Professional Documents
Culture Documents
Abstract - The application of differential protection has differential protection scheme. The paper will first define the
been shown to be effective in many applications within basics of differential protection and its importance in the
the Forest Product based industries. However, there are industrial power system. The paper will demonstrate the
some aspects of differential protection which need application of motor and transformer differential protection
special consideration. Some differential configurations schemes including step up/step down transformers used with
may be harmful to the systems to which they were variable frequency drives (VFD).
installed to protect. This paper will cover a few of the
basics surrounding typical differential applications. Also II. CURRENT TRANSFORMER FUNDAMENTALS
highlighted are some of the risk areas which are typically
overlooked when applying differential protection for Instrument transformers are a general classification used
certain applications. to identify devices that modify magnitudes or perform isolation
when used to monitor current and voltage. This isolation is
Index Terms – Differential Protection, Motor Differential intended to separate the utilization voltage or current from the
Protection, Magnetizing Current, Core Balance Differential, supply voltage or currents for both operator and device safety.
Transformer Protection, Differential Relay This section will focus on current instrument transformers
better known as CTs. Typically the secondary of a CT will be
I. INTRODUCTION rated 5 [A] or 1 [A] so that they can be used in conjunction
with metering or in the case of differential protection, a
The electric distribution system will experience various protective relay. This paper will focus on magnetic core CTs.
types of faults throughout its designed lifetime. These faults CTs are not a perfect transformation device and will incur
could be due to internal or external sources and may be losses from resistance of the copper wire and stray
temporary or permanent. inductance of the copper windings and core. The largest
Internal faults may cause thermal effects when high fault losses are due to current carrying copper windings and the
current flow results in system equipment overheating. This magnetic core that carries the flux to magnetize the circuit.
can include cables, machines, and transformer windings. This Fig. 1 depicts a model for a magnetic core CT from the
overheating may cause excessive insulation damage and secondary side. It can be seen that the impedance
possibly melt the winding conductors. Additional internal represented by and + cause current and voltage
sources of electrical faults may also be caused by voltage losses within the circuit. [2]
sags, switching surges, and over voltages. Voltage sags may
result in rotating machinery stalling due to lack of ride through I1
capability. Switching surges may cause over current
conditions due to the large inductive load created by motors. I’2 jX1 R1 I2
External faults, or surges from outside the system, are mainly
due to external phenomena such as lighting strikes or physical
damage to the system (i.e. a downed tree).
Due to the possibility of internal and external faults, the
distribution system must be instrumented with protective ZM Zb
devices for continuous monitoring. These protective devices
should monitor for the electrical status of various system
components (circuit breakers, contactors, motors,
transformers, generators, feeders, etc.) and de-energize them
when they are the cause of abnormal operating conditions [1].
The industrial power system, which is a subset of the
electric distribution system, is subject to the same Fig. 1 CT Equivalent Circuit Model
vulnerability. This paper will focus on internal faults within the Additionally, the burden, , of the device to receive the
distribution system that can be protected by using a signal produced by the CT, i.e. the protective relay, must be
within a tolerance described by the CT manufacturer to obtain against symmetrical and unsymmetrical faults. The
accurate measurements. The burden of the CT is defined as corresponding current that would enter the differential branch
the impedance produced by the protective device itself, in would be defined by equation (1).
addition to the impedance of the wiring to the secondary of the
current transformer [3]. 1
∆
=
−
(1)
III. BASICS OF DIFFERENTIAL PROTECTION
CT CT
Using simple input and output current measurements,
introduces a zone where protection is not present, (Fig. 2).
The zones of protection are defined by the placement of the CT CT
current transformers and their interconnection and interaction Protection Zone
with each other. In Fig. 2 the current transformers are CT CT
providing individual current feedback for the current measured
at the input, Zone A, and separately the output currents, Zone
B. There is no direct relationship to any loss or gain of current Iain/n Iaout/n
between the two zones. Rst
87
* Only one of three phases
Neutral shown
Iin Iout
Power System Fig. 4 Differential Protection Scheme
Zone A Zone A Component Zone B Zone B
CT
When differential protection is only needed for line to
CT
potential earth (PE), Fig. 4 can be modified to use only one 87
(differential) element and tying the secondaries of all current
transformers together. By connecting the current
Iout/n
Iin/n transformers in this fashion, the current flowing through the 87
element will be the residual difference from input and output
current transformers, i.e. the amount of current flowing to PE.
This can be seen in Fig 5. These types of schemes are
Fig. 2 Simple Zone Based Current Protection known as high impedance differential protection schemes.
There are additional types of differential protection known as
Differential protection is based on comparing phase low impedance differential protection, and voltage differential
currents entering the protective device Iin with the current protection. These schemes are often used on transformer
leaving the protective element Iout on each electrical phase circuits. There are multiple references on the basics
(Fig. 3). During normal operating conditions or with a fault surrounding these circuits and why these types of schemes
outside the protection device, the two currents are are utilized in industry [4] [5].
approximately equal. If there is a difference between the two
CT CT
currents, a fault is detected and the fault current is
proportional to this difference. Iain/n Iaout/n
A sample of both Iin and Iout is gathered by current CT Protected CT
transformers with a turns ratio n. As a result, the two currents
that are measured by this protection scheme are Iin/n and
Ibin/n Element Ibout/n
CT CT
Iout/n. This scheme can be seen in Fig 3.
Icin/n Icout/n
Iin Iout Ires-in Ires-out
Rst
Protection Zone
CT CT
87 ΔIres
Neutral
Iin/n Iout/n
Fig. 5 Differential Protection Scheme for High Impedance
Ground Fault
(1/n)(Iin-Iout)
In transformer applications related to motor applications,
Fig. 3 Basics of Differential Protection there are several factors that need to be considered in
relationship to differential protection:
Each phase of differential protection utilized a stabilizer • Magnetizing inrush currents
resistor Rst in series with a differential protection element • Over-excitation
(87). By connecting the differential elements, stabilizing • Current transformer saturation
resistors, and current transformers in the fashion depicted in • Phase relationships
Fig. 4, the resulting protection scheme will be able to protect • Multi-winding transformer applications
causing nuisance trips. To avoid this situation, the level of branch. This value takes into account the resistance of the
differential protection may need to be adjusted to be much current transformer itself in addition to the resistance of the
less sensitive or an additional time delay may be injected to wire that connects the secondary of the current transformer to
extend a ride through period for specific problem times, such the differential element. I2SC corresponds to the short circuit
as during motor start cycles. current at the secondary of the current transformer. This can
In this regard, the summation differential method is better be calculated by dividing the primary short-circuit current by
than the core balancing differential method because the motor the turns ratio of the current transformer. Finally, Iset is
cables are also included in the differential protection zone. defined as the set point of the differential relay. This value
should be selected to be higher than the nominal current that
IL1 would flow within the differential branch in order to prevent
IL2 unwanted tripping.
IL3
M
B. Sufficient Voltage at Differential Branch
Ph A Ph B Ph C
Flux Density
Saturation Region
differential protection that will activate when differential E. Current Transformer Selection Summary
currents are above the protection scheme set point.
In order to provide differential protection to rotating assets
C. Limiting Voltage at current transformer Secondary such as motors, generators, or transformers the previous
rules of thumb should be followed in order to create an
During times of a large fault within the protection zone, (i.e. effective protection scheme. In order to have an effective
three phase bolted fault), there will be a large short-circuit differential scheme, proper stabilizing resistor sizes must be
current produced inside the protection zone. At this time, the calculated in order to prevent unwanted tripping. Current
current transformer(s) selected will be highly saturated and transformers must also be sized so that the knee point of the
high voltage (HV) peaks may occur. These HV peaks may magnetizing curve is selected so to keep the current
permanently damage the current transformer(s) if not sized or transformer within the linear region of operation as much as
manufactured to handle these high voltages. In order to possible. Finally, the minimum fault current must be
prevent damage to current transformer(s), a non-linear calculated. An effective differential protection scheme will
resistor may be connected in parallel with the restraint resistor satisfy equations (2), (3), and (4).
and differential element to limit the voltage at the current
transformer’s terminals. This can be seen in Fig. 10. V. CURRENT TRANSFORMER SELECTION
Iin
The output characteristics of typical iron core current
Iout
transformers is that they are optimized when they are used
Protection Zone near their nominal design values. When used with very low
CT CT end or very high end currents, they are far from an ideal
transformer. For overcurrent and differential protection, where
high or low currents must be measured and checked, the
Iin /n Iout/n protection relay in combination with the actual performance of
current transformers at high and low end excitation levels
must be accurate to ensure correct protection functionality.
The difference between the ideal secondary current and the
actual secondary current, under steady-state conditions, is
defined as the composite error. The composite error includes
Rs amplitude and phase errors and also the effects of any
Rnon possible harmonics in the excitation current. The standard
rating and accuracy class characteristics for current
87
transformers, is generally defined as the rated frequency with
rated burden connected, the amplitude error, phase error and
composite error.
Fig. 10 Differential Protection with Non-linear (variable)
Resistor A. Current transformer saturation
The standard accuracy limit factors are 5, 10, 15, 20 and caused by internal faults and that caused by magnetizing
30. The actual accuracy limit factor depends on the actual inrush or over excitation. Typically the blocking element has
burden applied to the current transformer. an independent and settable threshold level. Most new
When the current through a current transformer equals and generation microprocessor based relays also include a fifth-
exceeds the nominal operating range, there may be enough harmonic element to produce an over excitation trip if fifth-
secondary differential current to trip a relay although there is harmonic current is detected for a settable time. Typically
really no in zone fault. This is because each current transformer over-excitation causes about 20-50% of fifth
transformer is unique and thus does not behave equally when harmonic component compared to the measured phase
approaching saturation. To avoid false trips caused by heavy currents.
through faults, the actual accuracy limit factor kA of the .
current transformers should exceed the relative setting ISET There are also some microprocessor based relays which
of the non-stabilized differential stage. include the interrogation of the second harmonic content for
Some protective relays include overcurrent elements that transformer inrush. The second harmonic function
can operate using a type of mathematic adaptive current interrogates the inrush current of a transformer and provides a
algorithm when the relay detects when a current transformer restraint or blocking function to maintain the integrity of the
is in a severely saturated condition. These algorithms are differential protection during inrush events. Generally the
typically only used for phase instantaneous overcurrent recommended setting for this protection is around 15-20% of
elements and have other limitations on their application to fundamental current, but this should be adjusted based on
corresponding pickup settings. These protective algorithms actual operating practices. There are situations where this
are always based solely only on the fundamental system setting may be well below that 20% level. As the second
frequency. harmonic current setting is lowered, the inrush restraint level
is also lower which may impact the tripping time of the
VI. DIFFERENTIAL RELAYING AND PROTECTION differential element for fault conditions
CHARACTERISTICS
VII. MAGNETIC CORE CURRENT TRANSFORMERS AND
The setup for differential protection typically includes at VARIABLE FREQUENCY
least two setting variables in regards to the rate of current
biasing required in relationship to the percentage of the pickup Most magnetic core current transformers are designed for
current settings. This is typically referred to as a dual slope an operating range between 40 and 400 Hz. The designs are
setting and can be seen in Fig. 11. The first part of the slope typically optimized for 50 or 60 Hz depending on their
is used to compensate for the apparent differential current manufacturing origin or specifications. Most of these types of
caused by things like tap changers. For example, a 19 current transformers can be used for frequencies lower than
position tap changer ±9x1.67% in its max/min position gives a 40 Hz but only with very careful consideration of the particular
setting 9x1.67%=15%. The start of the second slope and its situation and application. The capability of any ferromagnetic
steepness are rule of thumb values. The steepness and thus current transformers is proportional to the frequency of the
the slope and selectivity is a function of the level of protection current being measured. If the current transformer is designed
required. for an optimal 60 Hz, and current at lower frequencies are
applied and measured, the current transformer’s output drive
capability will fall proportionally to the frequency being
applied. This means that the burden on the current
transformer secondary must go down in proportion to
frequency to maintain secondary output accuracy. This
burden must also include the winding resistance of the current
Pickup Current Setting
Time
electric machines has been suggested in standards such as Interrupting
the [10] for quite some time. In fact, this recommendation Rating
began well before the introduction of vacuum switching
technologies and microprocessor based relays. Circuit Breaker Trip
Early switching devices, used for motor control, were air Characteristic Curve
blast (break) style devices, (fig. 9). These devices were very
large electro-mechanical switching mechanisms. Because of
their inherent size, they were not the fast switching devices
we know today, having opening times in the range of 6-15
Current
cycles. So getting these devices open as fast as possible was
very important to prevent extensive motor damage. Getting Fig. 13 Typical Circuit Break Trip Curve and Interrupting
the load offline quickly, in the event of a phase to phase fault, Ratings
is the intent of differential protection.
The newer switching technologies now include vacuum Vacuum contactors, on the other hand, due to their smaller
circuit breakers and fused vacuum contactors. As with the size, can open quite rapidly. However, unlike a circuit breaker,
older electromechanically switching devices, circuit breakers vacuum contactors have a very low current interrupting
still require a given amount of time to open their contacts and capability when compared to that of a circuit breaker. It is
disconnect current flow, in the range of 3-8 cycles. common for medium voltage vacuum contactors to have
interrupting capabilities from 4000 to 6000A. This is the
reason vacuum contactors are almost always used in
coordination with primary medium voltage fuses. This primary
fusing provides the short circuit interrupting capability for the
contactor fuse combination. Medium voltage power fuses are
able to quickly clear high levels of fault current within ¼ to ½
cycle.
IX. CONCLUSIONS
The use of differential protection on critical motor or
transformer applications does require some review of the
Contactor control system to which it is being applied. Traditional breaker
Interrupting control systems, where differential protection is used to
Rating reduce the potential damage to the connected load, has
significant practical value. Special care is required on the
application of differential protection where the control is by a
fused vacuum contactor. Vacuum contactors typically have a
Current relatively low interrupting capability. They should not be
Fig. 16 Proper Coordination of a Vacuum Contactor with configured to open under current conditions higher than their
Power Fuses interrupting rating. Always confer with the vacuum contactor
and/or controls supplier to validate control requirements of this
The three interrupters of the vacuum contactor, may be type.
placed in a situation where they must interrupt currents higher Care must be taken when magnetic core style current
than their designed maximums. In this case, there is a high transformers are applied to the output of any variable
frequency controller. Unpredictable characteristics may result
from applications at frequencies outside the design control and protection systems, arc resistant equipment and
specification for the magnetic core current transformer. It may infrared technologies. Several of his papers have been
be possible to apply magnetic core current transformers at published in the IEEE IAS Transactions and the IAS
frequencies lower than their design recommendation, but magazine. He is a Fellow member of the IEEE, the Industry
special relay settings will be required to facilitate the varying Application Society and is actively involved with the IEEE Pulp
outputs from the current transformers. and Paper Industry Committee, serving on its main executive
Special differential protection schemes require a full review board, its conference committee and on several sub-
by a qualified protection engineer. Too often untrained committees. He serves on several other technical groups and
personnel, who are not familiar with the settings of the participated on the local planning committees for the 2011
protection devices or of the full system configuration, enter IEEE-PCIC and 2002 IEEE-PPIC. He was won several IEEE
settings which permit a trip free environment but place the paper awards and was awarded a Meritorious Service Award
overall system and critical equipment in jeopardy. from the IEEE Pulp and Paper Industry Committee (PPIC) of
which he now leads as the committee chairman. He also sits
X. REFERENCES on the IEEE IAS Executive Board as the chairman of the
Process Industries Department. Mr. Kay is a Certified
[1] Sallam, Abdelhay A., and Om P. Malik. “Electric Engineering Technologist, in the province of Ontario.
Distribution Systems”. Hoboken: IEEE, 2011. Print.
[2] Pansini, Anthony J., “Guide to Electrical Power David C. Mazur (S’07, M’12), works as a global technical
Distribution Systems”. Lilburn, GA: Fairmont, 2005. Print. consultant for Rockwell Automation in Milwaukee, WI with a
[3] Horowitz, Stanley H., “Power System Relaying”. current focus on SCADA communications and substation
Chichester, UK: John Wiley & Sons, 2014. Print. automation. His experience includes the development of
[4] Mozina, C.J., "Protection of Power Plant Transformers regenerative variable frequency drive technology. David was
using Digital Technology," Transmission and Distribution engaged in the development of technology for time
Conference, 1999 IEEE , vol.1, no., pp.421,432 vol.1, synchronized continuous casters for the steel industry. David
11-16 Apr 1999, doi:10.1109/TDC.1999.755388 received his B.S. EE degree summa cum laude and first in his
[5] Mozina, C.J., "Protection and Commissioning of class from Virginia Polytechnic Institute and State University,
Multifunction Digital Transformer Relays at Medium Blacksburg, VA in 2011. David graduated with his M.S. EE
Voltage Industrial Facilities," Industry Applications, IEEE degree in 2012 for his work based on rotor angle
Transactions on, vol.41, no.6, pp.1420,1429, Nov.-Dec. measurement of synchronous machines from Virginia
2005, doi: 10.1109/TIA.2005.858278IEEE, Polytechnic Institute and State University. He graduated with
[6] Sevov, L., Kennedy, S., Paes, R., Ostojic, P., Differential the Ph.D. in Mining Engineering in September 2013 for his
Protection for Medium Voltage Pulse Transformers, work with automation and control of the IEC 61850 standard.
Petroleum and Chemical Industry Technical Conference David is an active member of the IEEE IAS and serves as
(PCIC), 2014 IEEE, DOI: working group chair for the Communication-Based Protection
10.1109/PCICon.2014.6961882 Publication Year: 2014, of Industrial Applications Working Group. He also serves as a
Page(s): 173-184. member of the Mining Industry Committee (MIC) as well as
[7] BS 3938:1973, British Standard, Specification for the Industrial and Commercial Power Systems Committee
Current Transformers, ISBN:0580073092 (I&CPS). David is also an active voting member of the IEEE
[8] Std. C37.110, IEEE Guide for the Application of Current Standards Association (SA).
Transformers used for Protective Relaying Purposes,
ISSN:0885-8977, DOI:10.1109/61.736693 Kenneth D. Mazur received his BSEE West Virginia
[9] IEEE, PC57.13-2008, Standard Requirements for University 1977. Ken has worked for United States Steel,
Instrument Transformers, ISBN:978-0-7381-5411-4, serving as a field construction engineer for 9 years before
DOI:10.1109/IEEESTD.2008.4581634 moving to Rockwell Automation. During his tenure at
[10] Std. 242-2001, IEEE Recommended Practice for Rockwell, Ken has held the roles of: lead project engineer,
Protection and Coordination of Industrial and field service engineer, PLC area manager, and account
Commercial Power Systems (IEEE Buff Book), E- manager. He has 25 plus years in design and construction
ISBN:978-0-7381-2845-0, experience in process control facilities.
DOI:10.1109/IEEESTD.2001.93369
[11] Kay, J. A., Selection, Application, and Interchangeability
of Medium-Voltage Power Fuses in Motor Control
Centers, IEEE Transactions on Industry Applications,
VOL. 42, NO. 6, pp1574-1581
NOVEMBER/DECEMBER 2006.