DKG-152

REMOTE START UNIT

DESCRIPTION
The DATAKOM model DKG-152 is a low cost, Then a new crank cycle is initiated. The engine is
microprocessor controlled unit designed to start and cranked up to 3 times.
stop the genset automatically on request of an When the Remote Start signal disappears, the
external Remote Start signal. It has high power engine will continue to run for Cooldown Duration.
relay outputs enabling it to interface directly with Then the fuel relay is deenergized.
diesel gensets.
If the ‘Activate to Stop’ option is selected, the
When the engine is running, the unit monitors fault AUXILIARY relay output will be energized for Stop
conditions and shuts-down the engine automatically Timer. At the end of the stop cycle the unit will be
in the occurrence of an alarm. The alarms are ready for a new Remote Start cycle.
identified by a group of LEDs displaying only the
The PREHEAT/STOP ( ) led will continuously
first occurring one.
indicate the AUXILIARY relay status.
The DKG-152 is also able to control ‘Energize to
The occurrence of below fault conditions will cause
Stop’ type of engines. The engine type selection is
the engine to be stopped immediately:
made by a jumper switch.
-Overspeed,
In the OFF position, the DC supply is removed from
the module, thus remote start operation is disabled -Underspeed,
and zero power consumption is achieved. -High engine temperature,
The unit powers up when the AUTO position on the -Low oil pressure,
front panel is selected. It will start the engine when If a fault condition occurs, the FUEL solenoid will be
its Remote Start input is pulled to battery negative. deenergized. If the ‘Energize to Stop’ option is
When the Remote Start signal arrives, the unit will selected, the AUXILIARY relay output will be
act like below: energized during Stop Timer and the led
If ‘Preheat’ option is selected, it energizes the associated with this condition will turn on.
AUXILIARY relay output for Preheat Delay, then Only the first occurring fault will be indicated. To
releases it. reset the fault condition, turn the switch to the OFF
Then it energizes the FUEL relay output for Wait position for a few seconds.
Before Start delay, then energizes the START The Charge Fail condition is treated as a warning
relay output for Start Duration. If the engine fires, only and do not cause the engine to stop. The input
the start relay is immediately released. The monitors the D+ terminal of the charge alternator.
protections will be enabled only after the Protection The unit is able to operate in both 50 and 60 Hz
Hold-off Timer has expired. systems. The selection is made with a jumper
If the engine does not fire, start and fuel outputs are switch.
deenergized and the unit will wait for Wait Between The unit uses high current two part connectors for
Starts period. easy replacement.
If ‘preheat’ option is selected, the AUXILIARY relay
output will be energized during this period.
TYPICAL CONNECTION DIAGRAM

INPUTS TECHNICAL SPECIFICATIONS


DC SUPPLY: 12 or 24 volts DC, (+) and (-) terminals. Alternator Voltage: 15 to 300 V-AC
L1: Generator phase voltage. Alternator Frequency: 50 or 60 Hz nominal.
NEUTRAL: Generator neutral terminal. Overspeed: nominal frequency + 14%
HIGH TEMP SWITCH: Negative closing switch input.
(+24% overshoot)
LOW OIL PRESSURE: Negative closing switch input.
REMOTE START: A negative supply connection to this Underspeed: 25Hz
input will cause the engine to run. DC Supply Range: 8 to 33 V-DC.
CHARGE: Connect the charge alternator’s D+ end to Current consumption: 80mA max. (Outputs open).
this terminal. This terminal will supply the excitation
Charge fail threshold: 6 V-DC.
current and measure the voltage of the charge alternator.
Charge excitation current: via 82 ohms resistor
connected to the FUEL output.
OUTPUTS Preheat Delay: 10 sec.
FUEL SOLENOID : 10amps@28V-DC. Wait Before Start: 0.75 sec.
START : 10amps@28V-DC. Start Duration: 6 sec.
AUXILIARY : 10amps@28V-DC. Wait Between Starts: 10 sec.
Number of Start Cycles: 3
OPTIONS Protection Hold-off Timer: 12 sec.
Cooldown Duration: 2 minutes.
JUMPER SELECTABLE STANDARD
FEATURES: Stop Timer: 30 sec.
Preheat with Activate to Start, Operating temp.: -20C (-4F) to 70 C (158F).
Energize to Stop without preheat, Storage temp.: -30C (-22F) to 80 C (176F).
50Hz nominal,
Maximum humidity: 95% non-condensing.
60Hz nominal.
Dimensions: 72x72x38mm (WxHxD)
OPTIONAL FEATURES:
Panel cutout dimensions: 68x68 mm
(SUBJECT TO SPECIAL ORDER)
Engine control (without alternator), Weight: 140g (approx.)
Manual Start version (DKG-151) Installation: Flat surface mounting on a Type 1
Negative pulling semiconductor outputs (DKG-154). enclosure. Retaining steel spring provided.
Different timer values.