TEST mode
This mode is the same as AUTO, except that the paralleling com-
mand is not passed to the circuit breaker, but is displayed on
the system.
U1 Line-/busbar voltage
U1 SYNCHROTACT CSS U2 Generator voltage
CB Circuit breaker
G Generator
CMD AVR Automatic voltage regulator
CB TR Turbine regulator (governor)
CMD Paralleling command
U+, U- Voltage adjusting commands
U2 f+, f- Frequency adjusting commands
U+
AVR U-
G f+
TR f-
Test
synchronizing Two circuit breakers
SYNCHROTACT CSS
Synchronizing
CB 1
Manual paralleling 1
switch G
AVR
CB 2
TR
AVR
G
TR
CB 2
Manual paralleling Synchrocheck G
AVR
switch TR
AVR
G
TR
Single channel version structured differently in terms of hardware and software, will
The circuit breaker is closed by the synchronizing device display the same malfunction simultaneously. The extra price
or by manual paralleling. of a dual channel system usually amounts to only a fraction of
the possible consequential costs of incorrect paralleling.
Dual channel version
An independent synchrocheck is connected in series, in both One or two circuit breakers
operating modes. This allows a degree of reliability, which is In the versions designed for two circuit breakers, the con-
already high in single channel systems, to be improved even nection of the selected paralleling point is integrated into
further. It is unlikely that both channels, which are each the SYNCHROTACT CSS.
Synchronizing instruments
–– Double voltmeter
–– Synchroscope
–– Double frequency meter
Controls
–– Key switch to enable paralleling of zero-voltage lines
–– Control mode selector switch: remote/local
–– Operating mode selector switch: AUTO/0/MAN/TEST
–– Push button switch to pre-select the circuit breaker
which is to be synchronized (in versions designed for two
circuit breakers)
–– Push-buttons to start or stop the synchronizing
process
–– Push-buttons to release the paralleling command and
manual paralleling
–– Push-buttons raise/lower commands for voltage and
frequency
Front view with all operation and display instruments Rear view of SYNCHROTACT CSS: all terminals and the synchrocheck
SYN 5100 are accessible from the rear
SIGNALISATION
remote / local
Start CMD
Stop
CB1 SELECTOR
CB2 AUTO / MAN / TEST U+/-; f+/-
CB1
CB2
Start/Stop Start / Stop
CMD AUTO
CB1 MAN SYN 5100
Feedback CB1 CLOSED TEST
AVR
G
~ TR
U+/-; f+/- U1/U2
U1/U2
CMD
CHK
CB1 / CB2
AVR
CB1
G U+/-; f+/-
CB2
~ TR
Single line schematic diagram of a dual channel SYNCHROTACT CSS for two generator circuit breakers.
www.abb.com/synchrotact