generators remained in
-140
0 5 10 15 20 25
an acceptable range of operation and with the least deviation.
Time [sec] The results showed a stable operation of microgrid during and
Figure 15. Relative generator angles on sever three phase fault after the fault and prove the robustness in grid connected mode
250 operation.
G1
200 G2 REFERENCES
G3
Internal Volatge E [V]
110
2008
100 [6] A. H. K. Alaboudy , H. H. Zeineldin and J. L. Kirtley "Micro grid
90
stability characterization subsequent to fault-triggered islanding
incidents", IEEE Trans. Power Del., vol. 27, no. 2, pp.658 -669 2012
80
[7] F. Andrade , J. Cusido and L. Romeral "Transient stability analysis of
70 inverter-interfaced distributed generators in a micro grid system", Proc.
Vbus1
60 Vbus2
2014th Eur. Conf. Power Electron. and Applicat.(EPE 2011), pp.1 -10 2011
50
Vbus3 [8] C. Xinhe , P. Wei and T. Xisheng "Transient stability analyses of micro-
grids with multiple distributed generations", Proc.Int. Conf. Power Syst.
40
Technol. (POWERCON), 2010
30
0 5 10 15 20 25
[9] S. Krishnamurthy , T. M. Jahns and R. H. Lasseter "The operation of
Time [sec] diesel gensets in a CERTS micro grid", Proc. IEEE Power and Energy Soc.
Figure 17. Generators bus voltage on sever three phase fault General Meeting Conversion and Delivery of Elect. Energyin the 21st
Century, pp.1 -8 2008
[10] A. Elmitwally and M. Rashed "Flexible operation strategy for an
61.1 isolated PV-diesel micro grid without energy storage", IEEE Trans. Energy
61
Convers., vol. 26, no. 1, pp.235 -244 2011
[11] M. Zhixin , A. Domijan and F. Lingling "Investigation of micro grids
Mech Frequency [Hz]
60.9 with both inverter interfaced and direct AC-connected distributed energy
resources", IEEE Trans. Power Del., vol. 26, no. 3, pp.1634 -1642 2011
60.8
[12] M. Datta , T. Senjyu , A. Yona , T. Funabashi and K. Chul-Hwan "A
60.7 coordinated control method for leveling PV output power fluctuations of PV-
diesel hybrid systems connected to isolated power utility", IEEE Trans.
60.6 Energy Convers., vol. 24, no. 1, pp.153 -162 2009
60.5
f2 [13] Ritwik Majumder, “Some Aspects of Stability in Microgrids,” IEEE
f3
TRANS. ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013
60.4
0 5 10 15 20 25
Time [sec]
Figure 18. Generators mech. frequency