All Forces are In kN, kNm, Stress in N/sqmm & Dimension are in mm.
Code References
ACI 318M:2011
Sr.No. Item Clause / Table
1. Ptmax : 10.3.5
2. Ptmin : 10.5.1
3. Vc : 11.2
4. Asv : 11.4.7.2
5. Min Shear Reinf : 11.4.6
Max Stirrup
6. : 11.4.5.1
Spacing
Shear Reinf -
7. : 11.5.3.5
Torsion
Side Face
8. : 10.6.7
Reinforcement
9. Tcr : 11.5.1
Group : G1
Beam No : B1
Analysis Reference (Member) 14.4m : 362
Beam Length : 5729.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 4 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 5 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 6 of 179
Group : G1
Beam No : B2
Analysis Reference (Member) 14.4m : 363
Beam Length : 5209.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 7 of 179
Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement calculated at a
C = As (flex) =
given section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 600 mm
Spc2 = 318 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 8 of 179
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G1
Beam No : B3
Analysis Reference (Member) 14.4m : 364,1758
Beam Length : 6929.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 9 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 10 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 120 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 120 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G1
Beam No : B4
Analysis Reference (Member) 14.4m : 365
Beam Length : 7139.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 11 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 12 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
= 120 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 120 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 13 of 179
Spacing Criteria
Group : G1
Beam No : B5
Analysis Reference (Member) 14.4m : 366,1771
Beam Length : 8439.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 14 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 15 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
= 120 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 120 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 16 of 179
Group : G1
Beam No : B6
Analysis Reference (Member) 14.4m : 367
Beam Length : 5999.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 17 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 18 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G1
Beam No : B7
Analysis Reference (Member) 14.4m : 368
Beam Length : 6809.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 19 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 20 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G2
Beam No : B8
Analysis Reference (Member) 14.4m : 370
Beam Length : 5729.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 21 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 22 of 179
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 16 16 16
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 500 500 500
Asv Reqd (sqmm) 1143.73 500 885.242
SCalc (mm) 100 300 100
SPrv (mm) 100 300 100
Av Total Prv (sqmm) 4021.2 1340.4 4021.2
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G2
Beam No : B9
Analysis Reference (Member) 14.4m : 371
Beam Length : 5209.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 23 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 24 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 25 of 179
Group : G2
Beam No : B10
Analysis Reference (Member) 14.4m : 372
Beam Length : 6929.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 26 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 27 of 179
Spc4=(X1+Y1)/4 = 315 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G2
Beam No : B11
Analysis Reference (Member) 14.4m : 373
Beam Length : 7139.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 28 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 29 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
Skin reinforcement
Spacing Criteria
Group : G2
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 30 of 179
Beam No : B12
Analysis Reference (Member) 14.4m : 374
Beam Length : 8439.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 31 of 179
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 32 of 179
Spacing Criteria
Group : G2
Beam No : B13
Analysis Reference (Member) 14.4m : 375
Beam Length : 5999.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 33 of 179
Basic
Spc1 = 600 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 34 of 179
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G2
Beam No : B14
Analysis Reference (Member) 14.4m : 376
Beam Length : 6809.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 35 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 36 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 37 of 179
Group : G3
Beam No : B15
Analysis Reference (Member) 14.4m : 481
Beam Length : 6930 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 38 of 179
Basic
Spc1 =d/2 = 315 mm
Spc2 = 300 mm
Skin reinforcement
Group : G3
Beam No : B16
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 39 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 40 of 179
Basic
Spc1 = 500 mm
Spc2 = 268 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 158 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 41 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G3
Beam No : B17
Analysis Reference (Member) 14.4m : 483
Beam Length : 8440 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 42 of 179
Basic
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 43 of 179
Spc1 = 500 mm
Spc2 = 268 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 158 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G3
Beam No : B18
Analysis Reference (Member) 14.4m : 473
Beam Length : 5999.99 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 44 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 45 of 179
Stirrup Rebar 16 16 16
Asv Torsion (sqmm) 699.018 699.018 699.018
Av Total Reqd (sqmm) 699.02 699.02 699.02
Asv Reqd (sqmm) 699.018 699.018 699.018
SCalc (mm) 100 265 265
SPrv (mm) 100 265 100
Av Total Prv (sqmm) 4021.2 1517.43 4021.2
Basic
Spc1 = 500 mm
Spc2 = 268 mm
For Torsion
(X1 = 430, Y1 = 630)
Spc3 = X1 = 430 mm
Spc4=(X1+Y1)/4 = 265 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 158 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 46 of 179
Group : G4
Beam No : B19
Analysis Reference (Member) 14.4m : 385
Beam Length : 5729.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 47 of 179
Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement calculated at a
C = As (flex) =
given section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 700 mm
Spc2 = 393 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 48 of 179
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G4
Beam No : B20
Analysis Reference (Member) 14.4m : 386
Beam Length : 5209.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 49 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 50 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 51 of 179
Spacing Criteria
Group : G5
Beam No : B21
Analysis Reference (Member) 14.4m : 387
Beam Length : 1897 mm
Breadth (B) : 1000 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 4384.01 kNm
As,min (flex) (B) : 3100 sqmm
As,nominal (Bn) : 1209 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 52 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 53 of 179
Basic
Spc1 = 1000 mm
Spc2 = 468 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
Group : G6
Beam No : B22
Analysis Reference (Member) 14.4m : 391
Beam Length : 6809.98 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 54 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 55 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 56 of 179
Spacing Criteria
Group : G7
Beam No : B23
Analysis Reference (Member) 14.4m : 484
Beam Length : 6930 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 57 of 179
Tcr/4 (kNm) - - - - - -
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 409.5 409.5 409.5 409.5 1310.72 2444.79
AstPrv (sqmm) 804.24 804.24 804.24 804.24 1963.48 3217
Reinforcement 4-#16 4-#16 4-#16 4-#16 4-#25 4-#32
Basic
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 58 of 179
Skin reinforcement
Group : G7
Beam No : B24
Analysis Reference (Member) 14.4m : 485
Beam Length : 7139.99 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 59 of 179
Basic
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 60 of 179
Spc1 = 500 mm
Spc2 = 268 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 158 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G7
Beam No : B25
Analysis Reference (Member) 14.4m : 486
Beam Length : 8440 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 61 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 62 of 179
Vs (kN) - - -
D+L 60.35 50.91
V (kN)
Mh (kNm) 255.52 896.23
Ms (kNm) 375.41 375.41
Sway-Right (kN) 102.89 214.15
Sway-Left (kN) 141.34 30.08
Vu-Sway (kN) 141.34 214.15
Vud (kN) 141.34 214.15
Av (sqmm) 416.67 416.67 416.67
Tu (kNm) 5.01 5.01 5.01
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 16 16 16
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 416.67 416.67 416.67
Asv Reqd (sqmm) 416.667 416.667 416.667
SCalc (mm) 100 265 100
SPrv (mm) 100 265 100
Av Total Prv (sqmm) 4021.2 1517.43 4021.2
Basic
Spc1 = 500 mm
Spc2 = 268 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 158 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 63 of 179
Group : G7
Beam No : B26
Analysis Reference (Member) 14.4m : 474
Beam Length : 5999.99 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 64 of 179
Basic
Spc1 = 500 mm
Spc2 = 268 mm
For Torsion
(X1 = 430, Y1 = 630)
Spc3 = X1 = 430 mm
Spc4=(X1+Y1)/4 = 265 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 65 of 179
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 158 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G8
Beam No : B27
Analysis Reference (Member) 14.4m : 400
Beam Length : 5729.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 66 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 67 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G8
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 68 of 179
Beam No : B28
Analysis Reference (Member) 14.4m : 401
Beam Length : 5209.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 69 of 179
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 70 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G8
Beam No : B29
Analysis Reference (Member) 14.4m : 402
Beam Length : 6929.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 71 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 72 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G8
Beam No : B30
Analysis Reference (Member) 14.4m : 403
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 73 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 74 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 75 of 179
Group : G8
Beam No : B31
Analysis Reference (Member) 14.4m : 404
Beam Length : 8439.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 76 of 179
Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement calculated at a
C = As (flex) =
given section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 77 of 179
Spacing Criteria
Group : G8
Beam No : B32
Analysis Reference (Member) 14.4m : 405
Beam Length : 5999.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 78 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 79 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 80 of 179
Group : G8
Beam No : B33
Analysis Reference (Member) 14.4m : 406
Beam Length : 6809.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 81 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 82 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G9
Beam No : B34
Analysis Reference (Member) 14.4m : 415
Beam Length : 5729.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 83 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 84 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G9
Beam No : B35
Analysis Reference (Member) 14.4m : 416
Beam Length : 5209.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 85 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 86 of 179
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 16 16 16
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 500 500 500
Asv Reqd (sqmm) 1092.323 500 1442.367
SCalc (mm) 100 300 100
SPrv (mm) 100 300 100
Av Total Prv (sqmm) 4021.2 1340.4 4021.2
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G9
Beam No : B36
Analysis Reference (Member) 14.4m : 417,1784
Beam Length : 6929.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 87 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 88 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 150 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 150 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 89 of 179
Group : G9
Beam No : B37
Analysis Reference (Member) 14.4m : 418
Beam Length : 7139.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 90 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 91 of 179
Spc4=(X1+Y1)/4 = 315 mm
= 120 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 120 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G9
Beam No : B38
Analysis Reference (Member) 14.4m : 419,1797
Beam Length : 8439.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 92 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 93 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
For Torsion
(X1 = 530, Y1 = 730)
Spc3 = X1 = 530 mm
Spc4=(X1+Y1)/4 = 315 mm
= 150 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 182 mm
Spc7 = 150 mm
Provided Spacing = 150 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 94 of 179
Spacing Criteria
Group : G9
Beam No : B39
Analysis Reference (Member) 14.4m : 420
Beam Length : 5999.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 95 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 96 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G9
Beam No : B40
Analysis Reference (Member) 14.4m : 421
Beam Length : 6809.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 97 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 98 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 99 of 179
Group : G10
Beam No : B41
Analysis Reference (Member) 14.4m : 414
Beam Length : 3909.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 100 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 101 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G10
Beam No : B42
Analysis Reference (Member) 14.4m : 1733,399
Beam Length : 10304.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 102 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 103 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 120 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 120 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G10
Beam No : B43
Analysis Reference (Member) 14.4m : 1731,384
Beam Length : 10624.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 104 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 105 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 106 of 179
Spacing Criteria
Group : G10
Beam No : B44
Analysis Reference (Member) 14.4m : 369
Beam Length : 3589.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 107 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 108 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Group : G11
Beam No : B45
Analysis Reference (Member) 14.4m : 422
Beam Length : 3909.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 109 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 110 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G11
Beam No : B46
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 111 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 112 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 113 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G11
Beam No : B47
Analysis Reference (Member) 14.4m : 392
Beam Length : 10624.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 114 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 115 of 179
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 16 16 16
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 500 500 500
Asv Reqd (sqmm) 500 500 500
SCalc (mm) 100 300 100
SPrv (mm) 100 300 100
Av Total Prv (sqmm) 4021.2 1340.4 4021.2
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 116 of 179
Group : G11
Beam No : B48
Analysis Reference (Member) 14.4m : 377
Beam Length : 3589.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 117 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 118 of 179
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Group : G12
Beam No : B49
Analysis Reference (Member) 14.4m : 423
Beam Length : 3909.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 119 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 120 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
Group : G12
Beam No : B50
Analysis Reference (Member) 14.4m : 408
Beam Length : 10304.98 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 121 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 122 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 123 of 179
Spacing Criteria
Group : G12
Beam No : B51
Analysis Reference (Member) 14.4m : 393
Beam Length : 10624.98 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 124 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 125 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G12
Beam No : B52
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 126 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 127 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 128 of 179
Skin reinforcement
Spacing Criteria
Group : G13
Beam No : B53
Analysis Reference (Member) 14.4m : 430
Beam Length : 7368.99 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 129 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 130 of 179
Basic
Spc1 = 500 mm
Spc2 = 268 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 158 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 131 of 179
Group : G13
Beam No : B54
Analysis Reference (Member) 14.4m : 429
Beam Length : 7116.98 mm
Breadth (B) : 500 mm
Depth (D) : 700 mm
Effective Depth (d) : 630 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1005.9 kNm
As,min (flex) (B) : 1050 sqmm
As,nominal (Bn) : 409.5 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 132 of 179
Basic
Spc1 = 500 mm
Spc2 = 268 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 158 mm
Spc5 = 150 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 133 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G14
Beam No : B55
Analysis Reference (Member) 14.4m : 424
Beam Length : 3909.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 134 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 135 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
For Torsion
(X1 = 630, Y1 = 930)
Spc3 = X1 = 630 mm
Spc4=(X1+Y1)/4 = 390 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 232 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 136 of 179
Spacing Criteria
Group : G15
Beam No : B56
Analysis Reference (Member) 14.4m : 438
Beam Length : 2950.99 mm
Breadth (B) : 1000 mm
Depth (D) : 1200 mm
Effective Depth (d) : 1130 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 6472.36 kNm
As,min (flex) (B) : 3766.67 sqmm
As,nominal (Bn) : 1469 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 137 of 179
Basic
Spc1 = 1000 mm
Spc2 = 518 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 138 of 179
For Torsion
(X1 = 930, Y1 = 1130)
Spc3 = X1 = 930 mm
Spc4=(X1+Y1)/4 = 515 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 282 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
Group : G16
Beam No : B57
Analysis Reference (Member) 14.4m : 394
Beam Length : 3492.99 mm
Breadth (B) : 1000 mm
Depth (D) : 1200 mm
Effective Depth (d) : 1130 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 139 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 140 of 179
Basic
Spc1 = 1000 mm
Spc2 = 518 mm
For Torsion
(X1 = 930, Y1 = 1130)
Spc3 = X1 = 930 mm
Spc4=(X1+Y1)/4 = 515 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 282 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 141 of 179
Spacing Criteria
Group : G17
Beam No : B58
Analysis Reference (Member) 14.4m : 379
Beam Length : 3589.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 142 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 143 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
For Torsion
(X1 = 630, Y1 = 930)
Spc3 = X1 = 630 mm
Spc4=(X1+Y1)/4 = 390 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 232 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 144 of 179
Group : G18
Beam No : B59
Analysis Reference (Member) 14.4m : 425,437
Beam Length : 6860.98 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 145 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
For Torsion
(X1 = 630, Y1 = 930)
Spc3 = X1 = 630 mm
Spc4=(X1+Y1)/4 = 390 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 146 of 179
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 232 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G19
Beam No : B60
Analysis Reference (Member) 14.4m : 395,380
Beam Length : 7082.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 147 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 148 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
For Torsion
(X1 = 630, Y1 = 930)
Spc3 = X1 = 630 mm
Spc4=(X1+Y1)/4 = 390 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 232 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 149 of 179
Spacing Criteria
Group : G20
Beam No : B61
Analysis Reference (Member) 14.4m : 426
Beam Length : 3909.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 150 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 151 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
Group : G21
Beam No : B62
Analysis Reference (Member) 14.4m : 432
Beam Length : 2935.99 mm
Breadth (B) : 1000 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 152 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 153 of 179
Basic
Spc1 = 1000 mm
Spc2 = 468 mm
For Torsion
(X1 = 930, Y1 = 930)
Spc3 = X1 = 930 mm
Spc4=(X1+Y1)/4 = 465 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 232 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 154 of 179
Skin reinforcement
Spacing Criteria
Group : G22
Beam No : B63
Analysis Reference (Member) 14.4m : 396
Beam Length : 3507.99 mm
Breadth (B) : 1000 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 4384.01 kNm
As,min (flex) (B) : 3100 sqmm
As,nominal (Bn) : 1209 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 155 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 156 of 179
Basic
Spc1 = 1000 mm
Spc2 = 468 mm
For Torsion
(X1 = 930, Y1 = 930)
Spc3 = X1 = 930 mm
Spc4=(X1+Y1)/4 = 465 mm
= 120 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 232 mm
Spc7 = 150 mm
Provided Spacing = 120 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 157 of 179
Group : G23
Beam No : B64
Analysis Reference (Member) 14.4m : 381
Beam Length : 3589.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 158 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 159 of 179
Spc3 = 6 x Small Longitudinal Dia = 96 mm
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
Group : G24
Beam No : B65
Analysis Reference (Member) 14.4m : 427
Beam Length : 3909.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 160 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 161 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 162 of 179
Group : G24
Beam No : B66
Analysis Reference (Member) 14.4m : 412
Beam Length : 10304.98 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 163 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 164 of 179
Spc3 = 6 x Small Longitudinal Dia = 96 mm
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G24
Beam No : B67
Analysis Reference (Member) 14.4m : 397
Beam Length : 10621.98 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 165 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 166 of 179
Basic
Spc1 = 700 mm
Spc2 = 393 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 167 of 179
Spacing Criteria
Group : G24
Beam No : B68
Analysis Reference (Member) 14.4m : 382
Beam Length : 3589.99 mm
Breadth (B) : 700 mm
Depth (D) : 1000 mm
Effective Depth (d) : 930 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 3068.81 kNm
As,min (flex) (B) : 2170 sqmm
As,nominal (Bn) : 846.3 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 168 of 179
Ast = Bn (for Mu = 0)
Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement calculated at a
C = As (flex) =
given section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 700 mm
Spc2 = 393 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 169 of 179
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 232 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
Spacing Criteria
Group : G25
Beam No : B69
Analysis Reference (Member) 14.4m : 428
Beam Length : 3909.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 170 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 171 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Group : G25
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 172 of 179
Beam No : B70
Analysis Reference (Member) 14.4m : 1743,413
Beam Length : 10304.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 173 of 179
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 120 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 120 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 174 of 179
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
Group : G25
Beam No : B71
Analysis Reference (Member) 14.4m : 1745,398
Beam Length : 10624.98 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 175 of 179
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 176 of 179
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 16 16 16
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 530.03 500 559.81
Asv Reqd (sqmm) 767.983 500 735.762
SCalc (mm) 100 300 100
SPrv (mm) 100 300 100
Av Total Prv (sqmm) 4021.2 1340.4 4021.2
Basic
Spc1 = 600 mm
Spc2 = 318 mm
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 300 mm
Skin reinforcement
Spacing Criteria
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 177 of 179
Group : G25
Beam No : B72
Analysis Reference (Member) 14.4m : 383
Beam Length : 3589.99 mm
Breadth (B) : 600 mm
Depth (D) : 800 mm
Effective Depth (d) : 730 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C20 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 1620.7 kNm
As,min (flex) (B) : 1460 sqmm
As,nominal (Bn) : 569.4 sqmm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 178 of 179
Basic
Spc1 = 600 mm
Spc2 = 318 mm
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021
Page 179 of 179
= 96 mm
Spc3 = 6 x Small Longitudinal Dia
Spc4 = d / 4 = 182 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Skin reinforcement
file:///C:/Users/vernp/AppData/Local/Temp/tmpA56.tmp 28/06/2021