You are on page 1of 2

• F-1100 SINGLE TURBINE •

INSERTION FLOW METER


FREQUENCY OUTPUT

Made in the USA

DESCRIPTION CALIBRATION
ONICON insertion turbine flow meters are Every ONICON flow meter is wet-calibrated in
suitable for measuring electrically conductive our flow laboratory against primary volumetric
water-based liquids. The F-1100 model provides standards directly traceable to NIST. Certification
a high-resolution frequency output for connection of calibration is included with every meter.
to an ONICON Display or BTU Meter.
FEATURES
APPLICATIONS Unmatched Price vs. Performance - Custom
• Chilled water, hot water, condenser calibrated, highly accurate instrumentation
water, and water/glycol/brine for HVAC at very competitive prices.
• Process water and water mixtures Excellent Long-term Reliability - Patented
• Domestic water electronic sensing is resistant to scale and
particulate matter. Low mass turbines with
GENERAL SPECIFICATIONS engineered jewel bearing systems provide a
mechanical system that virtually does not wear.
ACCURACY
± 0.5% OF READING at calibrated velocity Industry Leading Two-year "No-fault" Warranty -
± 1% OF READING from 3 to 30 ft/s (10:1 range) Reduces start-up costs with extended coverage
± 2% OF READING from 0.4 to 20 ft/s (50:1 range) to include accidental installation damage
SENSING METHOD (miswiring, etc.). Certain exclusions apply; see
Electronic impedance sensing our complete warranty statement for details.
(non-magnetic and non-photoelectric)
PIPE SIZE RANGE Simplified Hot Tap Insertion Design - Standard on
1¼" through 72" nominal every insertion flow meter. Allows for insertion
SUPPLY VOLTAGE and removal by hand without system shutdown.
24±4 V AC/DC at 30 mA
LIQUID TEMPERATURE RANGE
Standard: 180˚ F continuous, 200˚ F peak
High Temp: 280˚ F continuous, 300˚ F peak OPERATING RANGE FOR
Meters operating above 250˚ F require COMMON PIPE SIZES
316 stainless steel construction option 0.17 TO 20 ft/s
AMBIENT TEMPERATURE RANGE ± 2% accuracy begins at 0.4 ft/s
-5 to 160˚ F (-20 to 70˚ C) Pipe Size (Inches) Flow Rate (GPM)
OPERATING PRESSURE
1¼ 0.8 - 95
400 PSI maximum 1½ 1 - 130
PRESSURE DROP 2 2 - 210
Less than 1 PSI at 20 ft/s in 1½" pipe, 2½ 2.5 - 230
decreasing in larger pipes and lower velocities 3 4 - 460
4 8 - 800
OUTPUT SIGNAL PROVIDED: 6 15 - 1800
FREQUENCY OUTPUT 8 26 - 3100
0-15 V peak pulse, typically less than 300 Hz 10 42 - 4900
12 60 - 7050
(continued on back) 14 72 - 8600
16 98 - 11,400
18 120 - 14,600
20 150 - 18,100
24 230 - 26,500
30 360 - 41,900
36 510 - 60,900

2103 / 0212PA 1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699 12-28-00
www.onicon.com E-mail: sales@onicon.com
F-1100 SPECIFICATIONS cont. F-1100 Wiring Information
MATERIAL
Wetted metal components
Standard: Electroless nickel plated brass WIRE COLOR CODE NOTES
Optional: 316 stainless steel
ELECTRONICS ENCLOSURE (+) 24 V AC/DC Connect to power supply
RED
supply voltage, 30 mA positive
Standard: Weathertight aluminum enclosure
Optional: Submersible enclosure (–) Common ground Connect to power supply
BLACK
ELECTRICAL CONNECTIONS (Common with pipe ground) negative
3-wire for frequency output (+) Frequency output Signal for ONICON
Standard: 10' of cable with ½" NPT conduit GREEN signal: 0-15 V peak Display or BTU meter
connection pulse
Optional: Indoor DIN connector with 10' of
plenum rated cable

F-1100 Wiring Diagram


ONICON Display
or BTU Meter

ALSO AVAILABLE RED


GREEN
+ 24 V
FREQUENCY INPUT
BLACK GROUND

Note: Black wire is common with the pipe ground


SEL RST
(typically earth ground).
GPM

463798

POWER

SYSTEM-1
BTU METER

POWER

Display BTU Measurement


Modules Systems

Typical Meter Installation • Acceptable to install in vertical pipe


(New construction or scheduled shutdown) • Position meter anywhere in upper 180˚
for horizontal pipe

Optional output
signal(s) to
control system Onicon
Display or
BTU Meter
CLEARANCE
REQUIRED
FOR INSTALLATION
Connect factory wires Typically
to field wires in appropriate Detail of hot tap adapter 30" - 36"
junction box. with turbine assembly depending on
½" FNPT pipe size and
withdrawn
conduit connection height of valve
assembly.
Insertion depth
gage provided Standard Installation
with each meter Kit for Steel Pipe

1" Full port ball valve


1¼" for
1" Close nipple
hot tap
1" Branch outlet
ONICON INCORPORATED
1500 North Belcher Road
Clearwater, FL 33765 Minimum Hole Size = 1" FLOW
Tel (727) 447-6140 Must be centered
Fax (727) 442-5699
www.onicon.com
sales@onicon.com
Note: Installation kits vary based on pipe material and application. For installations in pressurized (live)
systems, use "Hot tap" 1¼ inch installation kit and drill hole using a 1 inch wet tap drill.
2103 / 0212B 12-28-00