You are on page 1of 5

1

Experimental Transient Stability Analysis of


MicroGrid Systems: lessons learned
R. Belkacemi, Member, IEEE, S. Zarrabian, A. Babalola, Student Members, and R. Craven, Member
IEEE
Department of Electrical and Computer Engineering
Tennessee Technological University
Cookeville, TN 38505

 as active damping control [3] and frequency control with


Abstract—A Transient Stability Analysis of a low inertia voltage regulation after islanded mode operation [4] or smooth
microgrid system is presented in this paper. The analysis is islanding operation with state feedback control [5, 6].
performed on experimental data collected for different case Transient stability analysis is one the other main aspect of
scenarios of grid disturbances. The test bed consists of a
stability studies in microgrids. In fact, for renewable resources
reconfigurable 100kW MicroGrid system with more than 10
rotating generators, PV, and Wind penetration capabilities. Both with current and reactive power support limitations, it is
islanded and non-islanded situations are considered for a solid crucial to provide appropriate operation of microgrids after
three phase fault analysis and comparison. The paper also large disturbances through accurate transient studies. In [7],
presents the results of fault scenario when the rotating machines the concept of energy function has been proposed for studying
are pushed to an unstable region. The experimental results and the transient stability analysis of microgrids, while [8] presents
system behavior observed show interesting phenomena. The
MicroGrid showed higher resiliency for faults than expected even
transient stability studies considering both voltage source
if the relative angles are more than 160º and even if the fault is inverter based resources and traditional synchronous
sustained for a long time. generators in the model. Some researches carry out the
stability studies for different types of distributed resources, for
Index Terms— Experimental data, Microgrid, Test bed, Three instance, [9] demonstrates the stability analysis of a microgrid
phase fault, Transient Stability having diesel generators and [10-13] analyze the stability of
microgrids with PV-diesel integration.
I. INTRODUCTION One of the other stability aspects in microgrids is the small

I n recent years, centralized generating facilities are giving


away to smaller distributed generation or microgrids. These
microgrids encompass wide range of energy resources, such as
signal stability. Some effective methods have been proposed to
improve small signal stability in microgrids such as the use of
energy management systems, effective coordinated control of
combustion generator, photovoltaic, wind, and fuel cells that if DGs, addition of supplementary control loops, and use of
operated as an isolated network will give rise to numerous stabilizers for DGs. For voltage stability enhancement in micro
problems and challenges in terms of control and stability of the grids, the following methods have been previously
system because of the low inertia and intermittency of the investigated: Reactive compensation, load shedding, and
resources. Unlike traditional large scale grids, microgrids are voltage regulations with DGs [13].
very sensitive to any disturbances in the system and can easily Most of the work done on transient stability after major
go unstable because of the lack of inertia. disturbances in microgrids is based on simulations of
Microgrids can operate either connected to the main grid linearized or nonlinear models. In this work, we present some
(grid connected operation) or separately in stand-alone mode of experimental observations and analysis of a microgrid
operation (autonomous or islanded operation). Although this system under large disturbances. The analysis covers the
integration of distributed resources makes the system more islanded and non-islanded mode of operation. The results are
flexible from an operation and control point of view, it also very educative and meant to help researchers in the area
makes the power grid more vulnerable to oscillations resulting understand unusual behaviors in terms of stability.
from grid disturbances. Therefore, research into microgrid
stability is of great importance. For instance, authors of [1, 2] II. MICROGRID TESTBED
investigated the effect of loading structure and condition in Fault scenarios have been implemented on a real time
micro grid stability. Some literatures propose control methods testbed system including both hardware and software setups.
for mitigating the effect of some the causes of instability, such The system has been provided by Tennessee Technological
University Smart Grid Laboratory. The testbed system has the
This project is partly funded by the Center for Energy Systems Research, capability of running 100-bus power system with two-way
Tennessee Technological University, Cookeville, Tennessee. communication infrastructure. The hardware structure can be
.
set up either for micro-grid or smart grid applications and can

978-1-4673-8040-9/15/$31.00 ©2015 IEEE


2

accommodate any grid configuration with more than 20


rotating machines. The hardware infrastructure offers the
capability of integrating wind and solar energy at any bus on
the system.
The main hardware setup consists of power generators with
a rating of 11.5 kW, transmission lines, loads, measurement
devices, breakers, switches, and Data Acquisitions Cards
(DAQ).
LABVIEW and Visual Studio provided the software
interface platforms which are used for programming and
controlling the hardware setups through network shared Figure 2. Schematic of the Wind Turbine Emulator Setup

variables. In fact, the measurements from the real time system For the solar emulation, the photovoltaic power profile
are stored in shared variables and can be read from the emulation (PPPE) software automatically calculates solar array
software interface for control and programming purposes. In voltage and current profiles based on user-defined parameters.
Fig.1, a view of hardware and software of the test bed system These profiles are sequentially sent to a Magna-Power
is shown. For this experiment, a 9-bus microgrid system is Electronics power supply, which emulates defined
designed. characteristics. The output from the power supply is then fed
to an IGBT inverter for grid integration. Fig.3 show the PV
integration setup.

Figure 3. Solar integration setup

The SixPac™ from APS Inc. is a flexible, highly integrated


IGBT based power assembly with a wide range of
applications. The SixPac™ can be configured as a full bridge
or three-phase bridge inverter mounted on an air-cooled or
liquid-cooled heat sink.
Fig.4 shows the single line diagram of the MicroGrid. The
microgrid under study is a meshed network of 9-bus system
interconnected by 13 transmission lines. The Microgrid is grid
Figure 1. Hardware software setup connected to the power utility which is in this case Tennessee
Valley Authority. The connection to the utility side is done in
Induction machine with its rotor windings short circuited is hardware by using a phase lock approach. The frequency and
used as a wind turbine generator. The stator can be connected the voltage magnitude of the microgrid are controlled in a way
directly to the grid. The wind turbine model is implemented on to allow for synchronization (phase sequence and voltage
real time simulator RTDS/RSCAD then the output is fed to magnitude difference).
induction generator as shown in Fig.2.
3

210
G1
G2
200
G3

190

Internal Volatge E [V]


180

170

160

150

140

130

120
0 5 10 15 20 25
Time [sec]
Figure 6 Generators internal Voltage for fault on grid connected case
125

Figure 4. Single line diagram of the microgrid

Generator Bus Voltage rms [V]


120

III. TRANSIENT ANALYSIS


115

Stability analysis of different case fault scenarios is presented


in this section. 110
A. Three phase to ground fault on the grid connected case Vbus1
In this scenario, a three phase to ground fault was applied on Vbus2
105 Vbus3
Bus 8 of the system at t = 6 sec. The microgrid was connected
to the main grid via a PCC (Point of Common Coupling)
switch at Bus 9. The experimental results obtained are shown 100
0 5 10 15 20 25

in Fig. 5 - 8. The results show that there was not much Time [sec]
transient difference before and after the fault and there was Figure 7. Generators bus Voltage for fault on grid connected case
only a small disturbance at the time when the fault was applied 60.4
and after that the system returned to its pre-fault state in about f2
60.35 f3
2 sec. Fig. 5 shows the load angles of the generators. After
small deviation at the time of fault, each generator’s angle 60.3
Mech Frequency [Hz]

returned to its initial level. Fig. 6 and 7 show the generators’ 60.25
internal and bus voltages respectively. There was a small sag
60.2
in the internal voltages, but the bus voltage dip for generator 1
was considerable because it is closer to the fault (see Fig. 7). 60.15
The change in bus voltages was about 8%, 4%, and 3% for 60.1
generators 1, 2, and 3 respectively.
60.05

60
-2 0 5 10 15 20 25
G1 Time [sec]
G2
-4 G3 Figure 8. Generators mech. Frequency for fault on grid connected case
Relative angle G [deg]

-6
B. Three phase to ground fault on the islanded case
-8

-10 In this scenario, a three phase to ground fault was applied on


-12
Bus 8 at t = 5 sec while the system was on islanded mode
operation. The results obtained are shown in Fig. 9 – 11. Fig. 9
-14
shows the load angles of the generators for this scenario.
-16 Compare this to Fig. 5, it is obvious that there wasmore
-18
deviation in the load angle for the islanded case than for the
0 5 10
Time [sec]
15 20 25
grid-connected case. Moreover, by looking at Fig. 10, it can be
Figure 5 Relative generator angles for fault on grid connected case
clearly seen that there was a high internal voltage dip at the
time of the fault. Fig. 11 indicates that the bus voltages of the
generators went to a very low level during the fault. The bus
voltage of 1 decreased by 25% (0.25 p.u deviation in voltage).
4

-5
experiencing the greatest change in values (see Fig. 12 and
G1
G2
13).
G3 Angle

-10 -4
G1
Relative angle G [deg]

G2
-6
G3
-15

Realative Angle G [deg]


-8

-20 -10

-12
-25

-14

-30
0 5 10 15 20 25 -16
Time [sec]
Figure 9. Relative generator angles for fault on islanded case -18
0 5 10 15 20 25
Time [sec]
240
Figure 12 Relative generator angles on grid disconnected case
220
210
Internal Voltage E [V]

200
200

180

Internal Voltage E [V]


190

160
180
G1
140 G2
170 G3
G1
120 G2
G3 160

100
0 5 10 15 20 25 150
Time [sec]
Figure 10. Generators internal Voltage for fault on islanded case 140
0 5 10 15 20 25
Time [sec]
125
Figure 13 Generators internal Voltage on grid disconnected case
120
Generator Bus Voltage rms [V]

123
115 G1
122 G2
G3
110
Generator Bus Votage [V]

121
105
120

100 119

95 Vbus1 118
Vbus2 117
90
Vbus3
85 116

80
115
0 5 10 15 20 25
Time [sec] 114
0 5 10 15 20 25
Figure 11. Generators bus Voltage at fault on islanded case Time [sec]
Figure 14. Generators bus Voltage on grid-disconnected case

C. PCC main grid open switch fault D. Sever Three phase to ground fault on the islanded case
In this scenario, the main grid was suddenly disconnected from In this case, one of the generators was loaded to an angle of 35
the microgrid system. The results are presented in Fig. 12 – 14. degrees and then a fault was applied; the microgrid was
In this case, it can be observed that all the load angles, internal operating in an islanded mode. The system experiences a very
voltages, and bus voltages of the generators remained in stable low voltage profile during the fault. The results can be seen in
condition after the disconnection from the main grid. The Fig. 15 – 18. Fig. 15 shows a severe deviation in the angles of
microgrid can smoothly supply the loads in stand-alone the generators. The internal voltage of the generators
condition that explains why there was no deviation seen in the decreased drastically, for instance, Generator 1 endured more
plot of generation bus voltages (see Fig. 14). It could be seen than 50% of voltage drop during the fault (see Fig. 16). In
that after the disconnection all the generators’ load angle and addition, the bus voltages decreased sharply, e.g., the bus
internal voltages settled at a new value to make up for the voltage of Generator 1 decreased by about 63% of its initial
increase in demand on each of the generators with Generator 1 value; this is shown in Fig. 17. We noticed for this case that if
5

the fault in maintained and not cleared, the system starts IV. CONCLUSION
oscillating. This paper presents experimental results of transient stability
40 response of microgrids. The four scenarios are presented to
G1
20 G2 study the transient behavior of microgrids in different fault
G3
circumstances. The results prove that when a microgrid is
0
operating in islanded mode, it would be more vulnerable to
Relative Angle G [deg]

-20
faults and abnormal conditions. In two of case studies
-40 performed in this paper, a fault condition is applied when the
-60 microgrid was operated in islanded mode. In these cases, the
-80
system became unstable with high voltage drop and angle
deviation in the generators. On the other hand, in the two other
-100
scenarios implemented while the system was connected to the
-120 main grid, the voltage and angle of the generators remained in
-140
0 5 10 15 20 25
an acceptable range of operation and with the least deviation.
Time [sec] The results showed a stable operation of microgrid during and
Figure 15. Relative generator angles on sever three phase fault after the fault and prove the robustness in grid connected mode
250 operation.
G1
200 G2 REFERENCES
G3
Internal Volatge E [V]

[1] R. Kamel , A. Chaouachi and K. Nagasaka "Detailed analysis of micro-


grid stability during islanding mode under different load
150
conditions", Engineering, vol. 3, no. 5, pp.508 -516 2011
[2] D. P. Ariyasinghe and D. M. Vilathgamuwa "Stability analysis of micro
100 grids with constant power loads", Proc. IEEE Int.Conf. Sustainable Energy
Technol., 2008 (ICSET 2008), pp.279 -284 2008
[3] D. M. Vilathgamuwa , X. N. Zhang , S. D. G. Jayasinghe , B. S. Bhangu ,
50 C. J. Gajanayake and K. J. Tseng "Virtual resistance based active damping
solution for constant power instability in AC micro grids", Proc. 37th Annu.
0
Conf. IEEE Ind. Electron. Soc. (IECON 2011), pp.3646 -3651 2011
0 5 10 15 20 25 [4] H. Karimi , H. Nikkhajoei and R. Iravani "Control of an electronically-
Time [sec]
coupled distributed resource unit subsequent to an islanding event", IEEE
Figure 16. Generators internal Voltage on sever three phase fault Trans. Power Del., vol. 23, no. 1, pp.493 -501 2008
130 [5] R. Majumder , A. Ghosh , G. Ledwich and F. Zare "Control of parallel
converters for load sharing with seamless transfer between grid connected and
120
islanded modes", Proc.IEEE Power and Energy Soc. General Meeting,
Generator Bus Voltage rms [V]

110
2008
100 [6] A. H. K. Alaboudy , H. H. Zeineldin and J. L. Kirtley "Micro grid
90
stability characterization subsequent to fault-triggered islanding
incidents", IEEE Trans. Power Del., vol. 27, no. 2, pp.658 -669 2012
80
[7] F. Andrade , J. Cusido and L. Romeral "Transient stability analysis of
70 inverter-interfaced distributed generators in a micro grid system", Proc.
Vbus1
60 Vbus2
2014th Eur. Conf. Power Electron. and Applicat.(EPE 2011), pp.1 -10 2011
50
Vbus3 [8] C. Xinhe , P. Wei and T. Xisheng "Transient stability analyses of micro-
grids with multiple distributed generations", Proc.Int. Conf. Power Syst.
40
Technol. (POWERCON), 2010
30
0 5 10 15 20 25
[9] S. Krishnamurthy , T. M. Jahns and R. H. Lasseter "The operation of
Time [sec] diesel gensets in a CERTS micro grid", Proc. IEEE Power and Energy Soc.
Figure 17. Generators bus voltage on sever three phase fault General Meeting Conversion and Delivery of Elect. Energyin the 21st
Century, pp.1 -8 2008
[10] A. Elmitwally and M. Rashed "Flexible operation strategy for an
61.1 isolated PV-diesel micro grid without energy storage", IEEE Trans. Energy
61
Convers., vol. 26, no. 1, pp.235 -244 2011
[11] M. Zhixin , A. Domijan and F. Lingling "Investigation of micro grids
Mech Frequency [Hz]

60.9 with both inverter interfaced and direct AC-connected distributed energy
resources", IEEE Trans. Power Del., vol. 26, no. 3, pp.1634 -1642 2011
60.8
[12] M. Datta , T. Senjyu , A. Yona , T. Funabashi and K. Chul-Hwan "A
60.7 coordinated control method for leveling PV output power fluctuations of PV-
diesel hybrid systems connected to isolated power utility", IEEE Trans.
60.6 Energy Convers., vol. 24, no. 1, pp.153 -162 2009
60.5
f2 [13] Ritwik Majumder, “Some Aspects of Stability in Microgrids,” IEEE
f3
TRANS. ON POWER SYSTEMS, VOL. 28, NO. 3, AUGUST 2013
60.4
0 5 10 15 20 25
Time [sec]
Figure 18. Generators mech. frequency

You might also like