You are on page 1of 28

SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.

11 15:11:32

Jindal 21MW / Folder / JINDAL GPR

MLFB: 7UM6221**B993CE0
Parameter set version: V04.63.02
Device path: C:\Siemens\Digsi4\D4PROJ\Jindal_2\P7DI\GV\SD\00000001
Author:
Creation date: 20.04.11 11:08:49
Last modified: 20.04.11 15:10:51
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 Power System Data 1 3
1.1 Group Power System Data 1; Group Power System 3
1.2 Group Power System Data 1; Group Generator/Motor 3
1.3 Group Power System Data 1; Group CT's 3
1.4 Group Power System Data 1; Group VT's 3
1.5 Group Power System Data 1; Group Breaker 3
1.6 Group Power System Data 1; Group Transducer 3
2 Settings groups 5
2.1 Group Power System Data 2; Group General 5
2.2 Group O/C I> (with undervoltage seal-in); Group O/C I> 5
2.3 Group O/C I>> (with direction); Group O/C I>> 5
2.4 Group Inverse O/C Time Protection; Group IDMT 5
2.5 Group Thermal Overload Protection; Group Therm Overload 5
2.6 Group Thermal Overload Protection; Group Temp. Input 6
2.7 Group Unbalance Load (Negative Sequence); Group Unbalance Load 6
2.8 Group Differential Protection; Group General 6
2.9 Group Differential Protection; Group I-Diff 6
2.10 Group Differential Protection; Group Characteristic 6
2.11 Group Underexcitation Protection; Group Underexcitation 7
2.12 Group Underexcitation Protection; Group Characteristics 7
2.13 Group Reverse Power Protection; Group Reverse Power 7
2.14 Group Forward Power Supervision; Group Forward Power 8
2.15 Group Impedance Protection; Group General 8
2.16 Group Impedance Protection; Group Zones 8
2.17 Group Impedance Protection; Group Power swing 8
2.18 Group Out-of-Step Protection; Group Out-of-Step 9
2.19 Group Undervoltage Protection; Group Undervoltage 9
2.20 Group Overvoltage Protection; Group Overvoltage 9

Page 1 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.21 Group Frequency Protection; Group Frequency Prot. 10


2.22 Group Overexcitation Protection (U/f); Group Overexcitation 10
2.23 Group Overexcitation Protection (U/f); Group Characteristics 10
2.24 Group Rate-of-frequency-change protection; Group df/dt Protect. 10
2.25 Group Rate-of-frequency-change protection; Group Stage 1 11
2.26 Group Rate-of-frequency-change protection; Group Stage 2 11
2.27 Group Stator Earth Fault Protection; Group Stator E Fault 11
2.28 Group Sensitive Earth Current Protection; Group Sens. E Fault 11
2.29 Group Stator Earth Fault Protection 3rdHarm.; Group SEF 3.Harm. 12
2.30 Group Breaker Failure Protection; Group Breaker Failure 12
2.31 Group Inadvertent Energisation; Group Inadvert. En. 12
2.32 Group Measurement Supervision; Group MeasSupervision 12
2.33 Group Supervision; Group General 13

Page 2 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

1 Power System Data 1


1.1 Group Power System Data 1; Group Power System
No. Settings Value Group
0242 Starpoint of Side 1 is Isolated All
0244 Starpoint of side 2 is Isolated All
0270 Rated Frequency 50 Hz All
0271 Phase Sequence L1 L2 L3 All
0272 Scheme Configuration Direct connected to busbar All
0274A Storage of th. Replicas w/o Power Supply NO All
0276 Unit of temperature measurement Degree Celsius All

1.2 Group Power System Data 1; Group Generator/Motor


No. Settings Value Group
0251 Rated Primary Voltage Generator/Motor 11.00 kV All
0252 Rated Apparent Power of the Generator 26.25 MVA All

1.3 Group Power System Data 1; Group CT's


No. Settings Value Group
0201 CT-Strpnt. Side1 in Direct. of Object NO All
0202 CT Rated Primary Current Side 1 1700 A All
0203 CT Rated Secondary Current Side 1 1A All
0204 Correction Angle CT W0 0.00 ° All
0205 CT Ratio Prim./Sec. Iee1 50.0 All
0210 CT-Strpnt. Side2 in Direct. of Object NO All
0211 CT Rated Primary Current Side 2 1700 A All
0212 CT Rated Secondary Current Side 2 1A All
0213 CT Ratio Prim./Sec. Iee2 100.0 All
0214 Grounded Terminal CT Iee2 Terminal Q7 All

1.4 Group Power System Data 1; Group VT's


No. Settings Value Group
0221 Rated Primary Voltage 11.00 kV All
0222 Rated Secondary Voltage (Ph-Ph) 110 V All
0223 UE Connection UE connected to broken delta winding All
0224 VT Ratio Prim./Sec. Ue 36.4 All
0225A Matching Ratio Ph.-VT to Broken-Delta-VT 1.73 All

1.5 Group Power System Data 1; Group Breaker


No. Settings Value Group
0280 Minimum TRIP Command Duration 0.05 sec All
0281 Closed Breaker Min. Current Threshold 0.04 A All

Page 3 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

1.6 Group Power System Data 1; Group Transducer


No. Settings Value Group
0295 Transducer 1 10 V All
0296 Transducer 2 10 V All
0297 Transducer 3 with filter All

Page 4 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2 Settings groups
2.1 Group Power System Data 2; Group General
No. Settings Value Group
1108 Measurement of Active Power for Generator A

2.2 Group O/C I> (with undervoltage seal-in); Group O/C


I>
No. Settings Value Group
1201 Overcurrent Time Protection I> ON A
1202 I> Pickup 1.01 A A
1203 T I> Time Delay 5.00 sec A
1204 State of Undervoltage Seal-in ON A
1205 Undervoltage Seal-in Pickup 77.0 V A
1206 Duration of Undervoltage Seal-in 7.00 sec A
1207A I> Drop Out Ratio 0.95 A

2.3 Group O/C I>> (with direction); Group O/C I>>


No. Settings Value Group
1301 Overcurrent Time Protection I>> ON A
1302 I>> Pickup 2.43 A A
1303 T I>> Time Delay 0.05 sec A

2.4 Group Inverse O/C Time Protection; Group IDMT


No. Settings Value Group
1401 Inverse O/C Time Protection Ip ON A
1402 Ip Pickup 0.95 A A
1403 T Ip Time Dial 0.05 sec A
1405 IEC Curve Very Inverse A
1407 Voltage Influence Voltage controlled A
1408 U< Threshold for Release Ip 77.0 V A

Page 5 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.5 Group Thermal Overload Protection; Group Therm


Overload
No. Settings Value Group
1601 Thermal Overload Protection ON A
1602 K-Factor 0.89 A
1603 Thermal Time Constant 600 sec A
1604 Thermal Alarm Stage 90 % A
1610A Current Overload Alarm Setpoint 0.89 A A
1612A Kt-Factor when Motor Stops 1.0 A
1615A Maximum Current for Thermal Replica 2.43 A A
1616A Emergency Time 100 sec A

2.6 Group Thermal Overload Protection; Group Temp.


Input
No. Settings Value Group
1605 Temperature Rise at Rated Sec. Curr. 100 °C A
1607 Temperature Input Disabled A
1608 Temperature for Scaling 100 °C A

2.7 Group Unbalance Load (Negative Sequence); Group


Unbalance Load
No. Settings Value Group
1701 Unbalance Load Protection ON A
1702 Continously Permissible Current I2 12.1 % A
1703 Warning Stage Time Delay 10.00 sec A
1704 Negativ Sequence Factor K 13.1 sec A
1705 Time for Cooling Down 889 sec A
1706 I2>> Pickup 60 % A
1707 T I2>> Time Delay 3.00 sec A

2.8 Group Differential Protection; Group General


No. Settings Value Group
2001 Differential Protection ON A
2005 Increase of Trip Char. During Start OFF A

2.9 Group Differential Protection; Group I-Diff


No. Settings Value Group
2021 Pickup Value of Differential Curr. 0.05 I/InO A
2026A T I-DIFF> Time Delay 0.00 sec A
2031 Pickup Value of High Set Trip 7.5 I/InO A
2036A T I-DIFF>> Time Delay 0.00 sec A

Page 6 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.10 Group Differential Protection; Group Characteristic


No. Settings Value Group
2041A Slope 1 of Tripping Characteristic 0.25 A
2042A Base Point for Slope 1 of Charac. 0.00 I/InO A
2043A Slope 2 of Tripping Characteristic 0.50 A
2044A Base Point for Slope 2 of Charac. 2.50 I/InO A
2051A I-RESTRAINT for Start Detection 0.10 I/InO A
2052A Factor for Increasing of Char. at Start 1.0 A
2053 Maximum Permissible Starting Time 5.0 sec A
2061A Pickup for Add-on Stabilization 4.00 I/InO A
2062A Duration of Add-on Stabilization 15 Cycle A
2063A Time for Cross-blocking Add-on Stabiliz. 15 Cycle A

2.11 Group Underexcitation Protection; Group


Underexcitation
No. Settings Value Group
3001 Underexcitation Protection ON A
3011 T-Short Time Delay (Char. & Uexc<) 0.50 sec A
3012 State of Excitation Volt. Supervision ON A
3013 Excitation Voltage Superv. Pickup 2.00 V A
3014A Undervoltage blocking Pickup 77.0 V A

2.12 Group Underexcitation Protection; Group


Characteristics
No. Settings Value Group
3002 Susceptance Intersect Characteristic 1 0.52 A
3003 Inclination Angle of Characteristic 1 80 ° A
3004 Characteristic 1 Time Delay 5.00 sec A
3005 Susceptance Intersect Characteristic 2 0.47 A
3006 Inclination Angle of Characteristic 2 90 ° A
3007 Characteristic 2 Time Delay 5.00 sec A
3008 Susceptance Intersect Characteristic 3 1.10 A
3009 Inclination Angle of Characteristic 3 90 ° A
3010 Characteristic 3 Time Delay 0.50 sec A

Page 7 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.13 Group Reverse Power Protection; Group Reverse


Power
No. Settings Value Group
3101 Reverse Power Protection ON A
3102 P> Reverse Pickup -2.43 % A
3103 Time Delay Long (without Stop Valve) 5.00 sec A
3104 Time Delay Short (with Stop Valve) 1.00 sec A
3105A Pickup Holding Time 0.00 sec A

2.14 Group Forward Power Supervision; Group Forward


Power
No. Settings Value Group
3201 Forward Power Supervision ON A
3202 P-forw.< Supervision Pickup 2.4 % A
3204 T-P-forw.< Time Delay 5.00 sec A
3203 P-forw.> Supervision Pickup 96.6 % A
3205 T-P-forw.> Time Delay oo sec A
3206A Method of Operation Method accurate A

2.15 Group Impedance Protection; Group General


No. Settings Value Group
3301 Impedance Protection ON A
3302 Fault Detection I> Pickup 0.97 A A
3303 State of Undervoltage Seal-in ON A
3304 Undervoltage Seal-in Pickup 77.0 V A
3305 Duration of Undervoltage Seal-in 4.00 sec A
3312 T END: Final Time Delay 3.00 sec A

2.16 Group Impedance Protection; Group Zones


No. Settings Value Group
3306 Impedance Zone Z1 90.07 Ohm A
3307 Impedance Zone Z1 Time Delay 1.00 sec A
3308 Impedance Zone Z1B 4.99 Ohm A
3309 Impedance Zone Z1B Time Delay oo sec A
3310 Impedanz Zone Z2 4.16 Ohm A
3311 Impedance Zone Z2 Time Delay oo sec A

Page 8 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.17 Group Impedance Protection; Group Power swing


No. Settings Value Group
3313 Power Swing Blocking OFF A
3314 Distance betw. Power Swing - Trip-Pol. 8.00 Ohm A
3315 Rate of Change of dZ/dt 300.0 Ohm/s A
3316A Power Swing Blocking locks out Zone Z1 A
3317A Power Swing Action Time 3.00 sec A

2.18 Group Out-of-Step Protection; Group Out-of-Step


No. Settings Value Group
3501 Out-of-Step Protection ON A
3502 Pickup Current for Measuring Release I1> 120.0 % A
3503 Pickup Current for Measuring Release I2< 20.0 % A
3504 Resistance Za of the Polygon (width) 8.91 Ohm A
3505 Reactance Zb of the Polygon (reverse) 22.49 Ohm A
3506 Reactance Zc of Polygon (forward char.1) 8.33 Ohm A
3507 Reactance Dif. Char.1 - Char.2 (forward) 6.40 Ohm A
3508 Angle of Inclination of the Polygon 90.0 ° A
3509 Number of Power Swing: Characteristic 1 1 A
3510 Number of Power Swing: Characteristic 2 4 A
3511 Holding Time of Fault Detection 20.00 sec A
3512 Min. Signal Time for Annun. Char. 1/2 0.05 sec A

2.19 Group Undervoltage Protection; Group


Undervoltage
No. Settings Value Group
4001 Undervoltage Protection ON A
4002 U< Pickup 99.0 V A
4003 T U< Time Delay 5.00 sec A
4004 U<< Pickup 93.5 V A
4005 T U<< Time Delay 2.50 sec A
4006A U<, U<< Drop Out Ratio 1.05 A

2.20 Group Overvoltage Protection; Group Overvoltage


No. Settings Value Group
4101 Overvoltage Protection ON A
4102 U> Pickup 121.0 V A
4103 T U> Time Delay 5.00 sec A
4104 U>> Pickup 126.5 V A
4105 T U>> Time Delay 2.50 sec A
4106A U>, U>> Drop Out Ratio 0.95 A
4107A Measurement Values Voltage protection with U-Phase-Phase A

Page 9 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.21 Group Frequency Protection; Group Frequency


Prot.
No. Settings Value Group
4201 Over / Under Frequency Protection ON A
4202 f1 Pickup 48.50 Hz A
4204 T f1 Time Delay 5.00 sec A
4205 f2 Pickup 47.40 Hz A
4207 T f2 Time Delay 2.50 sec A
4208 f3 Pickup 51.50 Hz A
4210 T f3 Time Delay 5.00 sec A
4211 f4 Pickup 52.60 Hz A
4213 T f4 Time Delay 2.50 sec A
4214 Handling of Threshold Stage f4 Freq. prot. stage automatic A
4215 Minimum Required Voltage for Operation 77.0 V A

2.22 Group Overexcitation Protection (U/f); Group


Overexcitation
No. Settings Value Group
4301 Overexcitation Protection (U/f) ON A
4302 U/f > Pickup 1.10 A
4303 T U/f > Time Delay 10.00 sec A
4304 U/f >> Pickup 1.40 A
4305 T U/f >> Time Delay 1.00 sec A

2.23 Group Overexcitation Protection (U/f); Group


Characteristics
No. Settings Value Group
4306 U/f = 1.05 Time Delay 20000 sec A
4307 U/f = 1.10 Time Delay 6000 sec A
4308 U/f = 1.15 Time Delay 4 sec A
4309 U/f = 1.20 Time Delay 4 sec A
4310 U/f = 1.25 Time Delay 3 sec A
4311 U/f = 1.30 Time Delay 2 sec A
4312 U/f = 1.35 Time Delay 2 sec A
4313 U/f = 1.40 Time Delay 1 sec A
4314 Time for Cooling Down 3600 sec A

Page 10 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.24 Group Rate-of-frequency-change protection; Group


df/dt Protect.
No. Settings Value Group
4501 Rate-of-frequency-change protection ON A
4518 Minimum Operating Voltage Umin 77.0 V A
4519A Reset Hysteresis for df1/dt & df2/dt 0.10 Hz/s A
4520A Measuring Window for df1/dt & df2/dt 5 Cycle A

2.25 Group Rate-of-frequency-change protection; Group


Stage 1
No. Settings Value Group
4502 Mode of Threshold (df1/dt >/<) -df/dt< negative rate of freq. change A
4503 Pickup Value of df1/dt Stage 1.5 Hz/s A
4504 Time Delay of df1/dt Stage 2.00 sec A
4505 AND logic with pickup of stage f1 OFF A

2.26 Group Rate-of-frequency-change protection; Group


Stage 2
No. Settings Value Group
4506 Mode of Threshold (df2/dt >/<) +df/dt> positive rate of freq. change A
4507 Pickup Value of df2/dt Stage 1.5 Hz/s A
4508 Time Delay of df2/dt Stage 2.00 sec A
4509 AND logic with pickup of stage f2 OFF A

2.27 Group Stator Earth Fault Protection; Group Stator E


Fault
No. Settings Value Group
5001 Stator Earth Fault Protection ON A
5002 U0> Pickup 6.0 V A
5005 T S/E/F Time Delay 0.50 sec A

2.28 Group Sensitive Earth Current Protection; Group


Sens. E Fault
No. Settings Value Group
5101 Sensitive Earth Current Protection ON A
5102 IEE> Pickup 100 mA A
5103 T IEE> Time delay 2.00 sec A
5104 IEE>> Pickup 400 mA A
5105 T IEE>> Time Delay 0.05 sec A
5106 IEE< Pickup (Interrupted Circuit) 0.0 mA A

Page 11 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.29 Group Stator Earth Fault Protection 3rdHarm.;


Group SEF 3.Harm.
No. Settings Value Group
5201 Stator Earth Fault Protection 3rdHarm. ON A
5203 U0 3rd Harmonic> Pickup 6.0 V A
5204 T SEF 3rd Harmonic Time Delay 0.50 sec A
5205 Release Threshold Pmin> 50 % A
5206 Release Threshold U1min> 77.0 V A
5207 Correction Factor for Pickup (V/100%) 0.0 A

2.30 Group Breaker Failure Protection; Group Breaker


Failure
No. Settings Value Group
7001 Breaker Failure Protection ON A
7002 Start with Internal TRIP Command Start Breaker Failure with CFC A
7003 Supervision Current Pickup 0.20 A A
7004 TRIP-Timer 0.25 sec A

2.31 Group Inadvertent Energisation; Group Inadvert.


En.
No. Settings Value Group
7101 Inadvertent Energisation ON A
7102 I Stage Pickup 0.9 A A
7103 Release Threshold U1< 77.0 V A
7104 Pickup Time Delay T U1< 5.00 sec A
7105 Drop Out Time Delay T U1< 1.00 sec A

Page 12 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32

2.32 Group Measurement Supervision; Group


MeasSupervision
No. Settings Value Group
8101 Measurement Supervision ON A
8102 Voltage Threshold for Balance Monitoring 50 V A
8103 Balance Factor for Voltage Monitor 0.75 A
8104 Current Balance Monitor Side 1 0.50 A A
8105 Balance Factor for Current Monitor S1 0.50 A
8106 Current Balance Monitor Side 2 0.50 A A
8107 Balance Factor for Current Monitor S2 0.50 A
8108 Summation Thres. for Volt. Monitoring 10 V A
8109 Factor for Volt. Sum. Monitoring 0.75 A
8110 Summated Cur. Mon. Threshold on Side 1 0.10 A A
8111 Summated Current Mon. Factor on Side 1 0.10 A
8112 Summated Cur. Mon. Threshold on Side 2 0.10 A A
8113 Summated Current Mon. Factor on Side 2 0.10 A

2.33 Group Supervision; Group General


No. Settings Value Group
8001 Fuse Failure Monitor ON A

Page 13 of 13
Document No. Rev.No.

SIEMENS LTD. Information#64R 0


Responsible Department: Take over Department: Document Type: Folder No.
E O IP PE -
Prepared: Checked: Released: Language Page:
VT\25.10.2010 PJD\25.10.2010 BD\25.10.2010 en
1 of 2
Valid for: Derived from: Replaces: E File no.:

E O IP PE - - GENERAL INFORMATIONS
\STANDARDS RELAY SETTING
\XRI-1

TYPE OF DOCUMENT: Standard Relay Settings for


Rotor Earth-fault Relay, XR1
Make: Woodward-SEG / CSPC.

Rev.No. Date Description Prepared: Checked: Approved:

______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.

Format No.: IP-Q-F-2002


Rev./Date : B / 30.03.2010
Page: Document No. Rev.No.

2 of 2 Information#64R 0

Relay Settings for XR1- Rotor Earth Fault relay


Sr. Setting Setting
Function Description Unit Remarks
No. Range Value
Coarse Adjustment Pointer
shall be at 80
1 R< Rotor E/F Alarm kΩ 20-140 80
Fine Adjustment Pointer shall
be at 0
Coarse Adjustment Pointer
shall be at 20
2 R<< Rotor E/F Tripping kΩ 0 - 30 20
Fine Adjustment Pointer shall
be at 0
Select 0 - 25 Sec Range
3 tR< Time delay for R< Sec 0-25 /0-50 5 ( Dip Switch shall be put on
multiplier 1)
Select 0 - 10 Sec Range
4 tR<< Time delay for R<< Sec 0-10/0-20 2 ( Dip Switch shall be put on
multiplier 1)

Dip Switch
Position ON/OFF
Selection
1 ON
2 ON
3 ON
4 OFF (Active)
5 OFF (Active)
6 ON
7 OFF(x1)
8 OFF(x1)

Note: After connection & power supply, pl test the relay with Test Push button & hold for 5 secs. Check the operation
of o/p contact.

______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010
Document No. Rev.No.

SIEMENS LTD. Information#25A 0


Responsible Department: Take over Department: Document Type: Folder No.
E O IP PE -
Prepared: Checked: Released: Language Page:
VT\25.10.2010 PJD\25.10.2010 BD\25.10.2010 en
1 of 3
Valid for: Derived from: Replaces: E File no.:

E O IP PE - - GENERAL INFORMATIONS
\STANDARDS RELAY SETTING
\PSY5

TYPE OF DOCUMENT: Standard Relay Settings for


Auto Synchronizing Relay, SPM-D10B / PSY5
Make: Woodward-SEG.

Rev.No. Date Description Prepared: Checked: Approved:

______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.

Format No.: IP-Q-F-2002


Rev./Date : B / 30.03.2010
Page: Document No. Rev.No.

2 of 3 Information#25A 0
Parameter list

PSY-5 Synchronizing system


Product number P/N ________________ Rev _________________________________
Version PSY5_____________________________________________________
Project _ _____________________________________________________
Serial number

Option Parameter Adjustment Range Standard Customer settings


100/400V;1/5A setting

CONFIGURE GENERAL PARAMETER


SPRACHE/LANGUAGE German/English English □G□E English
Software version 1.1XX 1.150
Enter code Number 0..9.999 XXXX 0002
Password Protection ON/OFF OFF □ on □ off OFF
Direct Para. YES/NO NO □Y□N NO
CONFIGURE BASIC SETTINGS
Rated Frequency fn 48.0..62.0 Hz 50.0Hz 50
Generator Freq. Setpoint 48.0..62.0 Hz 50.0Hz 50
VoltageSystem1 Secondary 50.440V 400V 110
VoltageSystem2 Secondary 50.440V 400V 110
VoltageSystem1 Primary 0.1..65.0kv 0.4kv 11000
VoltageSystem2 Primary 0.1..65.0kv 0.4kv 11000
Rated Voltage Vn 70..420V 400V 110
Voltage System System 50..440V 400V 110
CONFIGURE CONTROLLER
Automatic idle Running ON/OFF OFF □ on □ off ON
f control type THREEP/ANA./PWM ANALOG THREEP
Freq. controller ON/OFF ON □ on □ off ON
Freq. controller Isol. oper ON/OFF OFF □ on □ off OFF
Freq. Controller Ramp 0.1..99.9Hz/s 5.0Hz/s 5.0 Hz/s
Freq. contr.(A) Dead Band 0.02..1.00Hz 0.10Hz 0.10 Hz
Freq. contr.(A) Time Pulse> 10..250ms 80ms 80ms
Freq. contr.(A) Gain Kp 0.1..99.9 5.0 5
Freq. contr.(B) Dead Band 0.02..1.00Hz 0.10Hz 0.10 Hz
Freq. contr.(B) Time Pulse> 10..250ms 80ms 80ms
Freq. contr.(B) Gain Kp 0.1..99.9 30.0 5.0
f control output see table +20 mA
(+10V)
f control output Level PWM 3.0..10.0V 10.0V
PWM-signal Logic Positive Positive/negative Positive
f control output Init. state 0..100% 50%
f control output (max) 0..100% 100%
f control output (min) 0..100% 0%
Freq. contr.(A) Gain Kp. 1..240 15
Freq. contr.(A) Reset Tn 0.0..60.0s 2.5s
Freq. contr.(A) Derivate.Tv 0.00..6.00s 0.00s
Freq. contr.(B) Gain Kp. 1..240 15
Freq. contr.(B) Reset Tn 0.0..60.0s 2.5s
Freq. contr.(B) Derivate.Tv 0.00..6.00s 0.00s

______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010
Page: Document No. Rev.No.

3 of 3 Information#25A 0

Option Parameter Adjustment Range Standard Customer settings


100/400V;1/5A setting

V control. Type THREESTEP/AN ANALOG □ on □ off THREESTEP


ALOG
Volt. Controller ON/OFF ON □ on □ off ON
Volt. Controller Isol.oper ON/OFF OFF OFF
Volt. Controller Ramp 1..99V/s 25V/s 25 V/s
Volt. Contr.(A) Dead band 0.1..25.0% 0.5% 0.5%
Volt. Contr.(A) Time Pulse> 20..250ms 80ms 80ms
Volt. Contr.(A) Gain Kp 0.1..99.9 5.0 5
Volt. Contr.(B) Dead band 0.1..25.0% 0.5% 0.5
Volt. Contr.(B) Time Pulse> 20..250ms 80ms 80ms
Volt. Contr.(B) Gain Kp 0.1..99.9 30.0 30
V control output See table +20mA
(+10V)
V control output Init.stable. 0..100% 50%
V control output (max) 0..100% 100%
V control output (min) 0..100% 0%
Volt. Contr.(A) Gain Kp 1..240 15
Volt. Contr.(A) Reset Tn 0.0..60.0s 2.5s
Volt. Contr.(A) Derivat Tv 0.00..6.00s 0.00s
Volt. Contr.(B) Gain Kp 1..240 15
Volt. Contr.(B) Reset Tn 0.0..60.0s 2.5s
Volt. Contr.(B) Derivat Tv 0.00..6.00s 0.00s
CONFIGURE SYNCHRONIZATION
Synchronizing functions ON/OFF ON □ on □ off ON
Synchrocheck- mode ON/OFF OFF OFF
Synchronization df offs= 0.00..0.25Hz 0.10Hz 0.07
Synchronization df max 0.02..0.49Hz 0.18Hz 0.15
Synchronization df min 0.00..0.49Hz 0.10Hz -0.10
Synchronization dV max 0.1..15.0% 6% 10%
Synchronization Bkr.holdT> 0.04..0.50s 0.20s 100 ms
Phase matching ON/OFF OFF □ on □ off ON
Slip synchroniz Max.phase< 0.600 70 70
Slip synch.(A) TCloseCB 40..300ms 80ms 80ms
Slip synch.(B) TCloseCB 40..300ms 80ms 80ms
Phase matching Max phase< 0..600 70 70
Phase matching Dwell time 0.2..10.0s 10.0s 0.5S
Phase matching Gain 1..36 2 2
Phase matching df start 0.02..0.25Hz 0.20Hz 0.20HZ
CONFIGURE SYNCH-TIME MONITORING
Synch.time contr. Alarm ON/OFF OFF □ on □ off OFF
Synch.Zeituberw Delay time 10..999s 120s 300 sec
CONFIGURE BLACK START
Black start ON/OFF OFF □ on □ off ON
Black start U1=0/U2=0 ON/OFF OFF □ on □ off OFF
Black start U1=0/U2=Un ON/OFF OFF □ on □ off ON
Black start U1=Un/U2=0 ON/OFF OFF □ on □ off ON
Black start Tmin> 0..20s 5s 5s
Black start dV/V-0/< 3..50% 10% 10 %
Black start dV/V-Vn/< 1..20% 5% 5%
Black start df max= 0.05..5.00Hz 0.25Hz .25 Hz
Rel.connect 2 OFF/only asyn./only OFF OFF
syn./syn./asyn.
CONFIGURE PASSWORD
Define level 1 code 0000..9999 0001 0001
Define level 2 code 0000..9999 0002 0002

______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010
active SignalName Description IC Min Max Group IdInGrp
SystemMeasurement
a UGenNom Nominal generator voltage [kV]; 11 0.000 65.535 11 1
a UmachTprim Nominal transducer primary side generator voltage [kV]; 11 0.000 65.535 11 2
a UmachTsec Nominal transducer secondary side generator voltage [V]; 110 0.00 150.00 11 3
a IGenNom Nominal generator current [kA or A]; 1.377 0.000 65.535 11 7
a ImachIs5A Select current transducer type; 0 0 1 11 8
a ImachTprim Generator current transducer primary current [kA]; 1.7 0.000 65.535 11 9
a ImachTsec Generator current transducer secondary current [A]; 1 0.000 65.535 11 10

SysMeasConfig
a UMach1phase Umach single phase Measurement; 0 0 1 11 27
a UMachMeasCon Umach measurement configuration; 1 1 3 11 28
a IMachNumOfPhases Imach number of phases for measurement; 1 1 3 11 29
a IMachMeasCon Imach measurement configuration; 1 1 3 11 30

Protection
a EnaOverCurrMon Release Excitation Overcurrent Monitoring DC 1 0 1 16 4
a EnaOvrVoltageMon Release Excitation Overvoltage Monitoring 1 0 1 16 5
a EnablePQMon Release PQ Monitoring (Loss of Excitation) 1 0 1 16 6
a EnableVHzMon Release V/Hz Monitoring 1 0 1 16 7
a EnaMachMeasCTMon Release Machine CT Monitoring 1 0 1 16 8
a EnaMachMeasPTMon Release Machine PT Monitoring 1 0 1 16 9
a EnableUsynMon Release Synchronous Voltage PT Monitoring 1 0 1 16 10
a EnableIConvMon Release Converter Current CT Monitoring 1 0 1 16 11
a EnableUfMon Release Field Voltage PT Monitoring 1 0 1 16 12
a EnableExtSCMon Release External Short-Circuit Monitoring 1 0 1 16 13
a EnableRippleMon Release Ripple Monitoring 1 0 1 16 14
a EnaAuxSupervis Release Auxiliary Monitoring 1 0 1 16 15
a EnaPowSupplyMon Release Power Supply Monitoring 1 0 1 16 16
a PTEnaInPhaseMon Release Machine PT In-Phase Monitor 1 0 1 16 17
a PTEnaOpAmpCeilM Release Machine PT Opamp Ceiling Monitor 1 0 1 16 18
a PTEnaADCFreezeM Release Machine PT ADC Freeze Monitor 1 0 1 16 19
a PTEnaAllLostMon Release Machine PT All Lost Monitor 1 0 1 16 20
a CTEnaSumMon Release Machine CT Sum Monitor 1 0 1 16 21
a CTEnaOpAmpCeilM Release Machine CT Opamp Ceiling Monitor 1 0 1 16 22
a CTEnaADCFreezeM Release Machine CT ADC Freeze Monitor 1 0 1 16 23
a CTEnaParaPhaseM Release Machine CT Paraphase Monitor 0 0 1 16 24
a IconvEnaADCFreM Release Converter Current CT ADC Freeze Monitor 1 0 1 16 25
a IconvEnaOpACeilM Release Converter Current CT Opamp Ceiling Monitor 0 0 1 16 26
a UfEnaADCFreezeM Release Field Voltage PT ADC Freeze Monitor 1 0 1 16 27
a UfEnaOpAmpCeilM Release Field Voltage PT Opamp Ceiling Monitor 1 0 1 16 28
a UsynEnaOpACeilM Release Synchronous Voltage Opamp Ceiling Monitor 1 0 1 16 29
a UsynEnaADCFM Release Synchronous Voltage ADC Freeze Monitor 1 0 1 16 30
a UsynEnaAllLostM Release Synchronous Voltage All Lost Monitor 1 0 1 16 67
a EnaConvTempMon Release Converter Temperature Monitoring 1 0 1 16 31
a EnableDiodeMon Release Rotor Diode Monitoring 1 0 1 16 32
a EnableStallMon Release Stall Monitoring 0 0 1 16 33
a EnTrIndSupOnExTr Trip Indication Suppression for ext. Trip 1 0 1 16 34
a EnaAutResOnExtTr Automatic Reset after ext. Trip 1 0 1 16 35
a EnaIfExcOnMon Enable signal for field current monitoring while ExcOn sequence 0 0 1 16 63
a EnaUgExcOnMon Enable signal for generator votage monitoring while ExcOn sequence 0 0 1 16 64
a EnaFireAllTrpDet Enable signal for the FireAllTrip detection 1 0 1 16 66
a EnaPhaseSeqCheck Enable signal for the synchronous voltage phase sequence check while the ExcOn Sequence 1 0 1 16 80

PQMon
a Charact_QP10 P/Q Protection Q-Setpoint at P=1pu -0.036 -2.000 0.000 18 34
a Charact_QP08 P/Q Protection Q-Setpoint at P=0.8pu -0.324 -2.000 0.000 18 35
a Charact_QP06 P/Q Protection Q-Setpoint at P=0.6pu -0.342 -2.000 0.000 18 36
a Charact_QP04 P/Q Protection Q-Setpoint at P=0.4pu -0.378 -2.000 0.000 18 37
a Charact_QP02 P/Q Protection Q-Setpoint at P=0.2pu -0.405 -2.000 0.000 18 38
a Charact_QP00 P/Q Protection Q-Setpoint at P=0.0pu -0.45 -2.000 0.000 18 39
a DelayTime P/Q Protection delay 2 0.000 10.000 18 40

PowerSupplyMon
a EnaRedunSupply Select Redundant Power Supply Configuration 0 0 1 19 16
PSU1ICU1
a Enable Enables the ICU source fault detection; 1 0 1 19 17
a SourcesConfWord Bitset: Bit1=Source1 connected; Bit2=Source2 connected;3=Source3 connected; 7 0 7 19 18

Converter
a IfNom Nominal Field Current [A] 14.1 0.0 6553.5 21 1
a UfNom Nominal Field Voltage [V] 147 0.0 6553.5 21 2
a UsynNom Nominal Synchronous voltage [V] 200 0.0 6553.5 21 3
a ITransducNomConf Converter Current Transducer Configuration Word; 3 0 8 21 4
a UVoltDiviNomConf Converter Voltage Configuration Word; 1 0 3 21 5
a ConvertTypeConf Converter Type Configuration Word. [1..5] = [D1..D5] 1 0 5 21 6
a IfAGL Air gap line current [A]; 3.8 0.0 6553.5 21 12
a UsynFreqNom Nominal synchronous voltage frequency 50 0.0 480.0 21 39

StateMachine
a ExcSysSupplyMode Excitation system main supply mode; 0 0 1 22 2
a FieldFlashTout Field flash timeout time; 5 0.00 60.00 22 4
a ExcOnTimeout Excitation On timeout time; 40 0.00 655.35 22 5
a InvModeTime Invert mode time; 40 0.00 655.35 22 6

ExcitationSystem
a DirectExc Direct Excitation; 0 0 1 23 2
a NomMachineFreq Nominal Machine Frequency 50 10.00 120.00 23 3
a Xd Direct axis synchronous reactance 1.866 0.000 5.000 23 4
a Xq Machine quadrature Reactance 1.807 0.000 5.000 23 5
a CosPhiNom Nominal cos-phi; 1 0.0000 1.0000 23 6
a Xe Infinite grid Reactance 0.1 0.000 0.500 23 7
a Td0s Direct axis no-load transient time constant Td0' 3.214 0.000 65.535 23 8
a Tds Direct axis short circuit transient time constant Td' 0.561 0.000 65.535 23 9
a ChanConfigWord Channel configuration word. 0=not defined, 1=Ch1, 2=Ch1 & Ch2, 3=Ch1 & Ch2 and BFCR; 2 0 3 23 16
a ChannelDefWord Channel definition word. 0=not defined, 1=Ch1, 2=Ch2, 3=BFCR; 1 OR 2 0 3 23 17

PQ_Lim
a Charact_QP10 P/Q limiter. Q-Setpoint for P=1.0pu -0.032 -1.5000 0.0000 6 1
a Charact_QP08 P/Q limiter. Q-Setpoint for P=0.8pu -0.2879 -1.5000 0.0000 6 2
a Charact_QP06 P/Q limiter. Q-Setpoint for P=0.6pu -0.304 -1.5000 0.0000 6 3
a Charact_QP04 P/Q limiter. Q-Setpoint for P=0.4pu -0.336 -1.5000 0.0000 6 4
a Charact_QP02 P/Q limiter. Q-Setpoint for P=0.2pu -0.36 -1.5000 0.0000 6 5
a Charact_QP00 P/Q limiter. Q-Setpoint for P=0.0pu -0.4 -1.5000 0.0000 6 6
a Release_PQLim Enable P/Q limiter 1 0 1 6 7
AVR_SetPt_VHz
a LimiterGradient V/Hz Limiter. Gradient (Ug/f) 1.15 0.00 10.00 7 22
a LimiterVfn V/Hz Limiter. Voltage at nominal frequency 1.15 0.000 10.000 7 23
a ThermalDownTime V/Hz Limiter. inverse-time back-integration time 1000 0.0 6553.5 7 24
a Limiter_Release V/Hz Limiter. Release 1 0 1 7 25
a LimiterDelayTime V/Hz Limiter. inverse-time fixed delay (for inverse-time function 0) 0 0.0 100.0 7 26
a LimDelayFuncSel V/Hz Limiter. inverse-time select curve (0: fix delay, 1: normal inverse, 2: very inverse, 3: exremley
0 inverse)
0 3 7 27
a LimDelayFactor V/Hz Limiter. inverse-time k factor 0 0.0000 6.5535 7 28

AVR_PID
a ta PID Lag time constant 1 0.00 20.00 2 7
a tb PID Lead time constant 0.1 0.00 10.00 2 8
a vp PID proportional gain 40 0.1 250.0 2 9
a vo PID low frequency gain 200 0.1 1000.0 2 10
a voo PID high frequency gain 40 0.1 1000.0 2 11
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 2 12
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 2 13

Ind_PID
a ta PID Lag time constant 1 0.00 20.00 3 13
a tb PID Lead time constant 0.1 0.00 10.00 3 14
a vp PID proportional gain 40 0.1 250.0 3 15
a vo PID low frequency gain 200 0.1 1000.0 3 16
a voo PID high frequency gain 40 0.1 1000.0 3 17
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 3 18
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 3 19

Cap_PID
a ta PID Lag time constant 1 0.00 20.00 3 20
a tb PID Lead time constant 0.1 0.00 10.00 3 21
a vp PID proportional gain 40 0.1 250.0 3 22
a vo PID low frequency gain 200 0.1 1000.0 3 23
a voo PID high frequency gain 40 0.1 1000.0 3 24
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 3 25
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 3 26

Field_Cur_Max_Lim_PID
a ta PID Lag time constant 1 0.00 20.00 4 13
a tb PID Lead time constant 0.1 0.00 10.00 4 14
a vp PID proportional gain 40 0.1 250.0 4 15
a vo PID low frequency gain 200 0.1 1000.0 4 16
a voo PID high frequency gain 40 0.1 1000.0 4 17
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 4 18
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 4 19
Field_Cur_Min_Lim
a MinFieldCurrent Minimum field current limiter. Minimum field current (setpoint) 0 0.000 65.535 5 1
a Release_IfMinLim Enable minimum field current limiter 0 0 1 5 2

Field_Cur_Max_Lim
a MaxFieldCurrent Maximum field current limiter. Maximum field current. 1.6 0.000 5.000 4 1
a MaxTherFieldCur Maximum field current limiter. Maximum thermal field current. (inverse-time function starts if 1.05
the field
0.000
current2.000
exceeds4this value)
2
a PulseFun_En Maximum field current limiter. Enable dudt function 1 0 1 4 3
a ThermalDownTime Maximum field current limiter. Inverse-time back-integration time 1000 0.0 6553.5 4 4
a FixUpTime Maximum field current limiter. Inverse-time fixed delay (for inverse-time function 0) 0 0.0 100.0 4 5
a NoLimitDelay Maximum field current limiter. Time without limitation 0.01 0.000 1.000 4 6
a DelayFuncSelect Maximum field current limiter. Inverse-time select curve (0: fix delay, 1: normal inverse, 2: very inverse,
3 3:0 extremley
3 inverse)
4 7
a DelayFactor Maximum field current limiter. Inverse-time k factor 1 0.0000 6.5535 4 8
a TdynHys Maximum field current limiter. Time after limiter engagement with doubled hysteresis. (Helps to1prevent 0.00limiter
10.00
pump) 4 9
a Hysteresis Maximum field current limiter. Hysteresis to prevent limiter pump 0.05 0.000 0.200 4 10
a Release_IfMaxLim Maximum field current limiter. Enable max. field current limiter 1 0 1 4 11
a ThermCoolingFact Maximum field current limiter. Factor for thermal Limit until "Cooling" completed -> Italy Specification
1 0.5000 1.0000 4 12

AVR_SetPt
a MaxRefValue AVR Setpoint. Maximal value 1.1 0.000 1.500 7 3
a MinRefValue1 AVR Setpoint. Minimal value 1 0.9 0.000 1.500 7 6
Command
a ForceAuto Force the generator voltage regulator to be active; 0 0 1 99 5
a ForceManual Force the field current regulator to be active; 0 0 1 99 6
SystemMeasurement
a UGenNom Nominal generator voltage [kV]; 11 0.000 65.535 11 1
a UmachTprim Nominal transducer primary side generator voltage [kV]; 11 0.000 65.535 11 2
a UmachTsec Nominal transducer secondary side generator voltage [V]; 110 0.00 150.00 11 3
a IGenNom Nominal generator current [kA or A]; 1.377 0.000 65.535 11 7
a ImachIs5A Select current transducer type; 0 0 1 11 8
a ImachTprim Generator current transducer primary current [kA]; 1.7 0.000 65.535 11 9
a ImachTsec Generator current transducer secondary current [A]; 1 0.000 65.535 11 10

Converter
a IfNom Nominal Field Current [A] 14.1 0.0 6553.5 21 1
a UfNom Nominal Field Voltage [V] 147 0.0 6553.5 21 2
a UsynNom Nominal Synchronous voltage [V] 200 0.0 6553.5 21 3
a ITransducNomConf Converter Current Transducer Configuration Word; 3 0 8 21 4
a UVoltDiviNomConf Converter Voltage Configuration Word; 1 0 3 21 5
a ConvertTypeConf Converter Type Configuration Word. [1..5] = [D1..D5] 1 0 5 21 6
a IfAGL Air gap line current [A]; 3.8 0.0 6553.5 21 12
a UsynFreqNom Nominal synchronous voltage frequency 50 0.0 480.0 21 39

ExcitationSystem
a ChannelDefWord Channel definition word. 0=not defined, 1=Ch1, 2=Ch2, 3=BFCR; 1 OR 2 0 3 23 17
Document No. Rev.No.

SIEMENS LTD. Information#32Q 0


Responsible Department: Take over Department: Document Type: Folder No.
E O IP PE -
Prepared: Checked: Released: Language Page:
MKR\22.04.2011 PJD\22.04.2011 BD\22.04.2011 en
1 of 2
Valid for: Derived from: Replaces: E File no.:

E O IP PE - - GENERAL INFORMATIONS
\STANDARDS RELAY SETTING
\MRQ1

TYPE OF DOCUMENT: Standard Relay Settings for


Reverse Reactive Power Relay or
Field Failure Relay, MRQ1
Make: CSPC

Rev.No. Date Description Prepared: Checked: Approved:


______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.

Format No.: IP-Q-F-2002


Rev./Date : B / 30.03.2010
Page: Document No. Rev.No.

2 of 2 Information#59TN 0
Project: JINDAL TOWMCL 1X21MW

Relay Settings for MRQ1


Generator
Values Unit Description
Parameter
RATING (MW) 21 MW
Voltage 11000 Volt
FLC 1379.40 Amp
CT PR 1700 Amp
CT SEC 1 Amp
According to PT secondary which is being connected to
Un MRQ 110 Volt
MRQ1 Relay
According to CT secondary which is being connected to
In MRQ 1
Amp MRQ1 Relay
XD' (Saturated) 0.287 PU Value from Generator Data Sheet
XD (Saturated) 1.642 PU Value from Generator Data Sheet
PT PR 11000 Volt
PT SEC 110 Volt
MVA Rating 26.25 MVA
COS PHI 0.8

Protection Parameters:
Element Parameter Setting Range Setting Value
2 - 110V
U< 93
(EXIT - blocks the function)
U<
0.04 - 50 sec
t U< 2.5
(EXIT: t = ∞)
Z1A -300 - - - 300% of Zn 18
0 - - - 600% of Zn
Z1 Z1B (Z1B = 0 blocks the 202
function)
0.04 - 50 sec
t Z1 1
(EXIT: t = ∞)
Z2A -300 - - - 300% of Zn 18
0 - - - 600% of Zn
Z2 Z2B (Z2B = 0 blocks the 101
function)
0.04 - 50 sec
t Z2 0.25
(EXIT: t = ∞)

______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010

You might also like