Professional Documents
Culture Documents
What's an ECM?
The highest efficiency motor there is! … A DC Motor
Without mechanical Brushes and
Commutator
PSC motor:
optimized only at rated 550
design conditions 500
3 speed PSC
Induction Motor
highest operating cost 450
1200
E
1000
D
High Static Pressure
Speed (RPM)
C
800
B
600
A
200
Constant Airflow Profile (800 cfm)
0
0 10 20 30 40 50 60 70 80 90 100
Normalized Motor Torque (%)
ECM-Driven Systems Industrial Systems
How the GE ECM™
Makes Airflow Constant
Unlike a conventional induction motor, GE’s ECM If static pressure changes (for example, a clogged
motor regulates itself by automatically changing air filter, or different installation), then the blower
torque and speed to maintain a programmed level of speed will increase to Point B (see High Static
constant airflow over a wide range of external static Pressure Curve, blue line). This increase in speed
pressures. This is accomplished through several occurs when any blower––whether equipped with
steps. an ECM or AC induction motor––encounters an
increase in static pressure. The reason is that the
First, the air-moving system is characterized in an clogged filter restricts airflow in the system
airflow chamber for its torque and static pressure meaning there is less air for the blower to propel
operating range. That characteristic is then through the system. (This is akin to a car's wheels
programmed into the motor. Then the motor's losing traction on ice and spinning freely).
control is programmed with a set of desired airflows
(e.g. 800 cfm). That constant airflow is defined by The airflow at Point B, however, is lower than
the ECM's speed and torque, which is expressed in required to remain on the desired Constant Airflow
the graph nearby as the orange line. Point A on the Profile as expressed by the orange line. The motor
orange line, for instance, represents an airflow of will not operate at Point B because its programming
800 CFM at the initial level of static pressure in the does not allow this combination of torque and speed
system, here called Low Static Pressure (see the for this particular system. As a result, the GE ECM
green line). patented algorithm will increase torque and speed to
find a new stable operating point on the High Static
As long as the pressure remains constant, the ECM Pressure Curve. Increases in torque will continue
motor will continue to deliver 800 cfm to the until the speed and torque converge with the next
system. This is referred to as a stable operating stable operating point, which in this case is Point E
point which is defined as any point where the on High Static Pressure Curve. When operating a
system profiles intercept the ECM constant airflow point E, the blower is delivering higher torque,
profile. Points A and E in this example are the only higher speed, but the same airflow as in point A.
stable points for constant airflow in the graph.
© 2000 General Electric Company
ECM-Driven Systems Industrial Systems
The ECM’s Benefits in HVAC
The ECM’s Sound Advantage
Air noise dominates at high Tone levels of ECM & PSC motors
airflow, but ECM still has a 60
slight advantage (free discharge)
50
ECM can get to lower
Sound level (Db)
airflow than PSC 40
ECM Connections
5 AC Line
4 AC Line
Power Connection TIPS 3 Gnd
2 Lines 1&2 will be connected
1 for 120Vac applications only
ECMs connect directly to the line Make sure power is OFF before
Do Not insert contactors/relays in inserting or removing power
series with either AC line connector
Control is powered continuously Verify and re-verify connector
insures reliable start-up orientation before applying power
maximizes reliability
Plug is Polarized
Pins 1&2 are jumpered in harness Do Not force plug into motor
for Furnace (115V) operation
Line voltage should NEVER be
applied to pins 1 or 2.
ECM-Driven Systems Industrial Systems
Installation and Service
5 AC Line
4 AC Line
Power Connection TIPS 3 Gnd
2 Lines 1&2 will be connected
1 for 120Vac applications only
Furnaces/115Vac applications
require series inductance in AC line True RMS meters should be used
All 3/4 and 1hp applications will use to measure line current
inductor, 1/2hp may not Some clamp-on ammeters may not
Reason: read line current accurately.
AC line currents are non-
Remember -- the ECM’s current
sinusoidal
Inductor reduces peak line
will be very low at off-load
current conditions because of its high
Maintains circuit “ampacity” efficiency.
Inductor should always be in line
(HOT) side.
ECM-Driven Systems Industrial Systems
Installation and Service
Set Up TIPS
Set Up TIPS
Changing:
Heating airflow
Cooling Off delay
Cooling airflow
require the unit to be cycled off
before the change takes effect
Control Signal
Measurement Tips
True RMS meters should be used
Presence of half-wave signals from
interface board can be determined
ECM-Driven Systems Industrial Systems
Installation and Service
What If…
The system is probably being controlled by a thermostat that uses solid state
relays or triacs as output switches. The current leaking through such
switches can cause a voltage level to appear on the ECM Motor’s terminals
that make it react as if the thermostat is actually calling.
Another cause could be a high impedance compressor contactor or fan relay
coil that causes a voltage above one-half the control transformer output
voltage to appear on terminals “Y” or “G” of the motor.
… the changeover valve signal (“O”) is not
connected in a conventional air handler, so why is
is it in an ECM-driven Air Handler
If “Y” is not connected, the ECM-driven blower will only respond to the “G”
terminal in cooling. This means the blower will only operate at the “FAN-
ONLY” air volume and will not change to the “Cooling” airflow required
during compressor operation. The system will probably trip-off on high
compressor head pressure or, if there is sufficient airflow to prevent that, the
system’s capacity will be seriously degraded and will cause system reliability
degradation and comfort complaints.
… the dip-switch settings on the interface card are not changed at installation?
The dip switches on the interface card select airflow to match the size of the
system installed. If they are not verified to be in the position matching the
size of the condensing or heat pump unit, the indoor airflow will be grossly
over-blown or under-blown. Also, the DELAY and TRIM functions will
remain in factory default positions and may not be appropriate to the
customer’s home, preferences or lifestyle.
ECM-Driven Systems Industrial Systems
Installation and Service
What If answers…
… dip-switches controlling cooling and heating capacity are changed but the CFM doesn’t change!
In all probability, the switches were changed while the ECM-driven blower
was running. The blower must go through an off-cycle for the new settings
to take effect.
… there is no 24Vac on pin 12 of the ECM’s 16 pin connector?
Without 24VAC from the low voltage transformer present at pin 12 of the
ECM, the motor will not respond correctly to most of the control functions;
specifically, “O”, “Y1”, “Y/Y2”. It is important that in all systems
depending on these inputs that “R” be connected to pin 12 of the ECM. The
“Analyzer” troubleshooting tool can pin-point that problem, if it exists.
ECM-Driven Systems Industrial Systems
Installation and Service
Cu Ft/min
1400
MODEL WITH ANOTHER 1300
• Don’t exchange between different 1200
1100
OEM products 1000
• Don’t exchange between furnaces 900
0.0 0.2 0.4 0.6 0.8 1.0
and air handlers Ext Static Pressure (" H2O)