MEP Basis of Design Report Transbay Transit Center

San Francisco, CA

1.4. Ventilation Design Criteria


Title 24
ASHRAE 62.1-20073 Design
20083
People Area
Minimum
Outdoor Outdoor
Occupancy Category1 Exhaust
Air Rate Air Rate Air Change Rate
Rate Cfm/ft²
(Rp) (Ra) (ACH)
Cfm/Person Cfm/ft² (CFM/ft²)

Grand Hall 7.5 0.06 -- 0.15 --


Lower Concourse
7.5 0.06 -- 0.15 --
Circulation
Lower Concourse
7.5 0.06 -- 0.15 --
Waiting Areas
Bus Deck Waiting 7.5 0.06 -- 0.15 --
Public Lobbies 5 0.06 -- 0.15 --
Retail 7.5 0.12 -- 0.2 --
Retail – Circulation 7.5 0.06 -- 0.15 --
Restaurants – Dining 7.5 0.18 -- 0.15 --
Restaurants – Kitchen -- 0.06 0.7 0.15 20²
Meeting Rooms 5 0.06 -- 0.15 --
Corridors -- 0.06 -- 0.15 --
Administration/BOH 5 0.06 -- 0.15 --
Public Restrooms -- 0.06 50/unit -- 10
CHSR/Caltrain Ops 7.5 0.06 -- 0.15 --
CHSR/Caltrain
7.5 0.06 -- 0.15 --
Support
Locker/dressing rooms 20 0.06 0.25 0.15 --
Intercity Bus 7.5 0.06 -- 0.15 --
FCC 7.5 0.06 -- 0.15 --
SOC 7.5 0.06 -- 0.15 --
Electrical Substations -- -- -- -- 2
Electrical Closets -- -- -- -- 2
Storage Rooms -- 0.12 -- -- --
MDF Rooms 5 0.06 -- -- --
IDF Closets DNL DNL -- -- --
Elevator Machine
DNL DNL -- -- --
Rooms
Fire Pump Room DNL DNL 1.5 -- 2
Mechanical Rooms DNL DNL -- -- 2
Trash Compactor
-- -- 1.0 -- 6
Room
TSER Rooms -- -- -- -- 2

WSP Ref. No.: S08.14200.00 Heating, Ventilating


January 23, 2014 and Air Conditioning