Professional Documents
Culture Documents
GENERATOR PARALLELING
SWITCHGEAR
Application & Installation Guide Generator Paralleling Switchgear
Foreword
This section of the Application and Installation Guide generally describes
wide-ranging requirements and options for Switchgear with a focus on
Generator Paralleling Switchgear. Additional engine and generator systems,
components, and dynamics are covered in other sections of this Guide.
Systems and components described in this guide may not be available or
applicable for all Switchgear. While much of the content of this guide is
applicable to all switchgear the primary focus of this guide is on the North
American generator paralleling switchgear market.
Contents
1 SWITCHGEAR.....................................................................9
1.1 Codes, Standards, and Terms ........................................9
1.1.1 IEEE1547..............................................................9
2 VOLTAGE CLASSIFICATIONS............................................. 10
3 SWITCHGEAR TYPES ........................................................ 10
3.1 Metal-Enclosed...........................................................10
3.2 Metal-Clad .................................................................11
3.3 Arc Resistant .............................................................12
3.4 Enclosure Ratings .......................................................12
3.4.1 Non-Hazardous Locations .....................................12
3.4.2 Hazardous Locations ............................................16
3.4.3 NEMA Enclosure Type Numbers vs.
IEC Enclosure Classification Designations........................17
4 POWER ASSEMBLY ........................................................... 18
4.1 Switchgear vs. Switchboard ........................................18
4.2 Switchgear Standards .................................................19
4.3 Switchgear Dimensions ...............................................20
4.3.1 Metal-Enclosed ....................................................20
©2007 Caterpillar®
2 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
3 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
4 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
5 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
6 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
7 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
8 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
9 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
10 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
11 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
12 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
13 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
14 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
15 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
16 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
3.4.3 NEMA Enclosure Type Numbers equated with the enclosure Type
vs. IEC Enclosure Classification numbers in this standard.
Designations The IEC designation consists of the
IEC Publication 60529, letters IP followed by two numerals.
“Classification of Degrees of The first numeral indicates the degree
Protection Provided by Enclosures,” of protection provided by the
provides a system for specifying the enclosure with respect to persons
enclosures of electrical equipment on and solid foreign objects entering
the basis of the degree of protection the enclosure. The second numeral
provided by the enclosure. indicates the degree of protection
IEC 60529 does not specify degrees provided by the enclosure with
of protection against mechanical respect to the harmful ingress of
damage of equipment, risk of water.
explosions, or conditions such as Figure 7 provides an equivalent
moisture, corrosive vapors, fungus, conversion from the enclosure Type
or vermin. The NEMA Standard for numbers in this standard to the IEC
Enclosures for Electrical Equipment enclosure classification designations.
does test for environmental conditions The enclosure type numbers meet or
such as corrosion, rust, icing, oil, and exceed the test requirements for the
coolants. For this reason and because associated IEC Classification; for this
the test and evaluations for other reason Figure 7 cannot be used to
characteristics are not identical, the convert from IEC classifications to
IEC enclosure classification enclosure Type numbers.
designations cannot be exactly
©2007 Caterpillar®
17 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
18 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
Switchgear Switchboard
Figure 8 – Switchgear and Switchboard
©2007 Caterpillar®
19 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
20 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
21 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
22 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
more easily plated, and bolted joints if stranded wire is used. Flexible wire
are made more easily. The melting must be used for wiring across a
point of copper is higher than hinge to a panel.
aluminum so less damage is done The insulation on the wire must
to copper busses in case of an meet the requirements for Type TA,
arcing fault. TBS, or SIS as described in the
In most cases, copper is a more National Electrical Code.
expensive metal. If aluminum is used,
joints may be welded, making field 4.7 Transformers
changes difficult. Copper joints must
A transformer is a device that
be silver-plated; aluminum bolted
transfers electrical energy from one
joints may be silver-plated or tin-
circuit to another through a shared
plated. Where bolted joints are
magnetic field. A changing current in
necessary, as at shipping splits,
the primary circuit creates a changing
aluminum may be welded to copper.
magnetic field, which induces a
Bolted joints should be made to
voltage in the secondary circuit.
minimize the tendency to cold flow
The secondary circuit mimics the
(permanently deform due to constant
primary circuit but with different
stress) and to maintain a tight clamp
current and voltage.
in the case of some cold flow or
stretching of the bolt over a period 4.7.1 Current Transformers
of time. Current transformers (CTs) are
designed to provide a current in its
4.6 Wiring secondary conductor proportional to
When determining wiring, applicable the current flowing in its primary
standards must be used to determine conductor. Current transformers can
the following: safely isolate measurement and
control circuitry from high voltages
• Size of wire. and currents present in the circuit
• Insulation material. while giving an accurate measurement
of the primary current. Figure 10
• Terminal types. shows a picture of current
• Terminal insulation. transformers.
A detailed wiring diagram is required
to show the relative location of
terminals on various devices and
terminal blocks. Referring to this
diagram can identify when trouble-
shooting or making changes Figure 10 – Current Transformers
to wiring.
The current transformer ratio is
Secondary wiring in metal-clad generally selected so the maximum
switchgear must be enclosed in metal load current will read about 70% full
channels or in conduit to isolate it scale on a standard 5A coil ammeter.
from the primary circuits. The wire Therefore, the current transformer
should not be smaller than 16 AWG
©2007 Caterpillar®
23 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
24 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
5 CIRCUIT BREAKERS
Figure 13 – Wye Voltage Transformer The circuit breaker is an integral
Connection
component in switchgear, opening
4.7.3 Control Power Transformers and closing a circuit by non-automatic
Control power transformers (CPTs) means and opening the circuit
are used for auxiliary power to space automatically on a predetermined
heaters, lights, and receptacles and over-current level without damage.
control of electrically operated Circuit breakers are located between
breakers when external auxiliary the power source and the load and
power sources are unavailable. play a crucial role in two of the main
CPTs, when used for control of functions of switchgear:
electrically operated breakers, should • Switching the load to and from
be connected on the source side of the generator.
the main breaker so the control power
is available to close the main breaker. • Protecting the generator from
short circuits and overloads.
Some of the main features of CPTs
are listed below: All circuit breakers have the
following common design and
• Step the primary voltage down
functional characteristics:
to 120/240VAC.
• Frame.
• Provide 120/240VAC power
for heaters, lights, and breaker • Contacts and operating
control. mechanisms.
• Mounted in a drawout auxiliary • Trip units.
drawer up to 15kVA. • Arc extinguishing methods.
• Fix mounted in the rear of the • Mounting methods.
structure and provided with a
©2007 Caterpillar®
25 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
26 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
Rated (Maximum) 254V, 508V, 635V or 600V for integrally 120, 120/240, 240, 277, 347, 480Y/277,
Voltage fused CB’s 480 600Y/347 or 600 Vac
Rated Short - Time Carry for (2) 0.5 sec. periods (1 second Not specified
Current withstand)
Short-Circuit O -15 sec. - CO
O - (2 to 60 min.) - CO
Operating Duty
e.g. 4000A frame – 1,500 open/close
500 Drawout Operations
operations
Mechanical e.g. 800A Frame – 12,500 open/close
800A frame – 3,500 open/close
Endurance operations with maintenance every
operations
1,750 operations
No maintenance possible
Continuous - Current
UL 1066 UL 489
Test Requirements
Enclosure Required Optional
Allowable
Temp. Rise Total Temp Temp. Rise Total Temp
Temperature Limits
Internal Circuit Limit = Insulating Materials Capability
85ºC 125ºC
Breaker Contacts
Connections 85ºC 125ºC Limit = Insulating Materials Capability
At Terminal
55ºC 95ºC 50ºC 90ºC
Connection
Insulating Materials C37.13, Table 2 Table 7.1.4.1.1
Figure 15 – Low Voltage Circuit Breaker Standards Comparison
©2007 Caterpillar®
27 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
5.1 80% vs. 100% Rating labeled with special wiring and
installation.
All circuit breakers are tested
to carry their full current rating 5.1.1 NEC Requirements
indefinitely. However, the NEC With regards to the issue of over-
requires that circuit breakers and current protection, Section 210.20
circuit conductors be sized at 125% of the NEC states:
of their applied, continuous loads. The “Branch-circuit conductors and
purpose of this requirement is to build equipment shall be protected by
a “safety factor” into installations. over-current protective devices
Standard (80%) rated circuit that have a rating or setting that
breakers are tested in open air at complies with 210.20(A) through (D).
40°C ambient and required to carry (A) Continuous [loads lasting longer
their rated current without tripping than 3 hours] and Non-continuous
within specific operating temperature Loads. Where a branch circuit supplies
guidelines. However, in actual continuous loads, or any combination
installations, circuit breakers are often of continuous and non-continuous
installed in equipment with little or no loads, the rating of the over-current
ventilation. If the breaker carries its device shall not be less than the non-
full current rating, the temperature continuous load plus 125 percent of
inside the equipment (at the breaker, the continuous load. Exception: Where
and on the conductors) could be the assembly, including the over-
higher than rated limits. By restricting current devices protecting the branch
the amount of current flowing in each circuit(s), is listed for operation at
device, the NEC limits the heat to safe 100% of its rating, the ampere rating
levels. of the over-current device shall be
permitted to be not less than the sum
Both the NEC and UL489 (Molded of the continuous load plus the non-
Case Circuit Breaker Test Standard) continuous load.”
allow for testing and usage at 100%
current rating if the breaker, It is important to note that installing
conductors and enclosure are tested a 100% rated breaker in an assembly
and certified to make sure that the does not necessarily mean that the
temperature inside the enclosure will entire assembly is 100% rated. An
not exceed limits. The test is assembly may only be listed for 100%
conducted with the Circuit breaker operation after it has successfully
installed in the smallest enclosure they passed separate testing by UL, as
could be used in and the breaker must an assembly, per UL requirements.
carry 100% rated current until
maximum temperatures are reached. 5.2 Types of Circuit
The circuit breaker cannot trip and the Breakers
temperature rise at the customer
connection cannot exceed 60° C 5.2.1 Low Voltage Circuit Breakers
above ambient. If the temperature rise Low voltage circuit breakers are
exceeds 50°C, the breaker must be available in molded-case, insulated
case, and power type. When
specifying circuit breakers, the
©2007 Caterpillar®
28 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
29 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
30 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
Vacuum
Interrupter
Primary
Disconnects
©2007 Caterpillar®
31 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
32 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
There are several types of SF6 cooler gas to help cool the arc.
interrupter designs; the two most Contact erosion is also reduced
common types are: due to the rapid arc movement.
• Puffer. At current zero, the arc is cooled
• Rotary arc. and extinguished.
Puffer: 5.3 Trip Units
The puffer-type interrupter is more
complicated than the rotary arc-type. Trip units are most commonly found
on low voltage applications. The trip
units serve as the logic control for the
During current interruption a piston
breaker. There are two types of trip
compresses the SF6 gas in a cylinder,
units:
all of which is contained in an epoxy-
type enclosure. After the main • Thermal magnetic.
current-carrying contacts separate • Electronic.
the current transfers to the arcing
Thermal magnetic units offer a
contacts. Once the arcing contacts
delay in the event of overload while
separate the SF6 gas in the
responding quickly to excessive
compression chamber blasts the arc
current. Magnetic-only units are
through the nozzle. The heat created
mainly used to protect motors and
by the arc breaks the SF6 molecules
fire pumps in a high-heat application.
into fluorine and sulfur. Arc energy
is absorbed and the arc is cooled. Electronic trip units provide more
sophisticated protection and monitor-
As current zero is approached the
ing by measuring and comparing
heat energy subsides as more SF6
actual current with a reference table
gas flows through the nozzle and
of values to determine the appropriate
extinguishes the arc.
response. A variety of settings make
Rotary Arc:
it possible to adapt the breaker to the
The rotary arc technology is less precise characteristics of the
complicated than the puffer type; protected circuit.
however, it is not effective over as
wide a range of short circuit currents In addition, electronic trip units offer
and voltages as the SF6 puffer or communication and monitoring
vacuum CBs. capabilities. Current demand and
ground fault current can be monitored
As the contacts separate the arc
as well as breaker status, settings of
transfers from the main contacts to
protection functions, and trip history.
an annular contact; this causes the
current to switch into the coil behind Residual current devices that provide
it. The coil’s magnetic field, produced earth leakage protection are also
by the load current, causes the arc to available, as well as a broad range
rotate rapidly. The arc is cooled by of accessories.
moving through the SF6 gas. Four trip unit protective functions
The SF6 gas is normally at rest inside exist:
the interrupter. The arc’s movement 1. Long Delay (L).
acts like a mixer, mixing hotter and
©2007 Caterpillar®
33 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
34 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
35 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
36 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
Code Plates
Levering Mechanism
Ground Bar
Figure 27 – Medium Voltage Breaker Pan Assembly
Where:
5.5 Sizing Circuit Breakers
kW = net rating of the generator
A circuit breaker is required to set
connect or disconnect the electrical Volts = system voltage, phase-to-
load to and from the generator. To phase or line-to-line
size the circuit breaker and switchgear
pf = power factor of the system
the following formula should be used:
load
Breaker Size (in amperes) Constants:
1000 – to convert kW to watts
1.732 – for three-phase system
©2007 Caterpillar®
37 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
38 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
39 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
40 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
41 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
42 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
43 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
ready to accept the load takes the and the contingency outages under
first priority loads. As capacity which a system may be designed
becomes available, the next highest to operate satisfactorily.
prioritized load is powered. This For those conditions where the
process repeats until all loads are systems capability is exceeded,
applied. processes must be in place to
Smaller load steps equate to smaller automatically monitor power systems
transients, which result in smoother loading levels and reduce loading
transitions. For example, a medical when required. A load-shed system
center might prioritize lifesaving automatically senses overload
equipment as the number one need. conditions and sheds enough load to
relieve the overloaded generator sets
That equipment (or special outlets
before there is loss of generation, line
for that equipment) is the first
tripping, equipment damage, or a
supplied with electricity from the first
chaotic random shutdown of the
available generator set. Lights may
system.
be identified as the second most
important need and handled by the For example, in a factory all welding
second load step. equipment and other machines may
be operated at capacity at the same
When starting generator sets
time between 10 am and 12 noon and
without a preferred load order it is
then again between 1 pm and 3 pm.
suggested that the largest loads are
During these times the load to lights
started first.
in the lunchroom and parking lot
The largest transient will occur would be shed because they are less
before the system is heavily loaded. of a priority.
These large loads will have the least
Conversely, load-add circuits
effect on the rest of the system.
serve to bring loads online based
6.3.3 Load Shed/Add on available capacity of the power
When speaking of load system. Prioritization will dictate
shedding/adding this document is the order the loads come online.
referring to local loads served by
6.3.4 Dead Bus Arbitration
the switchgear and generator power
When multiple generators are
system. The utility industry uses
simultaneously started, their outputs
the term load shedding to mean
are not synchronized when they reach
disconnecting their service to users
rated speed and voltage. If more
as a means to manage capacity.
than one generator is allowed to
Power systems are designed and simultaneously close to the de-
operated so that for any normal energized (dead) bus, an out of phase
system condition, including a defined paralleling situation occurs. Therefore,
set of contingency conditions, there one generator must be selected to
are adequate generating and close to the dead bus prior to the
transmission capacities to meet load other generators initiating
requirements. However, there are synchronization.
economic limits on the excess
capacity designed into a system
©2007 Caterpillar®
44 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
45 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
46 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
47 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
48 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
49 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
50 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
from lead wire to lead wire across where the CTs are located. With AC
the air gap. generators the ammeter usually has a
Surge arrestors function best when 5A movement and must be used with
located close to generator output a current transformer.
leads.
7.4 Voltmeter
7 METERING Used to measure voltage, the
It is essential that critical values be voltmeter is often designed for 120V
measured and displayed for reference full-scale deflection and must be used
and control purposes. For switchgear with potential transformers (PTs). The
typical metering parameters are: voltmeter designed for wall-mounted
• Utility metering. switchgear can take the full voltage of
the system up to and including 600V.
• Trip unit metering. On floor-standing switchgear, the
• Generator/generator set voltmeter works on full voltage of
metering. 208V maximum. For voltage beyond
• System metering. 208V, PTs are used.
• Revenue metering.
7.5 Frequency Meter
7.1 Discrete Analog vs. This monitors the frequency of the
Virtual Metering AC sine wave of the source or bus.
©2007 Caterpillar®
51 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
52 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
53 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
to 5%; a minimum of 2.5% is required are set for isochronous (zero speed
to maintain stability in a speed-droop droop) operation, except with an
governor. Droop is calculated with the electric load-proportioning governor
following formula: (see 9.5.4).
No _ Load _ Speed − Full _ Load _ Rated
% Droop = X 100
Full _ Load _ Rated _ Speed 9.3 Synchronizing
If, instead of a decrease in speed
Synchronization, as applied to the
setting an increase takes place, the
electric power generation, is the
governor shows negative droop.
matching of the output voltage
Negative droop will cause instability
waveform of one alternating current
in a governor.
electrical generator with the voltage
Simple hydro-mechanical governors waveform of another alternating
have the droop function built in and current electrical system. For two
always operate in droop. More systems to be synchronized, five
complex governors include temporary conditions must be matched:
droop which returns the speed setting • The direction of rotation of these
to its original speed setting after the phases.
engine has recovered from a change • The voltage amplitudes of the
in speed or load. The temporary droop two systems.
is known as “compensation.”
• The frequencies of the two
Why Is Droop Necessary? systems.
In a system without droop, a load • The phase angle of the voltage
increase will cause the engine to of the two systems.
slow down.
The first two conditions are
The governor will respond by determined when the equipment is
increasing the fuel until the engine specified, installed, and wired. A
speed has returned to the original voltage regulator usually controls
speed. the output voltage of a generator
Due to the combined properties automatically. The last two
of inertia and power lag, the engine conditions, frequency matching and
speed will continue to increase phase matching, must be accounted
beyond the original speed setting, for each time the tie-breaker is closed,
causing an overshoot in speed. paralleling the generator sets or
The governor again will respond to systems.
decrease speed to correct for the 9.3.1 Rotation of Phases
overshoot. It will over-correct the Each generator set or system being
speed in the other direction causing paralleled must be connected so all
undershoot. This overcorrection of phases rotate in the same direction.
speed in both directions (instability) If the phase rotation is not the same,
will amplify until the engine shuts no more than one phase can be
down on over-speed. synchronized (see Figure 42).
It is impossible to have stable
parallel operation if two or more units
©2007 Caterpillar®
54 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
GENERATOR A 120
120 120
C
0° 120° 200°
A C B
A 120 B
120 120
©2007 Caterpillar®
55 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
Bus
©2007 Caterpillar®
56 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
57 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
not exist in the same phase of units an offline unit with an online
being paralleled. generator are shown below.
To meet the second and fourth
conditions the engine governors must
be adjusted to give similar frequency
under conditions of proportionate load
sharing. If one set is trying to operate
at a lower frequency than the others
the active or kW load will not be
proportionately shared and motoring
current will flow to the lower
frequency machine to make it
run at synchronous speed.
There are many manual-paralleling
methods in use; a common method of Figure 47 – Synchronizing Lights
manual paralleling is through the use 1. The online circuit breaker should
of synchronizing lamps. be closed and the offline
(incoming) circuit breaker should
To parallel a generator set with one
be open.
or more generator sets already on the
line, the first three conditions must 2. With the incoming unit governor
first be met. If there is a difference control lever in the full-governed
between the frequencies or voltages speed position, turn on the
of the generators being paralleled synchronizing lamps switch
there will be an undesirable line and observe the lamps for the
voltage disturbance when the frequency at which they flash.
incoming generator circuit breaker is By means of the governor control
closed. Extensive damage may result vary the incoming engine speed
if generators are paralleled while the until the synchronizing lamps
voltages are out of phase. In order to come on and fade out about six
manually parallel generator sets, it is to ten times a minute. Always
necessary to use one of two methods: have the incoming generator
(1) synchronizing lamps or (2) a initially slightly higher in
synchroscope. frequency; doing this will assure
that the incoming generator set
Example – Synchronizing Lamps: will absorb a small amount of
The dark lamp method is most load instead of consuming power
commonly used as the indicator of when initially connected to the
when to close the incoming circuit bus.
breaker. This method lights the 3. To put the generator set online
synchronizing lamps when there is a and in-sync with the online
potential between the phases of the source wait until the lamps are
incoming and the online generators. dark and then very quickly, while
This means that when all the lamps the lamps are still dark, close the
are dark the generators are circuit breaker. The incoming
synchronized. Steps for synchronizing
©2007 Caterpillar®
58 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
59 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
60 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
61 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
I1 = 50A I2 = 50A
Generators
Generator Generator
Circulating currents exist in G1 G2
Load
1 MW
paralleled generators when multiple 479 Volts 481 Volts
generators are attempting to operate
at different voltages although they are
connected through the common bus.
This current will exist when the Figure 52 – Paralleled Generators –
internal excitation voltage produced Unbalanced Voltage
by each generator is slightly different In practice the manual, precise
but the terminal or bus voltage is the matching of voltages is not possible.
same. These circulating currents Some means must be provided to
reduce the effective excitation of one make load sharing between paralleled
or more generators and increase the generators simple to control.
effective excitation of others.
Because circulating current or load
Generator voltage is directly related
unbalance is the result of voltage
to exciter output; hence an attempted
mismatch, the voltage regulator will
generator voltage difference is the
act as the control system using
result of different exciter output.
paralleling compensation circuits
The voltage regulator controls exciter
called reactive droop compensation or
output. Control of circulating currents
reactive cross-current compensation.
is accomplished by biasing the voltage
regulator. The principle of operation of the
reactive droop circuit can be described
An example to illustrate the effect of
by the curve in Figure 53.
the voltage regulator on the generator
system can be seen using two
©2007 Caterpillar®
62 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
IL = 100A
I1 = 50A I2 = 50A
Generator Generator
Load
G1 G2
100 A
480 Volts 480 Volts
©2007 Caterpillar®
63 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
64 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
65 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
66 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
67 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
68 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
69 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
70 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
inspect and service them more very little equipment. Devices are
frequently. available from manufacturers which
can also be used to check calibration
Routine maintenance of the
and timing; these devices are
switchgear should involve cleaning
relatively inexpensive. Equipment for
of the structure and especially the
testing magnetically operated trip
insulating supports for the bus.
devices is much more expensive. For
• All electrical connections should this reason, testing of these magnetic
be checked to make sure that bolts trip devices often is not practical;
and terminal screws are tight. however, they should be inspected
• Relays should be tested in to see that parts move freely.
accordance with the Where dashpots are used for timing,
manufacturer’s instructions. they should be inspected to be sure
• Megohmeter tests may be made to that the oil is clean and it flows freely
check the insulation of both the through the orifice.
primary circuits and the control
circuits. Records of these readings 12.2 Spare Parts
should be kept; a low megohmeter Depending on the criticality of the
reading may not indicate trouble application, ample supply of spare
but a reading which has been parts may be recommended.
falling steadily over a period of
time indicates that trouble is 12.3 Safety
developing and corrective action
should be taken. Safety is one of the most important
considerations with switchgear
Care of the circuit breakers involves
planning and maintenance. It requires
periodic inspection, cleaning, and
a periodic review of all equipment
lubrication. Frequency of servicing
and operations by a qualified, safety-
will depend on conditions of the
minded, and trained team. The team
atmosphere and frequency of
must know and be familiar with all of
operation. Breakers, which are
the equipment they operate.
operated several times daily, should
be serviced more frequently. Whether high-voltage lines or
However, breakers which are not feeders should be grounded after
required to be operated for long being de-energized so that men can
periods of time should be opened and safely work on them depends upon
closed several times every two or the qualifications of the men doing
three weeks to burnish the contacts the grounding, since it is necessary
and make sure that all moving parts for the line to be dead before it is
operate freely. When servicing, make grounded. The hazards are great
sure all bolts are tight. and the consequences are very
serious if energized.
When possible, check the over-
current trip devices to be sure they 12.3.1 NFPA 70E
are operating properly. With static trip NFPA 70E is the Standard for
devices, a function test of the over- Electrical Safety Requirements for
current trip device can be made with Employee Workplaces. This standard
©2007 Caterpillar®
71 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
72 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
73 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
74 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
75 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
76 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
25 SYNCHRONIZING OR
14 APPENDICES SYNCHRONIZM-CHECK DEVICE is
a device that operates when two
14.1 Appendix A AC circuits are within the desired
Device Number Function and limits of frequency, phase angle,
Description or voltage to permit or to cause
1 MASTER ELEMENT is the initiating the paralleling of these two
device, such as a control switch, circuits.
voltage relay, float switch, etc. 27 UNDER-VOLTAGE RELAY is a
which serves either directly or device that functions on a given
through such permissive devices value of under-voltage.
as protective and time-delay relays 32 DIRECTIONAL POWER RELAY is a
to place a piece of equipment in or device that functions on a desired
out of operation. value of power flow in a given
2 TIME-DELAY STARTING OR direction or upon reverse power.
CLOSING RELAY is a device 38 BEARING PROTECTIVE DEVICE
which functions to give a desired is a device that functions on
amount of time delay before or excessive bearing temperature
after any point of operation in a or on other abnormal mechanical
switching sequence or protective conditions associated with the
relay system, except as bearing such as undue wear, which
specifically provided by device may eventually result in excessive
functions 48, 62, and 79. bearing temperature or failure.
Also known as a Timer.
39 MECHANICAL CONDITION
12 OVER-SPEED DEVICE is usually MONITOR is a device that
a direct-connected speed switch functions upon the occurrence of
which functions on machine over- an abnormal mechanical condition
speed. Generally covered within (except those associated with
the protective scheme of the bearings as covered under device
generator controller or engine function 38) such as excessive
controller device. vibration, eccentricity, expansion,
15 SPEED OR FREQUENCY shock, tilting or seal failure.
MATCHING DEVICE is a device 40 FIELD RELAY is a relay that
that functions to match and hold functions on a given or abnormally
the speed or frequency of a low value or failure of machine
machine or of a system equal to, field current, or on an excessive
or approximate to, that of another value of the reactive component
machine source or system. Also of the armature current in an AC
known as a Synchronizer. machine indicating abnormally low
21 DISTANCE RELAY is a relay field excitation.
that functions when the circuit 41 FIELD CIRCUIT BREAKER is a
admittance, impedance, or device that functions to apply
reactance increases or decreases or remove the field excitation
beyond pre-determined limits. of a machine.
©2007 Caterpillar®
77 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
78 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
79 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear
©2007 Caterpillar®
80 All rights reserved.
Application & Installation Guide Generator Paralleling Switchgear