www.tyco-fire.com
Contacts
Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General substantially lower-end head pres-
sures, as compared to ESFR Sprinklers
Description having nominal K-factors of 14.0 and
16.8. This feature offers flexibility when
TYCO Model ESFR-25 Pendent Sprin- sizing system piping, as well as possi-
klers are Early Suppression, Fast bly reducing or eliminating the need for
Response (ESFR) sprinklers having a a system fire pump.
nominal K-factor of 25.2 (Ref. Figure 1). Also, Model ESFR-25 Sprinklers permit
They are suppression-mode sprinklers use of a maximum deflector-to-ceiling
that are especially advantageous as a distance of 18 in. (460 mm) versus 14
means of eliminating the use of in-rack in. (356 mm). Additionally, a storage
sprinklers when protecting high-piled arrangement of 40 ft (12,2 m) with a
storage. ceiling height of 45 ft (13,7 m) does not
The Model ESFR-25 Sprinklers are pri- require in-rack sprinklers as do other
marily used for ceiling-only sprinkler ESFR Sprinklers having nominal K-fac-
protection of, but not limited to, the fol- tors of 14.0 and 16.8.
lowing storage applications: The Model ESFR-25 Sprinklers are to obtain complete installation guide-
• most encapsulated or non-encap- listed by Underwriters Laboratories lines. The general guidelines in this
sulated common materials including (UL) for specific applications with data sheet are not intended to provide
cartoned, unexpanded plastics a maximum storage height of 43 ft complete installation criteria.
(13,1 m) with a maximum ceiling height
Sprinkler
• uncartoned (exposed) expanded of 48 ft (14,6 m) without the require-
plastics in accordance with NFPA 13 ment for in-rack sprinklers. Refer to the
and FM Global standards
• some storage arrangements of rub-
Specific Application Listing (UL) for the
design criteria. Identification
ber tires, roll paper, flammable liq-
uids, aerosols, and automotive
Applications for the TYCO ESFR Sprin-
klers are expanding beyond currently
Number (SIN)
components recognized installation standards. For Refer to Table A for sprinkler identifica-
For more specific criteria, refer to Table information on research fire tests, such tion number.
B as well as the applicable design as with flammable liquids and aerosols,
standard. that may be acceptable to an author-
ity having jurisdiction, contact Techni- Technical
The Model ESFR-25 Pendent Sprin-
klers provide the system designer
cal Services.
Data
with hydraulic and sprinkler place- NOTICE Approvals
ment options not presently available to UL and C-UL Listed
the traditional ESFR sprinklers having The Model ESFR-25 Sprinklers
described herein must be installed FM Approved
nominal K-factors of 14.0 and 16.8. In VdS Approved
particular, the Model ESFR-25 Sprin- and maintained in compliance with this
NYC Approved under MEA 356-01-E
kler has been designed to operate at document, as well as with the applica-
LPCB Certified (Cert. Nos. 094b and 007l)
ble standards of the National Fire Pro- CE Certified (Certificate of Conformity
IMPORTANT tection Association (NFPA), in addition 1725-CPR-F0010)
Refer to Technical Data Sheet to the standards of any authorities
TFP2300 for warnings pertaining to having jurisdiction, such as FM Global. Finish
Failure to do so may impair the perfor- Natural Brass
regulatory and health information.
mance of these devices. Physical Characteristics
Always refer to Technical Data Frame ���������������������������������������������������������Brass
Sheet TFP700 for the “INSTALLER The owner is responsible for main-
Deflector ���������������������������������������������������Bronze
WARNING” that provides cautions taining their fire protection system Compression Screw �������������������� Stainless Steel
with respect to handling and instal- and devices in proper operating con- Hook ��������������������������������������������������������MONEL
lation of sprinkler systems and com- dition. Contact the installing contrac- Strut ���������������������������������������������������������MONEL
ponents. Improper handling and tor or product manufacturer with any Link Assembly ��������������������������������Solder, Nickel
installation can permanently damage questions. Button ���������������������������������������������������������Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
a sprinkler system or its compo- In all cases, the appropriate NFPA or Ejection Spring ������������������������������������ INCONEL
nents and cause the sprinkler to fail FM Global installation standard, or
to operate in a fire situation or cause other applicable standard, must be Additional Technical Data
it to operate prematurely. referenced to ensure applicability and Refer to Table A for additional techni-
cal data.
Page 1 of 6 AUGUST 2018 TFP312
TFP312
Page 2 of 6
7 1" NPT
Components: 8 1-13/16"
9/16" (46,0 mm)
1 - Frame
(14,3 mm)
2 - Deflector
9 NOMINAL
3 - Compression MAKE-IN
Screw
4 - Hook 6
5 - Strut
6 - Link Assembly 3-13/16"
5 (96,8 mm) THERMAL
7 - Button SENSING
8 - Sealing ELEMENT
Assembly
4
9 - Ejection Spring WRENCH
FLATS
3
2
TEMPERATURE
RATING
2" (50,8 mm)
FIGURE 1
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE
The fusible link assembly is com- Sprinkler Identification Number (SIN) TY9226
prised of two link halves that are joined
together by a thin layer of solder. When K-factor, gpm/psi½ (lpm/bar½) 25.2 gpm/psi½ (362,9 lpm/bar½)
the rated temperature is reached, the
165˚F (74˚C)
solder melts and the two link halves Temperature Rating ˚F (˚C) 212˚F (100˚C)
separate, activating the sprinkler and
flowing water. Thread Size 1 in. NPT or ISO 7-R 1
Criteria Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Response Type QR QR
Refer to FM Global
Idle Pallet Storage Refer to NFPA 13 2-0, 8-9, and 8-24
Refer to FM Global
Rubber Tire Storage Refer to NFPA 13 2-0 and 8-3
TABLE B
MODEL ESFR-25 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Description Specification, UL
165˚F (74˚C)
Temperature Rating ˚F (˚C) 212˚F (100˚C)
Response Type QR
Minimum of 4 in. (100 mm) from walls but no more than 1/2 the
Deflector Distance from Walls allowable distance permitted between sprinklers
Storage Arrangement Palletized, solid piled, open frame; single row or double row
NFPA 13 for ESFR Sprinklers based upon 45 psi (3,1 bar) design
Sprinkler System Design pressure 169 gpm (640 lpm) with 12 sprinkler remote area
Hose Stream allowance and Water Supply Duration 250 gpm for 60 minutes (950 lpm for 60 minutes)
TABLE C
MODEL ESFR-25 PENDENT SPRINKLER
SPECIFIC APPLICATION LISTING (UL)
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TFP312
Page 5 of 6
Installation
temperature rating), with Natural Brass
Automatic sprinklers must never be finish, P/N (specify):
painted, plated, coated, or other-
TYCO Model ESFR-25 Early Suppres- 165°F (74°C) . . . . . . . . . . . . . . . . . . 58-441-1-165
wise altered after leaving the factory. 212°F (100°C) . . . . . . . . . . . . . . . . . 58-441-1-214
sion, Fast Response 25.2K Pendent Modified sprinklers must be replaced.
Sprinklers must be installed in accor- Sprinklers that have been exposed to Special Order
dance with this section. corrosive products of combustion, but Sprinkler Assemblies with
General Instructions have not operated, should be replaced ISO 7-1 Thread Connection
Damage to the fusible Link Assem- if they cannot be completely cleaned Specify: Model ESFR-25, Early Sup-
bly during installation can be avoided by wiping the sprinkler with a cloth or pression, Fast Response 25.2K
by handling the sprinkler by the frame by brushing it with a soft bristle brush. Pendent Sprinklers (TY9226) with
arms only and by using the appropri- Care must be exercised to avoid ISO 7-1 thread connection, (specify
ate sprinkler wrench. Do not apply damage to the sprinklers before, temperature rating), with Natural Brass
pressure to the fusible Link Assembly. during, and after installation. Sprin- finish, P/N (specify):
Failure to do so can lead to an unstable klers damaged by dropping, striking, 165°F (74°C) . . . . . . . . . . . . . . . . . 58-442-1-165
link assembly and premature activation wrench twist/slippage, or the like, must 212°F (100°C) . . . . . . . . . . . . . . . . 58-442-1-214
of the sprinkler. Damaged sprinklers be replaced. Also, replace any sprinkler Sprinkler Wrench
must be replaced. that has a cracked bulb or that has lost Specify: W-Type 1 Sprinkler Wrench,
A leak-tight 1 in. NPT sprinkler joint liquid from its bulb. Refer to Installation P/N 56-872-1-025
should be obtained by applying a min- section for additional information.
imum-to-maximum torque of 20 to 30 The owner is responsible for the
lb-ft (26,8 to 40,2 N∙m). Higher levels inspection, testing, and maintenance of
of torque can distort the sprinkler inlet their fire protection system and devices
with consequent leakage or impairment in compliance with this document, as
of the sprinkler. well as with the applicable standards
Note: Install the Model ESFR-25 of the National Fire Protection Associ-
Pendent Sprinkler in the pendent posi- ation, such as NFPA 25, in addition to
tion (Ref. Figure 2). the standards of any authorities having
jurisdiction. Contact the installing con-
Step 1. With pipe thread sealant tractor or product manufacturer with
applied, hand-tighten the sprinkler into any questions.
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle Automatic sprinkler systems are rec-
the Model ESFR-25 Pendent Sprinkler ommended to be inspected, tested,
only by the Frame arms. and maintained by a qualified Inspec-
tion Service in accordance with local
Step 2. Wrench-tighten the Model requirements and/or national codes.
ESFR-25 Pendent Sprinkler using only
the W-Type 1 Sprinkler Wrench (Ref.
Figure 2) and by fully engaging (seating)
the wrench on the sprinkler wrench
flats (Ref. Figure 1).
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-25
Pendent Sprinkler for damage. In par-
ticular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figure 1, and that the Link Assem-
bly is not bent, creased, or forced out
of normal position in any way. Replace
damaged sprinklers.
TFP312
Page 6 of 6