Informe de dispositivos

Etiqueta: ________________________________

PC Host, COM6 [HART Communication], HARTCH, [Waterpilot


Ruta de comunicación:
2x / FMX 21 / V1.00.xx]:0
Creado por: Marcobre
Creado en: domingo, 16 de mayo de 2021 11:15:26
Estado DTM: En línea
Dirección del dispositivo: 0
Número de serie: P5039B01122
Tipo de dispositivo: Waterpilot 2x / FMX 21 / V1.00.xx
Proveedor: Endress+Hauser
Clase: Level
Versión: 1.4.188.39
Página 1 de 8
Versión DTM: 1.4.188

Página 2 de 8
OnlineParameterize
Online Parameterize
Language
Display/Operat.
Parameter Value
Format 1st value Auto

Setup
Parameter Value
Measuring mode Pressure
Press. eng. unit mbar
Corrected press. 268.3mbar
Pos. zero adjust Abort
Set LRV 0.0000mbar
Set URV 400.0000mbar
Damping value 2.0s
Pressure af.damp 268.2mbar

Extended setup
Parameter Value
Code definition 0
Device tag ________________________________
Operator code 0

Current output
Parameter Value
Alarm behav. P Warning
Output fail mode Max
High alarm curr. 22.000mA
Set min. current 3.8 mA
Output current 14.730mA
Get LRV Abort
Set LRV 0.0000mbar
Get URV Abort
Set URV 400.0000mbar

Diagnosis
Parameter Value
Status Good
Diagnostic code No error
Instructions No action needed
Last diag. code S971 Adjustment
Min. meas.press. -18.8751221mbar
Max. meas.press. 256.4554138mbar

Página 3 de 8
Diagnostic list
Parameter Value
Diagnostic 1 No error
Instructions 1 No action needed
Diagnostic 2 No error
Instructions 2 No action needed
Diagnostic 3 No error
Instructions 3 No action needed
Diagnostic 4 No error
Instructions 4 No action needed
Diagnostic 5 No error
Instructions 5 No action needed
Diagnostic 6 No error
Instructions 6 No action needed
Diagnostic 7 No error
Instructions 7 No action needed
Diagnostic 8 No error
Instructions 8 No action needed
Diagnostic 9 No error
Instructions 9 No action needed
Diagnostic 10 No error
Instructions 10 No action needed

Event logbook
Parameter Value
Last diag. 1 S971 Adjustment
Last diag. 2 C482 Current simul.
Last diag. 3 F882 Input signal
Last diag. 4 C482 Current simul.
Last diag. 5 No error
Last diag. 6 No error
Last diag. 7 No error
Last diag. 8 No error
Last diag. 9 No error
Last diag. 10 No error

Instrument info
Parameter Value
Firmware version 01.00.06
Serial number P5039B01122
Ext. order code FMX21-BE251HGD15A+IRPO
Order identifier FMX21-2J4H4/0
Cust. tag number 3254-LIT
Device tag ________________________________
ENP version 02.01.01
Config. counter 70
LRL sensor -1000.00mbar
URL sensor 1000.00mbar
Manufacturer ID 17
Device type code 36
Device revision 1

Página 4 de 8
Measured values
Parameter Value
Meas. pressure 268.3mbar
Sensor pressure 255.3mbar
Corrected press. 268.3mbar
Pressure af.damp 268.3mbar
Sensor temp. 24.1°C

Simulation
Parameter Value
Simulation mode None

Reset
Parameter Value
Enter reset code 0

Expert
System
Parameter Value
Code definition 0
Operator code 0

Instrument info
Parameter Value
Cust. tag number 3254-LIT
Device tag ________________________________
Serial number P5039B01122
Firmware version 01.00.06
Ext. order code FMX21-BE251HGD15A+IRPO
Order identifier FMX21-2J4H4/0
ENP version 02.01.01
Electr.serial no P3084001C1A
Sensor serial no P500B801BCB

Display
Parameter Value
Format 1st value Auto

Management
Parameter Value
Download select. Device replacement
Enter reset code 0

Página 5 de 8
Measurement
Parameter Value
Measuring mode Pressure

Basic setup
Parameter Value
Pos. zero adjust Abort
Calib. offset 0.0000mbar
Damping value 2.0s
Press. eng. unit mbar
Temp. eng. unit °C
Sensor temp. 24.1°C

Pressure
Parameter Value
Set LRV 0.0000mbar
Set URV 400.0000mbar
Meas. pressure 268.3mbar
Sensor pressure 255.3mbar
Corrected press. 268.3mbar
Pressure af.damp 268.3mbar

Sensor limits
Parameter Value
LRL sensor -1000.00mbar
URL sensor 1000.00mbar

Sensor trim
Parameter Value
Lo trim measured -13.8378220mbar
Hi trim measured 978.4667969mbar
Lo trim sensor 0.0132mbar
Hi trim sensor 989.1536mbar

Output
Current output
Parameter Value
Output current 14.730mA
Alarm behav. P Warning
Output fail mode Max
High alarm curr. 22.000mA
Set min. current 3.8 mA
Get LRV Abort
Set LRV 0.0000mbar
Get URV Abort
Set URV 400.0000mbar
Startcurrent 12mA
Curr. trim 4mA 4.001mA
Curr. trim 20mA 20.000mA
Offset trim 4mA 0.000mA
Offset trim 20mA 0.000mA

Página 6 de 8
Communication
HART config
Parameter Value
Burst mode Off
Burst option Command 1
Current mode Signaling
Bus address 0
Preamble number 5

HART info
Parameter Value
Device type code 36
Device revision 1
Manufacturer ID 17
Hart version 6
Descriptor ________________
HART message ________________________________
HART date 20.05.19

HART output
Parameter Value
Primary value is Meas. pressure
Primary value 268.2255859mbar
Secondary val.is Corrected press.
Secondary value 268.2645874mbar
Third value is Sensor pressure
Third value 255.2714233mbar
4th value is Temp. sensor
4th value 24.1140442°C

HART input
Parameter Value
HART input value 0.0Unknown
HART input stat. Uncertain
HART input unit Unknown
HART input form. x.x

Application
Parameter Value
Electr. delta P Off

Página 7 de 8
Diagnosis
Parameter Value
Status Good
Diagnostic code No error
Instructions No action needed
Last diag. code S971 Adjustment
Reset logbook Abort
Min. meas.press. -18.8751221mbar
Max. meas.press. 256.4554138mbar
Reset peakhold Abort
Operating hours 5003
Config. counter 70

Diagnostic list
Parameter Value
Diagnostic 1 No error
Instructions 1 No action needed
Diagnostic 2 No error
Instructions 2 No action needed
Diagnostic 3 No error
Instructions 3 No action needed
Diagnostic 4 No error
Instructions 4 No action needed
Diagnostic 5 No error
Instructions 5 No action needed
Diagnostic 6 No error
Instructions 6 No action needed
Diagnostic 7 No error
Instructions 7 No action needed
Diagnostic 8 No error
Instructions 8 No action needed
Diagnostic 9 No error
Instructions 9 No action needed
Diagnostic 10 No error
Instructions 10 No action needed

Event logbook
Parameter Value
Last diag. 1 S971 Adjustment
Last diag. 2 C482 Current simul.
Last diag. 3 F882 Input signal
Last diag. 4 C482 Current simul.
Last diag. 5 No error
Last diag. 6 No error
Last diag. 7 No error
Last diag. 8 No error
Last diag. 9 No error
Last diag. 10 No error

Simulation
Parameter Value
Simulation mode None

Página 8 de 8