The design of an electrical system or a part of same implies Electrodynamic efforts between conductors
not only the selection of the structure itself, but also the In the design of bar support systems, we have to take into the
elements that form it. Among these, the insulators play a account the electrodynamic efforts caused by the throughput
fundamental role in the reduction of risks caused by dielectric of current. The greater efforts, to which the insulating
stress to acceptable values. supports have to be proportioned, are those due to short
The fundamental parameters by which we can identify an circuit currents. By means of the nomographs set out below, it
insulator are of two types: electrical and mechanical is possible to obtain the minimum bending breakage load
■ electrical parameter (which guarantee a safety level greater than or equal to 2.5) in
rated operating voltage the bar system, and consequently select the most suitable
rated insulation voltage insulating support
■ mechanical parameter
Minimum value of the bending breakage load

Nomograph 1
Determination of effort F for units of length

Data required: I = short circuit current


D = distance between phases

Example: Isc = 15 kA (in AC) D = 7 cm


result deducible from the nomograph: F > 150 daN/m

Short circuit in DC Short circuit in AC (Effective value)