Control Outputs Rear Facia Settings & Electrical Connection
The following are provided:-
Tachometer/calibration output:–
• Switched +ve RUN relay and START outputs, used for 0 – 1mA into 75 meter
controlling the engine fuel and starter motor circuits.
VR1: Nominal speed calibration:–
• A –ve DC (open collector transistor), common ALARM +ve –ve With engine running at normal
output, used for remotely signalling a fault condition. speed, adjust VR1 until calibration
meter reads 0.75mA.
Fault protection and Alarm System VR2: Overspeed trip level:–
VR1
After the operator has started the engine and the fault 100 - 130% of nominal calibrated
override timer has expired, the Keystart monitors for engine VR2 speed, clockwise to increase
and plant faults through remotely connected switch sensors. VR3: Fault override timer:–
VR3 < 10 to > 30 seconds
Dedicated inputs are provided for Low Oil Pressure and clockwise to increase
High Engine Temperature switch sensors. 1 or 2 additional
inputs may be used for general purpose ‘plant fail’ contacts. Switch Settings (N.B. = up = down)
Switches at the rear allow the inputs to be configured for S1 S2 S3 S4
use with remote contacts which either open or close during Not Fault Inputs:– Supply:–
fault, with wiring polarity to either +ve or –ve DC. Used closed –ve 12 V DC
closed +ve 24 V DC
The Keystart may optionally be fitted with an engine open –ve
overspeed trip, available in alternator sensing (generator open +ve
AC, 50/60Hz) or magnetic pickup sensing variants.
If any of the above faults occur, Keystart will:- 1 – ve DC power supply 16 Input 1: Low Oil Pressure
2 Charge fail input 17 Input 2: High Engine Temp.
• turn off its RUN output (stopping the engine) 3 +ve DC power supply 18 Input 3: Plant Fail (9700 only)
• indicate the fault on the appropriate front facia LED 4 Aux. input ('A' option) 19 Input 4: Plant Fail
5 Mag. pickup input (KEY9701 only) 20 - No connection -
• activate its Alarm output (to remotely signal that a 6 Alarm output: –ve DC, < 250mA
fault has occurred). 7 - No connection - 22 Fuel output: + ve DC, 16A max.
8 - No connection - 23 Start output: + ve DC, 15A max.
The automatic fault shutdowns operate on a first-up and 9 - No connection - 24 - No connection -
latching basis - subsequent faults are not indicated and the 10 - No connection - 25 - No connection -
displayed fault can only be cleared by switching the 11 - No connection - 26 - No connection -
Keystart to STOP. 12 - No connection - 27 - No connection -
13 - No connection - 28 - No connection -
Charge Fail Warning 14 - No connection - 29 L Generator AC: 90 - 300 VAC
15 Aux./preheat output: +ve DC 30 N (KEY9702 only)
A charge failure warning LED is provided for use with an ('A' option only)
engine driven charge alternator. The charge alternator’s Note:–
WL terminal is connected to the Keystart, which will in turn Pin 5 is not used on models 9700 and 9702.
monitor the WL voltage and provide the alternator with Pin 18 is not used on overspeed models 9701 and 9702.
Pins 29 and 30 are not used on models 9700 and 9701.
excitation current at engine start up.
Installation Typical Connection Circuit
The Keystart uses a DIN standard 96 x 96 mm casing, + VE DC
designed for mounting in a control panel cut-out (92 x 92mm
DIN). Electrical connection is through a pair of ‘two-part’ Emergency
Stop RAL alarm
type terminal blocks at the rear of the unit, with 2 separate
¼” blade terminals on overspeed versions for the Generator AC
(KEY9702 only)
tachometer or calibration meter. L 29 3 6
(’A’ option only)
Also at the rear is are 4 switches for the setting of the N 30 15
supply voltage and alarm input configurations, and up to 3 Aux Remote
potentiometers: one to set the fault ‘override’ time (all units),
+ Start 15
Start
WL Stop
and 2 more to set the speed calibration and overspeed trip 2 Run Run
level, where fitted. Magnetic pickup 4
–
(KEY9701 only)
5 Start
RUN
22
16
When ordering, please specify:– RFL fuel
LOP
17 23
a) Base unit type:-
Keystart 9700: no overspeed 19
HET
b) Options:- preheat
‘A’: auxiliary control/preheat option RPH (’A’ option
only)
RPM/Calib.
N.B: stock units are supplied with switch settings for 24VDC Meter
power supply, inputs closing to –ve DC during fault.
– VE DC
Frank W. Murphy Ltd. Frank W. Murphy Ltd. en France Frank W. Murphy Southern Division Murphek Pty. Ltd.
Incorporating Modex Automation Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89 PO Box 1819, Rosenberg, Texas 77471, USA 1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Church Road, Laverstock, Salisbury U.K. Direct usine Tel: + 44 1722 410697 Tel: + 1 281 342 0297 Fax: + 1 281 341 6006 Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
Since 1939 Tel: + 44 1722 410055 Fax + 44 1722 410088 email: sales@fwmurphy.co.uk email: sales@fwmurphy.com email: murphy@macquarrie.com.au
Frank W. Murphy Manufacturer Pour service en Français, tél: + 44 1722 410697 Frank W. Murphy Pte, Ltd. Murphy Switch of California Murphy de Mexico S.A. de C.V.
PO Box 470248, Tulsa, Oklahoma 74147, USA email: sales@fwmurphy.co.uk No. 2 Tuas South Street 2, Sprintecs Building PO Box 900788, Palmdale, California 93590, USA Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146 web: http://www.fwmurphy.co.uk 02-01/02, Singapore 637895 Tel: + 1 805 272 4700 Fax: + 1 805 947 7570 San Luis Potosí, S.L.P. México 78384
email: sales@fwmurphy.com Tel: + 65 863 1398 Fax: + 65 863 0208 email: sales@murphyswitch.com Tel: + 52 48 206264 Fax: + 52 48 206336
web: http://www.fwmurphy.com email: fwmsales@fwmurphy.com.sg web: http://www.murphyswitch.com email: murmexsl@sanluis.podernet.com.mx