GENERAL A : DXN1 = 42 mm

DXN3 = 48 mm
D : DXN1 = 51 mm
DXN3 = 57 mm
Ø : DXN1 = 4,5 mm
DXN3 = 5 mm
OPERATION OPTIONAL SOCKET-OUTLET LOCKING DECLARATION OF CONFORMITY RESPONSIBILITY
• Single-padlocking: cover closed, insert a padlock that fits tightly in the
The DXN DECONTACTOR™ is a plug and socket-outlet for industrial DXN6 = 55 mm DXN6 = 68 mm DXN6 = 5 mm • To be connected, the plug and the socket-outlet must have similar ratings locking hole (6 mm or 8 mm depending on the option chosen). These accessories use the technology. They have been designed, In the case accessories are associated with accessories or
purpose with integral switching device (according to IEC/EN 60309-1). It is (voltage, current …), and compatible contact configurations. • Triple-padlocking: cover closed, insert into the hole the shaft that can manufactured and controlled in a strict respect of the requirements and spare parts other than from , the CE marking is invalidated and
designed for use in explosive atmospheres and complies with the relevant A • The socket-outlet is shielded by a protective lid held in the closed accommodate up to three padlocks. rules of international and European standards and particularly the ATEX MARECHAL ELECTRIC S.A.’s responsibility cannot be engaged.
international and European safety standards and particularly the position by a latch. Depress the latch to release the lid. • Screw locking: cover closed, turn the triangular or hexagonal screw of the Directive 94/9/EC. They bear the CE marking. MARECHAL ELECTRIC S.A.’s responsibility is strictly limited to the obligations
ATEX 94/9/EC Directive. It can be installed in zones 1 and 2 (for gas) and in latch with a key until it reaches the bottom. Do not overtighten. expressly agreed in its general sales conditions. Any penalty or indemnity
Note: The CE marking does not apply to spare parts and components
zones 21 and 22 (for dust). cable provided herein will be considered as lump damages, redeeming from any
supplied separately.
Live parts are protected against a 1-mm metallic wire (IP4X/IPXXD)
according to IEC/EN 60529 standard.
MAINTENANCE other sanctions.
For the latest certificates, please visit:
• IEC / EN 60079-17 standard: Explosive atmospheres – Part 17: marechal.com - Documentation - Certificates. MARECHAL ELECTRIC S.A. is a member of the international
Stripping length
WARNINGS Wiring capacity mm²
mm Tightening
Flat
Electrical installations inspection and maintenance, foresees very strict association, BECMA: the Butt-contact Electrical Connectors
Rigid/ Socket-outlet/
torque screwdriver requirements regarding the maintenance of electric installations which Manufacturers’ Association.
Contacts Flexible Plug/inlet N.m
• Installation and maintenance of «Ex» accessories must be performed by stranded connector must be imperatively respected.
an authorized electrician, according to applicable standards and to the DXN1 1 to 4 1.5 to 6 12 12 0.8 3 mm • Ensure that the fixing screws, caps and cable glands are tight.
present instruction sheet. DXN3 Main 2.5 to 10 2.5 to 16 20 21 1.2 5 mm • Check the cleanliness of contact surfaces. Any deposit can be rubbed off
• These accessories must be used according to their designed destination. DXN3 Auxiliary 1.5 to 2.5 1.5 to 4 17 17 0.8 3 mm with a clean cloth. In case of damage, contact your supplier to have them
Respect their assigned ratings in terms of current, voltage, IP and their Ex DXN6 Main 6 to 16 6 to 25 20 21 2.5 5 mm • To connect, align the red marks on the housings. Insert the plug and turn replaced by the manufacturer.
classification (see CE declaration). DXN6 Auxiliary 1.5 to 2.5 1.5 to 4 17 21 0.8 3 mm until the stop. The plug is in the rest position, circuit open. • For socket-outlets that have a safety shutter, contact surfaces may be www.becma.ch
• For optimum switching operation, ensure that the flexible cable does not Push the plug fully home until latched. inspected directly from the front by an authorized electrician: depress the
hinder the return of the plug or connector to its rest position. spring-loaded ejection ring on two opposite points. The safety shutter can
• Additional components used (e.g. cable entry, adaptor, blanking cap, etc.) Other sizes can be used with the help of wiring lugs. then be rotated clockwise to inspect contact tips. Do not forget to re-lock
must be certified with a protection mode and an IP compatible with the Terminals are spring-assisted to prevent loosening due to strand the safety shutter after inspection.
use in question. settlement, vibration or thermal cycling. Respect recommended torques. • Inspect periodically IP gaskets. Replace as needed.
• Where there is a risk of deformation of the surface on which the accessory • Check regularly the continuity of the ground circuit by electric tests.
is installed, care must be taken to prevent the transmission of this
deformation to the accessory or its surface box.
• Apply without excess the necessary torque to tighten self-tapping screws.
Do not overtighten screws supplied with polymeric accessories.

• Respect tightening torques. COLOUR-CODED RINGS • To disconnect, depress the latch. The plug returns to its rest position.
• DXNs can be used without any mechanical precautions except for the Insert the colour-coded rings between the inlet/plug top or socket-outlet INSTRUCTION SHEET
DXN1 which should not be exposed to shocks superior to 4 joules. and their rear accessory. The two protrusions of the rings must be positioned Technology
• accessories must be used with complementary on the latch side for the socket-outlet/connector and on the catch side for
accessories only. the plug/appliance inlet. These rings act as seals.
• Rules impose that any replacement of component must be performed
under the control of the manufacturer MARECHAL ELECTRIC S.A.

INSTALLATION
• Install the socket-outlet facing downwards, with the latch at the top (or
on the side in case of risk of accumulation of foreign bodies inside the
cover). • Turn the plug in the opposite direction to remove it. Shut the socket-
• Panel mounting socket-outlets and inlets must be assembled on an ‘Ex e’ outlet lid.
increased safety enclosure according to the following sketch.

A 4xØ

N° 7e - Rev. : 14 - 09/2013

D A
DXN
MARECHAL ELECTRIC S.A.
5, avenue de Presles - F-94417 Saint-Maurice Cedex - France
Tel. : +33 (0)1 45 11 60 00 / Fax : +33 (0)1 45 11 60 60

marechal.com