You are on page 1of 20

99/316/RVD

RESULT OF VOTING ON FDIS (RVD)

P ROJECT NUMBER :

IEC 61936-1 ED3

D ATE OF CIRCULATION :
2021-05-21

R EFERENCE NUMBER OF THE FDIS:

99/311/FDIS

IEC TC 99 : I NSULATION CO - ORDINATION AND SYSTEM ENGINEERING OF HIGH VOLTAGE ELECTRICAL POWER INSTALLATIONS ABOVE 1,0 K V AC AND 1,5
K V DC

S ECRETARIAT : S ECRETARY : C HAIR :

Australia Ms Erandi Chandrasekare Mr Michael Schwan

O F INTEREST TO THE FOLLOWING COMMITTEES : H ORIZONTAL STANDARD :


TC 8,TC 9,TC 10,TC 11,TC 17,TC 18,TC 20,TC 22,TC 64,TC
66,TC 78,TC 88,TC 89,TC 115,TC 122,ACTAD

F UNCTIONS CONCERNED :
EMC E NVIRONMENT Q UALITY ASSURANCE S AFETY

S UBMITTED FOR CENELEC PARALLEL VOTING N OT SUBMITTED FOR CENELEC PARALLEL VOTING

The FDIS document was distributed to National Committees with a request that voting take place for publication as an International Standard.

P- MEMBERS VOTING
M EMBERS VOTING P-M EMBERS IN FAVOUR I N FAVOUR % C RITERIA R ESULT

15 15 100 ≥66,7 % APPROVED

A LL VOTES
T OTAL VOTES CAST T OTAL AGAINST A GAINST % C RITERIA R ESULT

21 0 0 ≤25 % APPROVED

W HEN THE APPROVAL CRITERIA HAVE BEEN MET :


T HE FINAL DRAFT INTERNATIONAL STANDARD (FDIS) WILL BE PUBLISHED AS AN I NTERNATIONAL S TANDARD

W HEN THE APPROVAL CRITERIA HAVE NOT BEEN MET :


T HE FDIS IS REFERRED BACK TO THE C OMMITTEE FOR A DECISION BY

The result of voting and comments received are attached as annexes. These comments are given purely for information as no further changes
are allowed to the document at this stage, other than the correction of errors. The comments may be taken into account in a future revision
of the publication.

T ITLE :

Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1: AC


2 99/316/RVD

N OTE FROM TC/SC OFFICERS :

Annexes: Result of voting, Comments received


3 99/316/RVD

Voting Result on 99/311/FDIS


Circulation Date: 2021-03-26 Closing Date: 2021-05-07
IEC 61936-1 ED3: Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1: AC

Country Status Vote Comments Received


Argentina O -
Australia P Y - 2021-04-21
Austria P A - 2021-05-06
Belarus - Y - 2021-05-04
Belgium O A - 2021-05-07
China P Y - 2021-04-25
Croatia O Y - 2021-05-07
Czech Republic P Y Y 2021-05-06
Democratic People's Republic of Korea - Y - 2021-05-03
Denmark P Y Y 2021-04-19
Egypt P Y - 2021-04-15
Finland P Y - 2021-05-04
France P Y Y 2021-05-06
Germany P Y Y 2021-04-23
Greece - A - 2021-05-07
Hungary O -
India O -
Iran P A - 2021-05-03
Ireland P Y - 2021-03-31
Italy P Y - 2021-05-07
Japan P Y - 2021-04-28
Korea, Republic of P Y - 2021-05-07
Netherlands P Y - 2021-05-03
New Zealand O -
Norway P Y - 2021-04-21
Poland O A - 2021-05-05
Portugal - A - 2021-05-07
Qatar - Y - 2021-05-04
Romania O Y - 2021-05-07
Russian Federation O A - 2021-04-30
Slovakia O -
Slovenia O -
South Africa O -
Spain O -
Sweden P Y - 2021-04-20
Switzerland P A - 2021-04-28
Ukraine O -
United Arab Emirates - Y - 2021-05-04
United Kingdom P A - 2021-04-28
United States of America - A - 2021-05-03
Approval Criteria Result
P-Members voting: 15
P-Members in favour: 15 = 100% >=66.7% APPROVED
Total votes cast: 21 Total against: 0 = 0% <=25% APPROVED
Final Decision: APPROVED
4 99/316/RVD

Notes

Vote: Does the National Committee agree to publish the FDIS as an International Standard?
Y = In favour; N = Against; A = Abstention.
Abstentions are not taken into account when totalizing the votes.
P-members not voting: (0).

*Comments not included in the compiled table, available as a separate file, because they were not submitted using the template Form-
Comments.
5 99/316/RVD

Date Document Project Nr.


99/311/FDIS IEC 61936-1 ED3

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
CZ Annex A Table 1 te The Czech National Committee wish change Annex A (normative) Not accepted.
status Annex A (informative) Not an obvious editorial error.
Values of rated insulation levels and
Values of rated insulation levels and minimum FDIS has been accepted as IS,
minimum clearances based on current
clearances based on current practice in some NC CZ is invited to comment
practice in some countries
counries during next MT. See also RVC,
item 287.
EN 61936-1 (status normative).
Noted for future consideration.
DE01 Foreword The information “list of all parts in the IEC Delete: Not accepted.
61936 series, published under the general title IEC TC 99 is currently drafting a principles Information in an informative
Power installations exceeding 1 kV AC and document to be observed in preparation of part. Does not affect the result of
1,5 kV DC, can be found on the IEC website.”. safety accepted FDIS to IS.
includes a future document IEC 61936-0. The
publication of part 0 is not predictable. publications regarding high voltage
installations (IEC TS 61936-0 ED1: Power
Therefore delete the sentence dealing with
installations
part 0.
exceeding 1 kV a.c. and 1,5 kV d.c – Part
0: Principles to be observed in preparation
of safety publications - high voltage
installations).

DE02 3.3.1 ed Correction of IEC Definition (missing “a” ) substation (of a power system) Accepted.
An obvious editorial error.
According to IEV.
DE03 4.4.3.1 ed The whole sentence is difficult to understand. Old: Accepted.
Add some words for better reading. When high-voltage equipment is used To make the sentence easy to
under conditions different from the normal understand, use the text already
environmental conditions given in 4.4.2, approved in the CDV:
4.4.3.2 to 4.4.3.5 shall be complied with. “When high-voltage equipment is
used under conditions different
Proposal New:
from the normal environmental
When high-voltage equipment is used conditions given in 4.4.2, the
under conditions different from the normal following subclauses 4.4.3.2 to
environmental conditions given in 4.4.2,the 4.4.3.5 shall be complied with”
special conditions according to 4.4.3.2
to 4.4.3.5 shall be complied with.
6 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
DE04 5.5 2th para ed The present wording can be improved. old: Accepted.
Under dynamic conditions, the minimum Existing wording can lead to
The present wording “of a) or b)” suggests temporary clearances expressed as a misunderstanding. Proposed text
that that only the values from a) and b) are is only an editorial rewording of
percentage of
basis for calculation, and not the values under text and does not change the
normal conditions the minimum clearances under steady technical content.
state conditions [(if necessary corrected in Replace last paragraph with DE
accordance proposal according to:
Under dynamic conditions, the
with a) or b)]) are to be considered minimum temporary clearances
independently and are to be greater than: expressed as a percentage of
the minimum clearances under
1) 75 % of a) or b) in case of conductor
steady state conditions given in
swing due to the influence of wind, or Table 2, Table 3 and Annex A [(if
2) 75 % of a) or b) in the case of rupture of necessary corrected in
accordance with a) or b)]) are to
one sub-chain in a multiple insulator chain,
be considered independently
or and are to be greater than:
3) ) 50 % of a) or b) in the case of 1) in case of conductor swing
conductor swing due to the influence of due to the influence of wind :75
short-circuit. %, or
New: 2) in the case of rupture of one
sub-chain in a multiple insulator
Under dynamic conditions, the minimum chain: 75 %, or
temporary clearances expressed as a 3) in the case of conductor swing
percentage of the minimum clearances due to the influence of short-
under steady state conditions given in circuit: 50%.
Table 2, Table 3 and Annex A [(if
necessary corrected in accordance
with a) or b)]) are to be considered
independently and are to be greater than:
1) in case of conductor swing due to the
influence of wind :75 %, or
2) in the case of rupture of one sub-chain
in a multiple insulator chain: 75 %, or
3) ) in the case of conductor swing due to
the influence of short-circuit: 50%.
7 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
DE05 Figure 1 ed The distance between the two pictures of Increase distance and add a) and b) for Not accepted.
Figure 1 is too small. identification of both pictures: Does not add any clarification
a) Indoor installation
b) Outdoor installation
DE06 Figure 1 ed Similar style in this document Change: Accepted with modification.
T = N + 100 (500 minimum) Change
to „T = N + 100 (500 minimum)“
T = N + 100 (min. 500) to
„T = N + 100 (minimum 500)“

DE07 Figure 2 ed improve wording by inserting “high” Indoor: O1 = N + 200 (min. 500) Accepted.

Outdoor : O2 = N + 300 (min. 600)

Barrier less than 1 800 high

or rails, chains, ropes


DE08 Figure 3 ed Formula for H’ is wrong Correct to Accepted.
Um > 52 kV: H’ = N – 4500 (6000) Um > 52 kV: H’ = N + 4500 (min. 6000) An obvious editorial error during
Um ≤ 52 kV: H’ = N – 4300 figure update. Existing wording
Um ≤ 52 kV: H’ = 4300
makes no sense. The figure text
In clause 7.7 H’ is defined as 4300 mm for Um shall be coordinated with
≤ 52 kV. requirements stated in normative
text in Subclause 7.7
DE09 Figure 5 ed The distance between picture 5a and 5b of Increase distance. Not accepted
Figure 5 is too small. Does not add any clarification
DE10 Figure 5 ed Key: d) O2 ≥ N + 300 mm (min. 600 mm) if the Accepted with modification.
d) O2 ≥ N + 300 mm (≥ 600 mm) if the roof is roof is accessible when the conductors are Editorial. Align wording with
accessible when the conductors are live. live. requirements normative text in
Subclause 7.2.3.
Replace
“O2 ≥ N + 300 mm (min. 600
mm)”
With
“O2 ≥ N + 300 mm (minimum
600 mm)”
8 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
DE11 Figure 5 ed The unit “kW” is wrong, correct is “kV”: Correct to: Accepted.
W = N + 1000 for Um ≤ 123 kW W = N + 1000 for Um ≤ 123 kV An obvious editorial error during
W = N + 2000 for Um > 123 kW W = N + 2000 for Um > 123 kV figure update.

DE12 Figure 7 ed The caption a) and b) can be improve. The Instead of: Not accepted.
difference of the two figures is, that distance Not an obvious editorial error.
a) – Fire protection between transformer
between transformer and building are in one
case “less G1” and in the other “less G2”. The and Noted for future consideration.
building surface consists of zones which has building surface of non-combustible
to fulfill different requirements. material
b) – Fire protection between transformer
and
building surface of combustible material
New:
a) – Fire protection between transformer
and
building surface with distances less G1
b) – Fire protection between transformer
and
building surface with distances less G2

DK Ge The list of TC’s “OF INTEREST TO THE TC 81 “Lightning protection” should be Noted
FOLLOWING COMMITTEES:” contain a included in the list of Committees “OF
variety of technical committees in IEC, which INTEREST TO THE FOLLOWING
has interest in the topic of 61936-1. Lightning COMMITTEES:”. This should be updated
protection though is a major topic as well, and for the next revision of the standard.
the standard 62305 is a normative reference.

FR01 ge The French NC casts a positive vote on this Noted


document but asks to consider the following
proposal for better understanding and for
future evolutions.
All technical comments are proposed as work
bases for future edition of
IEC 61936-1
9 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR02 ge The following editorial comments will be made Please consider the following comments Noted
only on the recommendation to operate near
live parts of power installations
They are based on the application of safe
principles for working according to EN 50110-
1 applicable in Europe
FR03 ge The name CIGRÈ and CIGRÉ is unused. Please replace the term by CIGRE Accepted
FR04 Introductio Third ed This sentence is heavy : We propose to simplify the sentence : Not accepted.
n paragraph It continues the effort to towards the alignment It continues the effort to align the worldwide Keep existing text to avoid
all over the world of practices concerning the practices all over the world of practices recurring wording
design and erection of high voltage power concerning the design and erection of high
installations.
voltage power installations.

FR05 3.7 3.1.8 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: Accepted, if IEC 60050-
available on Electropedia. 195:2021 is still not published at
“[SOURCE: IEC 60050-195:1998, 195-02-
the time of publication of IEC
19, modified – ….]” 61936-3 ED3.
FR06 3.4 3.4.4 ed Apply "ISO/IEC DIR 2, 16.5.10”. If a Correct the source as follow: Accepted
terminological entry is reproduced from “[SOURCE: IEC 60050-195:1998, 195-06- An obvious editorial error and
another document, the source shall be given 15, modified – “from any usual direction of according to IEC directives for
at the end of the entry. If any changes are definitions. The correction does
access” has been replaced with “by a
made to the original terminological entry, this not change the definition
human being or livestock with hazardous-
shall be indicated, along with a description of live-parts from any usual direction of
what has been modified. access”.]”
The source is incomplete.
The edition of 2021 of IEC 60050-195 is not
available on Electropedia.

FR07 3.5.5 ed The wording of the definition: Considering this point raised we would Accepted.
“in the case of high voltage, area limited by propose to read simply: An obvious editorial error as the
the minimum clearance of danger zone “in the case of high voltage, area limited by existing text does not
around hazardous-live-parts without complete the minimum clearance of danger zone correspond to its source. In
around hazardous-live-parts without addition, the correction does not
protection”
change the definition
complete protection
Is misleading on one point; Note 1 to entry: Entering the danger zone
why using again the same term “danger zone” is considered the same as touching live
in the definition. This is forbidden by ISO/IEC parts.
directives 2 [SOURCE: IEC 61140:2016, 3.35]
10 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR08 3.5.6 ed The wording of the definition: We would propose to read simply: Not accepted.
“clearance which describes the area of danger “clearance which describes the area of Not an obvious editorial error
zone around hazardous-live-parts without danger zone around hazardous-live-parts and the proposal may change
complete protection against direct contact” without complete protection against direct the meaning.
contact Noted for future consideration.
is also misleading by using:

“without complete protection” which allows


“uncomplete protection”

FR09 3.7 3.7.1 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-01-
03, modified – The note 1 to entry has
been added.]”

FR10 3.7 3.7.2 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-01-
01, modified – ….]”

FR11 3.7 3.7.3 ed The definition of the term “earth electrode” Add the source as follow: Accepted.
comes from IEC 60050-195:1998, 195-02-01. “[SOURCE: IEC 60050-195:1998, 195-02- Add the source as follows:
Apply "ISO/IEC DIR 2, 16.5.10”. If a 01.]” “[SOURCE” IEC 60050-
terminological entry is reproduced from 195:1998, 195-02-01, modified –
another document, the source shall be given In the definition, <electrical
power installations> has been
at the end of the entry.
added.
The source is missing.

FR12 3.7 3.7.4 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-02-
03, modified – ….]”

FR13 3.7 3.7.8 ed The definition of the term “electric resistivity of Add the source as follow: See FR05
soil” comes from IEC 60050-195:1998, 195- “[SOURCE: IEC 60050-195:1998, 195-01-
01-19. 19.]”
Apply "ISO/IEC DIR 2, 16.5.10”. If a
terminological entry is reproduced from
another document, the source shall be given
at the end of the entry.
The source is missing.
11 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR14 3.7 3.7.10 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-01-
17, modified – The note 1 to entry has
been added.]”

FR15 3.7 3.7.12 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-05-
11, modified – ...]”

FR16 3.7 3.7.16 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-05-
12, modified – ...]”

FR17 3.7 3.7.21 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-06-
10, modified – ...]”

FR18 3.7 3.7.22 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-06-
11, modified – ...]”

FR19 3.7 3.7.23 ed The edition of 2021 of IEC 60050-195 is not Correct the source as follow: See FR05
available on Electropedia. “[SOURCE: IEC 60050-195:1998, 195-02-
12]”

FR20 4 te The user's expectations include also Replace reliability by dependability or Not accepted.
expectation on lifetime. Reliability should be introduce durability. Noted for future consideration.
completed by durability both being covered by And add a new definition in 3.1 (3.1.19) :
dependability.
dependability, <of an item>
ability to perform as and when required
Note 1 to entry: Dependability includes
availability (192-01-23), reliability (192-01-
24), recoverability (192-01-25),
maintainability (192-01-27), and
maintenance support performance (192-
01-29), and, in some cases, other
characteristics such as durability (192-01-
21), safety and security.
12 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
Note 2 to entry: Dependability is used as a
collective term for the time-related quality
characteristics of an item.
[SOURCE: IEC 60050-192:2015, 192-01-
22]

FR21 4.2.10 ed The note has to be clarified. Modifiy the note as follow : Not accepted.
Note NOTE Guidance on ensuring Noted for future consideration.
electromagnetic compatibility and to
ensuring so that electromagnetic fields…

FR22 4.3.1 te Combinations of loads are not between Replace by: Not accepted.
normal and exceptional loads. Noted for future consideration.
4.3.1 General
Structural calculation methods refer to
Equipment and supporting structures,
permanent loads and imposed loads (service,
including their foundations, shall withstand
operating, variable) loads. The snow and wind
all the anticipated load combinations.
are part of the service loads. Structural
calculation methods combine the loads with The load assumptions related to the local
respective factors for the permanent and conditions shall be determined in an
service loads and the nature and the element agreement between the supplier and user.
on which loads are applied.
Three load cases shall be considered,
As example fire and rare case of snowfall are permanent and variables considered as
exceptional. normal loads and exceptional loads.
In each of these load cases, several
Occasional is not exceptional; Snowfalls are combinations shall be investigated. The
occasional, not permanent and not most unfavourable combination shall be
exceptional. used to determine the mechanical strength
of the structures.
The text should be updated.
4.3.1.2 Permanent loads
Dead load of equipment and structure
represent the permanent loads. In the
normal load case, the following loads shall
be considered:
– dead load
– tension load,
13 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
4.3.1.2 Variable loads
Service and operating loads such as
switching, short circuit and erection loads
are variable loads.
The environmental effect such as snow,
ice, wind pressure are also variable loads.
Consideration shall be given to temporary
stresses and loads that may be applied
during construction or maintenance
procedures. Specific equipment can be
affected by cyclic loads (refer to specific
equipment standards).
In the variable load case, dead load and
tension load acting simultaneously with the
largest of the following occasional loads
shall be considered:
– ice, snow load and
– wind load.
– erection load,
– switching forces,
– short-circuit forces,
The load combinations of permanent loads
and variable loads shall be considered as
normal loads.
4.3.1.3 Exceptional loads
In the exceptional load case, load and
tension load acting simultaneously with the
largest of the following occasional loads
shall be considered:
– loss of conductor tension,
– seismic loads and
– buoyant force to the foundation at
flooding.

Note: In any case the structural calculation


shall consider the soil reaction.
14 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR23 4.4.2 te The ambient conditions are considered for Modify as follows : Not accepted.
performance only verified by type tests as 4.4.2 Normal conditions Noted for future consideration.
mentioned within IEC 62271-1. However, for 4.4.2.1 General
transformer the performance and normal Operation under normal service conditions
service conditions are different as defined by is considered to be covered by the type
IEC 60076 series of standard, which should tests according to this document and
be considered as mentioned line 1448. relevant product standard.
For power transformers normal service
Why? As example the ageing rate for conditions are defined by IEC 60076-1 and
distribution power transformer is 1.08 for 20°C IEC 60076-2 for oil immersed power
avg, 6.12 for 35°C avg, 6.44 for 35°C avg and transformers and IEC 60076-11 for dry
40°C maximum. type power transformers.
4.4.2.2 Indoor conditions
For indoor electrical HV switchgear and
controlgear, normal conditions shall be as
follows:

4.4.2.3 Outdoor conditions
For outdoor electrical HV switchgear and
controlgear, normal conditions shall be as
follows:

FR24 4.4.2.1 e) te The influence of criteria on water vapour Replace by: Not accepted.
pressure is better compared to those defined Noted for future consideration.
– the average value of the relative
for relative humidity being influenced by
humidity, measured over a period of 24 h,
ambient air temperature.
does not
Relative humidity criteria is never achieved exceed 95 %;
due to the influence of ambient air
temperature. – the average value of the water vapour
pressure, over a period of 24 h, does not
Information of the associated temperature if exceed 2,2 kPa;
95% of relative humidity is considered.
– the average value of the relative
2.2 kPa is the value for 95% at 20°C. humidity, over a period of one month, does
not exceed 90 %;
5.3kPa is the value for 95% at 35°C.
– the average value of the water vapour
pressure, over a period of one month, does
not exceed 1,8 kPa.
15 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
NOTE 1 Condensation can be expected
where sudden temperature changes occur
in periods of high humidity.

NOTE 2 To avoid breakdown of insulation


and/or corrosion of metallic parts due to
high humidity and condensation,

equipment designed for such conditions


and tested accordingly is normally used.

NOTE 3 Condensation can be prevented


by special design of the building or
housing, by suitable ventilation and heating
of the station or by the use of
dehumidifying equipment.

FR25 4.5.3 Ed/te Relevant information is existing within the Complete the note with the text as follows: Not accepted.
IMO/ILO/UNECE Code of Practice for Packing Additional information can be found within Noted for future consideration.
of Cargo Transport Units (CTU Code); the IMO/ILO/UNECE Code of Practice for
Reference to this in the note could be useful. Packing of Cargo Transport Units (CTU
Code)

FR26 6.2.2 te The guidance to manage the trade-off Add the following text after “IEC 60076 (all Not accepted.
between influencing parameters related to parts) Noted for future consideration.
temperature rise might be mentioned to bring
“The Annex D of the IEC 62271-202 brings
awareness to the readers.
guidance on the interactions between load
factor scenarios, temperature rise of power
transformer and enclosure effect if any, for
distribution oil immersed and dry types
power transformers.”
16 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR27 7.2.3 Figure 2 ed In Figure 2 the drawing is misleading. The We propose to re-introduce the indications Not accepted.
origin of the arrow N is not clear. “O-N”, “B-N” and “H-N” of the original Not an obvious editorial error.
drawing (figure 1) of IEC 61936:2010 as
indicated in the figure below : Noted for future consideration.

FR28 7.2.4 Figure 3 ed In Figure 3 the drawing is misleading. The We propose to re-introduce the indications Not accepted.
origin of the arrow N is not clear. “H’-N”, “C-N”, “E-N” of the original drawing Not an obvious editorial error.
(figure 2) of IEC 61936:2010 as indicated
in the figure below : Noted for future consideration.

FR29 7.4.2.3 ed Lighting strikes is not the right expression Replace by “lighting strokes”. Accepted.
Fifth dash An obvious editorial error.
17 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR30 7.5.1 te The sentence is not enough clear for the Replace Not accepted.
context of this standard and is wrong in main Noted for future consideration.
situations within the context of prefabricated “For the purpose of this standard,
substations. The prefabricated substations in prefabricated substations covered by IEC
accordance with IEC 62271-202 are installed 62271-202 are not considered as
on public area especially for utilities and/or buildings.”
must bring precaution for worker in operating
room. For that building codes need to be by:
applied on the structure (enclosure) of the
“For the purpose of this standard,
prefabricated substation during the design,
prefabricated substations covered by IEC
verification and handling life phase. For this
62271-202 are not considered as buildings,
building codes when existing, from the site
however applicable regulation(s) for
where the substations is designed and /or
buildings when existing can be met.”
where it is installed can be applicable and can
be different.

FR31 7.5.7.1 Te When air conditioning is used, the flow of cold Add a new sentence in line 2156 Not accepted.
air must not be directly blowed to hot surface In the case air conditioning is used, Noted for future consideration.
of the equipment to avoid any risk of thermal precaution shall be taken to avoid any
shock thermal shock on equipment or local
condensation
FR32 7.5.7.1 te Stress the use of passive solution that would Change: Not accepted.
be recommended for energy saving. “Where natural ventilation is inadequate, Noted for future consideration.
additional measures shall be
“Where natural ventilation is inadequate, implemented”.
additional measures shall be implemented”.
Into:
Natural ventilation or heat limiting solutions
(e.g. shadow) will be preferred, but where
this is inadequate, additional measures
shall be implemented.

FR33 7.5.7.1 te Equipment that is correctly cooled can still be Add: Not accepted.
too hot to touch. Dealing with temperatures of “The accessible surfaces of electrical Noted for future consideration.
touchable hot surfaces should be mentioned, equipment should not exceed the
at least as general recommendation. temperature limits defined in IEC Guide
Reference to IEC Guide 117 can be used. Ed 117.”
1.0 2010-10: ” Electrotechnical equipment –
Temperatures of touchable hot surfaces”
18 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR34 8.2.3.1 Te For enclosure with an IP degree IP2XC is not Modify as follow : Not accepted.
considered as safe and should be increased Noted for future consideration.
to IP3X or IP2XD When protection by enclosure is used for
equipment or assembly, the minimum
degree of protection shall be IP3X or
IP2XD with a clearance for active parts
equal to N

FR35 8.2.3.2 Te In the clause 8.2.2.1, when enclosure is used Modify as follows: Not accepted.
the degree of protection shall be IP2XC, but in Noted for future consideration.
8.2.2.2, it is only written IP2X in minimum. « When protection by enclosure is used,
the degree of protection shall meet the
Degree of protection of indoor should be the
same than for Outdoor and should be IP2XC requirements of IP2XC in minimum with a
in both case. clearance for active parts equal to N.. »

FR36 8.2.3.1 Te For enclosure with an IP degree IP2XC is not Modify as follow : Not accepted.
considered as safe and should be increased Noted for future consideration.
to IP3X or IP2XD When protection by enclosure is used for
equipment or assembly, the minimum
degree of protection shall be IP3X or
IP2XD with a clearance for active parts
equal to N

FR37 8.5 te The arc fault can happen when the substation Replace by: Not accepted.
is in operation and not only when equipment is Noted for future consideration.
operated. “Electrical power installations shall be
designed and installed so that persons are
Sentence should be improved as proposed protected as far as practical from arc faults
during operation “

FR38 8.7.2.2 Table 4, Te Considering the previous comment, the Remove the reference to 60076-13. Not accepted.
Note 1 reference to the IEC 60076-13 is not relevant. Add the reference of the 60076-22-1 Noted for future consideration.
The scope of the IEC 60076-13 is for liquid
filled transformer below 1000 kVA and below
24 kV which has generally much less than
1000 l of liquid.
And as the clause 7.3 of the IEC 60076-13,
the preferred dielectric liquid is mineral oil.
The reference of FM global standard 9330
could be evaluated.
The IEC 60076-22-1 is treating of the safety
device for transformer could be added.
19 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR39 Annex F Third ed The paragraph: We would propose to read: Not accepted.
paragraph “Each of these three procedures involves “Each of these three procedures involves Noted for future consideration.
adequate safety measures that mitigate the adequate safety measures that mitigate the
risks of electric shocks, short-circuit and arc risks of electric shocks, short-circuit and
faults.” arc faults. Example of such working
procedures are described in the EN 50110-
Could be improved by the use of the EN 1”
50110-1 as example

FR40 Annex F Sixth ed The wording of the first dash is misleading We could propose to modify the paragraph Not accepted.
paragraph because the distance defining the outer limit of as follows: Noted for future consideration.
the vicinity zone and the working distance are
not yet defined in Clause 3.5 “An illustration of working distances is
given in Figure F.1. These are described
as follows:
– Dv: Distance (Dv) defining the outer limit
of the vicinity zone, which is the limited
space outside the minimal clearance of
danger zone (N).
– Dw: Working distance (Dw) defining the
distance to be observed between exposed
live parts and any person working in a
closed electrical operating area including
any conductive tool directly handled.

FR41 Annex F NOTE 2 ed The reference to CIGRE could be completed We would propose to read: Not accepted.
by the reference to EN 50110-1 Noted for future consideration.
NOTE 2 Further information regarding safe
work methods can be found in CIGRÉ
Technical Brochure 805, Guidelines for
safe work methods in substations or in the
European standard EN 50110-1 –
Operation of electrical installations.

FR42 Annex F Figure F.1 ed The wording of the title: We would propose to read Not accepted.
Working clearances within closed electrical Working distances clearances within the Not an obvious editorial error
operating areas vicinity zone closed electrical operating and the proposal may change
Is misleading because the aim was to show areas the meaning.
“working distances” Noted for future consideration.
20 99/316/RVD

MB/ Line Clause/ Paragraph/ Type of Comments Proposed change Observations of the secretariat
NC number Subclause Figure/ Table/ comment
(e.g. 17) (e.g. 3.1) (e.g. Table 1)
FR43 Annex G All ed Use everywhere in the document the Correct accordingly. Not accepted.
abbreviations: The Country note is wording
- AC, DC, according to IEC 60050-151 from respective National
Committees.
(see 151-15-01 and 151-15-02),
instead of a.c., d.c., ac, dc., A.C., D.C.

FR44 Bibliograp ed The reference to EN 50110-1 could be added Please add: Not accepted.
hy Not used within the document
EN 50110-1:2013, Operation of electrical
installations – Part 1: General requirements

FR
FRENCH VERSION ONLY
FR45 Title ed The French title “Installations électriques de The title has to be modified as follow :
puissance supérieure à 1 kV en courant
alternatif et 1,5 kV en courant continu - Partie Installations électriques de puissance de
1: Courant alternatif » is uncorrect tension supérieure à 1 kV en courant
alternatif et 1,5 kV en courant continu -
Partie 1: Courant alternatif