WF 400 x 400 x 21 x 21
WF 500 x 200 x 9 x 14
Specification of RBS:
a = 0.6 bf
b = 0.75 db
c = 0.25 bf
2 2
4 c +b
r=
H upper column = 4.0 m 8c
H lower column = 4.0 m
L beam = 6.0 m
Calculate:
a. Determine the RBS geometry with the cut radius then draw the side and top views
b. Calculate Zx RBS with radius cut
c. Calculate Mp RBS with radius cut
d. Control strong column weak beam concept (with Nuc = 0.3 Ny and Muv = 0)
e. Calculate the shear force in the panel zone area (from the beam capacity)
f. Calculate the shear strength of the panel zone (assume Nu < 0.75 Ny)
g. Control Panel zone for strength and thickness
Good Luck!
1
Answer
a. Determine the RBS geometry with the cut radius and draw the side and top views
Beam WF 500 x 200 x 9 x 14 (WF 496x199x9x14)
a = 0.6 bf = 0,6 x 199 = 119,4 mm, use a = 120 mm
b = 0,75 db = 0,75 x 496 = 372 mm, use b = 370 mm
c = 0,25 bf = 0,25 x 199 = 49,75 mm, use c = 50 mm
4 c 2 +b 2 4×49 , 752 +3722
r= = =372 ,57 mm
8c 8×49 , 75
WF 400 x 400 x 21 x 21
WF 500 x 200 x 9 x 14
t = 372,57
370
120
Fy
b. Calculate Zx RBS with radius cut
C
d - ec
14 PNA
et
+ T
Sx = Ix/y = Ix/(d/2)
9
496
= 1/6 bd2 b Fy
Zx = 1/4 bd2
f = Zx / Sx = 1.5 (shape factor)
f = Mp/My = Zx Fy / Sx Fy
Zx = C ec + T et
Zx = b . d/2 . d/4 + b . d/2 . d/4 = ¼ b d2
14 ( 248−14 )2
[ (
Z xRBS =2× ( 99 ,5×14 ) × 248−
2)+
2 ]
×9 =1 .164 .230 mm3 =1 .164 , 23 cm3
2
d. Control strong column weak beam concept (with Nuc = 0,3 Ny and My = 0)
∑ M∗pb ¿ ∑ (1,1 R y f y Z+M y )=1×( 1,1×1,5×2500×1 .164 ,23 )=4 .802 . 448 ,75 kg.c
m
= 48,02 t.m
- Requirement of Strong Column Weak Beam Concept
∑ M∗pc ¿ =137 ,2 =2 ,857 ¿ ¿
∑ M∗pb ¿ 48, 02 > 1 (Strong Column Weak Beam satisfactory)
e. Calculate the shear force in the panel zone area (from the beam capacity)
M u =0,8 ∑ R y M p =0,8×1×1,5×2500×1. 164 ,23=3. 492 , 69 kg.cm = 34,93 t.m
0,8 ∑ R y M p 1×34 , 93
V col = = =4 , 366
∑h 2×4,0 ton
0,8 ∑ R y M p 1×34 , 93
T b =Cb = = =72 , 47
d−t f ( 0 , 496−0 , 014 ) ton
V ju=T b ,ka −V col =72,47−4 ,366=68,104 ton
f. Calculate the shear strength of the panel zone (assume Nu < 0,75 Ny)
3
where:
tp = 21 mm dc = 400 mm
bcf = 408 mm tcf = 21 mm
db = 496 mm fy = 250 mm
v = 0,75
2
3×408×21
[
φ v V n =0,6×0 , 75×250×400×21× 1 +
496×400×21 ]
=1 . 067 . 430 ,85
N = 108,77
ton
f. Control Panel zone for strength and thickness
- Control to strength
V ju=68 ,104 ton <φv V n=108 ,77 ton OK
- Control to thickness
Data:
d z =496−2×14=468 mm
w z =400−2×21=358 mm
468+358
t p =21 mm> =9 , 18 mm
90 (OK)
The thickness of panel zone tp = 21 mm (Satisfactory)