MLFB: 7UM6221**B993CE0
Parameter set version: V04.63.02
Device path: C:\Siemens\Digsi4\D4PROJ\Jindal_2\P7DI\GV\SD\00000001
Author:
Creation date: 20.04.11 11:08:49
Last modified: 20.04.11 15:10:51
Operating mode: Offline
Comment:
Setting values in: Secondary value description
PRINT - CONTENTS
1 Power System Data 1 3
1.1 Group Power System Data 1; Group Power System 3
1.2 Group Power System Data 1; Group Generator/Motor 3
1.3 Group Power System Data 1; Group CT's 3
1.4 Group Power System Data 1; Group VT's 3
1.5 Group Power System Data 1; Group Breaker 3
1.6 Group Power System Data 1; Group Transducer 3
2 Settings groups 5
2.1 Group Power System Data 2; Group General 5
2.2 Group O/C I> (with undervoltage seal-in); Group O/C I> 5
2.3 Group O/C I>> (with direction); Group O/C I>> 5
2.4 Group Inverse O/C Time Protection; Group IDMT 5
2.5 Group Thermal Overload Protection; Group Therm Overload 5
2.6 Group Thermal Overload Protection; Group Temp. Input 6
2.7 Group Unbalance Load (Negative Sequence); Group Unbalance Load 6
2.8 Group Differential Protection; Group General 6
2.9 Group Differential Protection; Group I-Diff 6
2.10 Group Differential Protection; Group Characteristic 6
2.11 Group Underexcitation Protection; Group Underexcitation 7
2.12 Group Underexcitation Protection; Group Characteristics 7
2.13 Group Reverse Power Protection; Group Reverse Power 7
2.14 Group Forward Power Supervision; Group Forward Power 8
2.15 Group Impedance Protection; Group General 8
2.16 Group Impedance Protection; Group Zones 8
2.17 Group Impedance Protection; Group Power swing 8
2.18 Group Out-of-Step Protection; Group Out-of-Step 9
2.19 Group Undervoltage Protection; Group Undervoltage 9
2.20 Group Overvoltage Protection; Group Overvoltage 9
Page 1 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 2 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 3 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 4 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
2 Settings groups
2.1 Group Power System Data 2; Group General
No. Settings Value Group
1108 Measurement of Active Power for Generator A
Page 5 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 6 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 7 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 8 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 9 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 10 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 11 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 12 of 13
SIMATIC Jindal 21MW / Folder / JINDAL GPR/7UM622 20.04.11 15:11:32
Page 13 of 13
Document No. Rev.No.
E O IP PE - - GENERAL INFORMATIONS
\STANDARDS RELAY SETTING
\XRI-1
______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.
2 of 2 Information#64R 0
Dip Switch
Position ON/OFF
Selection
1 ON
2 ON
3 ON
4 OFF (Active)
5 OFF (Active)
6 ON
7 OFF(x1)
8 OFF(x1)
Note: After connection & power supply, pl test the relay with Test Push button & hold for 5 secs. Check the operation
of o/p contact.
______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010
Document No. Rev.No.
E O IP PE - - GENERAL INFORMATIONS
\STANDARDS RELAY SETTING
\PSY5
______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.
2 of 3 Information#25A 0
Parameter list
______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010
Page: Document No. Rev.No.
3 of 3 Information#25A 0
______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010
active SignalName Description IC Min Max Group IdInGrp
SystemMeasurement
a UGenNom Nominal generator voltage [kV]; 11 0.000 65.535 11 1
a UmachTprim Nominal transducer primary side generator voltage [kV]; 11 0.000 65.535 11 2
a UmachTsec Nominal transducer secondary side generator voltage [V]; 110 0.00 150.00 11 3
a IGenNom Nominal generator current [kA or A]; 1.377 0.000 65.535 11 7
a ImachIs5A Select current transducer type; 0 0 1 11 8
a ImachTprim Generator current transducer primary current [kA]; 1.7 0.000 65.535 11 9
a ImachTsec Generator current transducer secondary current [A]; 1 0.000 65.535 11 10
SysMeasConfig
a UMach1phase Umach single phase Measurement; 0 0 1 11 27
a UMachMeasCon Umach measurement configuration; 1 1 3 11 28
a IMachNumOfPhases Imach number of phases for measurement; 1 1 3 11 29
a IMachMeasCon Imach measurement configuration; 1 1 3 11 30
Protection
a EnaOverCurrMon Release Excitation Overcurrent Monitoring DC 1 0 1 16 4
a EnaOvrVoltageMon Release Excitation Overvoltage Monitoring 1 0 1 16 5
a EnablePQMon Release PQ Monitoring (Loss of Excitation) 1 0 1 16 6
a EnableVHzMon Release V/Hz Monitoring 1 0 1 16 7
a EnaMachMeasCTMon Release Machine CT Monitoring 1 0 1 16 8
a EnaMachMeasPTMon Release Machine PT Monitoring 1 0 1 16 9
a EnableUsynMon Release Synchronous Voltage PT Monitoring 1 0 1 16 10
a EnableIConvMon Release Converter Current CT Monitoring 1 0 1 16 11
a EnableUfMon Release Field Voltage PT Monitoring 1 0 1 16 12
a EnableExtSCMon Release External Short-Circuit Monitoring 1 0 1 16 13
a EnableRippleMon Release Ripple Monitoring 1 0 1 16 14
a EnaAuxSupervis Release Auxiliary Monitoring 1 0 1 16 15
a EnaPowSupplyMon Release Power Supply Monitoring 1 0 1 16 16
a PTEnaInPhaseMon Release Machine PT In-Phase Monitor 1 0 1 16 17
a PTEnaOpAmpCeilM Release Machine PT Opamp Ceiling Monitor 1 0 1 16 18
a PTEnaADCFreezeM Release Machine PT ADC Freeze Monitor 1 0 1 16 19
a PTEnaAllLostMon Release Machine PT All Lost Monitor 1 0 1 16 20
a CTEnaSumMon Release Machine CT Sum Monitor 1 0 1 16 21
a CTEnaOpAmpCeilM Release Machine CT Opamp Ceiling Monitor 1 0 1 16 22
a CTEnaADCFreezeM Release Machine CT ADC Freeze Monitor 1 0 1 16 23
a CTEnaParaPhaseM Release Machine CT Paraphase Monitor 0 0 1 16 24
a IconvEnaADCFreM Release Converter Current CT ADC Freeze Monitor 1 0 1 16 25
a IconvEnaOpACeilM Release Converter Current CT Opamp Ceiling Monitor 0 0 1 16 26
a UfEnaADCFreezeM Release Field Voltage PT ADC Freeze Monitor 1 0 1 16 27
a UfEnaOpAmpCeilM Release Field Voltage PT Opamp Ceiling Monitor 1 0 1 16 28
a UsynEnaOpACeilM Release Synchronous Voltage Opamp Ceiling Monitor 1 0 1 16 29
a UsynEnaADCFM Release Synchronous Voltage ADC Freeze Monitor 1 0 1 16 30
a UsynEnaAllLostM Release Synchronous Voltage All Lost Monitor 1 0 1 16 67
a EnaConvTempMon Release Converter Temperature Monitoring 1 0 1 16 31
a EnableDiodeMon Release Rotor Diode Monitoring 1 0 1 16 32
a EnableStallMon Release Stall Monitoring 0 0 1 16 33
a EnTrIndSupOnExTr Trip Indication Suppression for ext. Trip 1 0 1 16 34
a EnaAutResOnExtTr Automatic Reset after ext. Trip 1 0 1 16 35
a EnaIfExcOnMon Enable signal for field current monitoring while ExcOn sequence 0 0 1 16 63
a EnaUgExcOnMon Enable signal for generator votage monitoring while ExcOn sequence 0 0 1 16 64
a EnaFireAllTrpDet Enable signal for the FireAllTrip detection 1 0 1 16 66
a EnaPhaseSeqCheck Enable signal for the synchronous voltage phase sequence check while the ExcOn Sequence 1 0 1 16 80
PQMon
a Charact_QP10 P/Q Protection Q-Setpoint at P=1pu -0.036 -2.000 0.000 18 34
a Charact_QP08 P/Q Protection Q-Setpoint at P=0.8pu -0.324 -2.000 0.000 18 35
a Charact_QP06 P/Q Protection Q-Setpoint at P=0.6pu -0.342 -2.000 0.000 18 36
a Charact_QP04 P/Q Protection Q-Setpoint at P=0.4pu -0.378 -2.000 0.000 18 37
a Charact_QP02 P/Q Protection Q-Setpoint at P=0.2pu -0.405 -2.000 0.000 18 38
a Charact_QP00 P/Q Protection Q-Setpoint at P=0.0pu -0.45 -2.000 0.000 18 39
a DelayTime P/Q Protection delay 2 0.000 10.000 18 40
PowerSupplyMon
a EnaRedunSupply Select Redundant Power Supply Configuration 0 0 1 19 16
PSU1ICU1
a Enable Enables the ICU source fault detection; 1 0 1 19 17
a SourcesConfWord Bitset: Bit1=Source1 connected; Bit2=Source2 connected;3=Source3 connected; 7 0 7 19 18
Converter
a IfNom Nominal Field Current [A] 14.1 0.0 6553.5 21 1
a UfNom Nominal Field Voltage [V] 147 0.0 6553.5 21 2
a UsynNom Nominal Synchronous voltage [V] 200 0.0 6553.5 21 3
a ITransducNomConf Converter Current Transducer Configuration Word; 3 0 8 21 4
a UVoltDiviNomConf Converter Voltage Configuration Word; 1 0 3 21 5
a ConvertTypeConf Converter Type Configuration Word. [1..5] = [D1..D5] 1 0 5 21 6
a IfAGL Air gap line current [A]; 3.8 0.0 6553.5 21 12
a UsynFreqNom Nominal synchronous voltage frequency 50 0.0 480.0 21 39
StateMachine
a ExcSysSupplyMode Excitation system main supply mode; 0 0 1 22 2
a FieldFlashTout Field flash timeout time; 5 0.00 60.00 22 4
a ExcOnTimeout Excitation On timeout time; 40 0.00 655.35 22 5
a InvModeTime Invert mode time; 40 0.00 655.35 22 6
ExcitationSystem
a DirectExc Direct Excitation; 0 0 1 23 2
a NomMachineFreq Nominal Machine Frequency 50 10.00 120.00 23 3
a Xd Direct axis synchronous reactance 1.866 0.000 5.000 23 4
a Xq Machine quadrature Reactance 1.807 0.000 5.000 23 5
a CosPhiNom Nominal cos-phi; 1 0.0000 1.0000 23 6
a Xe Infinite grid Reactance 0.1 0.000 0.500 23 7
a Td0s Direct axis no-load transient time constant Td0' 3.214 0.000 65.535 23 8
a Tds Direct axis short circuit transient time constant Td' 0.561 0.000 65.535 23 9
a ChanConfigWord Channel configuration word. 0=not defined, 1=Ch1, 2=Ch1 & Ch2, 3=Ch1 & Ch2 and BFCR; 2 0 3 23 16
a ChannelDefWord Channel definition word. 0=not defined, 1=Ch1, 2=Ch2, 3=BFCR; 1 OR 2 0 3 23 17
PQ_Lim
a Charact_QP10 P/Q limiter. Q-Setpoint for P=1.0pu -0.032 -1.5000 0.0000 6 1
a Charact_QP08 P/Q limiter. Q-Setpoint for P=0.8pu -0.2879 -1.5000 0.0000 6 2
a Charact_QP06 P/Q limiter. Q-Setpoint for P=0.6pu -0.304 -1.5000 0.0000 6 3
a Charact_QP04 P/Q limiter. Q-Setpoint for P=0.4pu -0.336 -1.5000 0.0000 6 4
a Charact_QP02 P/Q limiter. Q-Setpoint for P=0.2pu -0.36 -1.5000 0.0000 6 5
a Charact_QP00 P/Q limiter. Q-Setpoint for P=0.0pu -0.4 -1.5000 0.0000 6 6
a Release_PQLim Enable P/Q limiter 1 0 1 6 7
AVR_SetPt_VHz
a LimiterGradient V/Hz Limiter. Gradient (Ug/f) 1.15 0.00 10.00 7 22
a LimiterVfn V/Hz Limiter. Voltage at nominal frequency 1.15 0.000 10.000 7 23
a ThermalDownTime V/Hz Limiter. inverse-time back-integration time 1000 0.0 6553.5 7 24
a Limiter_Release V/Hz Limiter. Release 1 0 1 7 25
a LimiterDelayTime V/Hz Limiter. inverse-time fixed delay (for inverse-time function 0) 0 0.0 100.0 7 26
a LimDelayFuncSel V/Hz Limiter. inverse-time select curve (0: fix delay, 1: normal inverse, 2: very inverse, 3: exremley
0 inverse)
0 3 7 27
a LimDelayFactor V/Hz Limiter. inverse-time k factor 0 0.0000 6.5535 7 28
AVR_PID
a ta PID Lag time constant 1 0.00 20.00 2 7
a tb PID Lead time constant 0.1 0.00 10.00 2 8
a vp PID proportional gain 40 0.1 250.0 2 9
a vo PID low frequency gain 200 0.1 1000.0 2 10
a voo PID high frequency gain 40 0.1 1000.0 2 11
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 2 12
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 2 13
Ind_PID
a ta PID Lag time constant 1 0.00 20.00 3 13
a tb PID Lead time constant 0.1 0.00 10.00 3 14
a vp PID proportional gain 40 0.1 250.0 3 15
a vo PID low frequency gain 200 0.1 1000.0 3 16
a voo PID high frequency gain 40 0.1 1000.0 3 17
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 3 18
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 3 19
Cap_PID
a ta PID Lag time constant 1 0.00 20.00 3 20
a tb PID Lead time constant 0.1 0.00 10.00 3 21
a vp PID proportional gain 40 0.1 250.0 3 22
a vo PID low frequency gain 200 0.1 1000.0 3 23
a voo PID high frequency gain 40 0.1 1000.0 3 24
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 3 25
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 3 26
Field_Cur_Max_Lim_PID
a ta PID Lag time constant 1 0.00 20.00 4 13
a tb PID Lead time constant 0.1 0.00 10.00 4 14
a vp PID proportional gain 40 0.1 250.0 4 15
a vo PID low frequency gain 200 0.1 1000.0 4 16
a voo PID high frequency gain 40 0.1 1000.0 4 17
a EnableSetPtCorr Enable Setpoint correction for less regulator deviation 0 0 1 4 18
a GainReduction Gain reduction for INTEGRAL TYPE AVR LIMITER 0.5 0.0000 1.0000 4 19
Field_Cur_Min_Lim
a MinFieldCurrent Minimum field current limiter. Minimum field current (setpoint) 0 0.000 65.535 5 1
a Release_IfMinLim Enable minimum field current limiter 0 0 1 5 2
Field_Cur_Max_Lim
a MaxFieldCurrent Maximum field current limiter. Maximum field current. 1.6 0.000 5.000 4 1
a MaxTherFieldCur Maximum field current limiter. Maximum thermal field current. (inverse-time function starts if 1.05
the field
0.000
current2.000
exceeds4this value)
2
a PulseFun_En Maximum field current limiter. Enable dudt function 1 0 1 4 3
a ThermalDownTime Maximum field current limiter. Inverse-time back-integration time 1000 0.0 6553.5 4 4
a FixUpTime Maximum field current limiter. Inverse-time fixed delay (for inverse-time function 0) 0 0.0 100.0 4 5
a NoLimitDelay Maximum field current limiter. Time without limitation 0.01 0.000 1.000 4 6
a DelayFuncSelect Maximum field current limiter. Inverse-time select curve (0: fix delay, 1: normal inverse, 2: very inverse,
3 3:0 extremley
3 inverse)
4 7
a DelayFactor Maximum field current limiter. Inverse-time k factor 1 0.0000 6.5535 4 8
a TdynHys Maximum field current limiter. Time after limiter engagement with doubled hysteresis. (Helps to1prevent 0.00limiter
10.00
pump) 4 9
a Hysteresis Maximum field current limiter. Hysteresis to prevent limiter pump 0.05 0.000 0.200 4 10
a Release_IfMaxLim Maximum field current limiter. Enable max. field current limiter 1 0 1 4 11
a ThermCoolingFact Maximum field current limiter. Factor for thermal Limit until "Cooling" completed -> Italy Specification
1 0.5000 1.0000 4 12
AVR_SetPt
a MaxRefValue AVR Setpoint. Maximal value 1.1 0.000 1.500 7 3
a MinRefValue1 AVR Setpoint. Minimal value 1 0.9 0.000 1.500 7 6
Command
a ForceAuto Force the generator voltage regulator to be active; 0 0 1 99 5
a ForceManual Force the field current regulator to be active; 0 0 1 99 6
SystemMeasurement
a UGenNom Nominal generator voltage [kV]; 11 0.000 65.535 11 1
a UmachTprim Nominal transducer primary side generator voltage [kV]; 11 0.000 65.535 11 2
a UmachTsec Nominal transducer secondary side generator voltage [V]; 110 0.00 150.00 11 3
a IGenNom Nominal generator current [kA or A]; 1.377 0.000 65.535 11 7
a ImachIs5A Select current transducer type; 0 0 1 11 8
a ImachTprim Generator current transducer primary current [kA]; 1.7 0.000 65.535 11 9
a ImachTsec Generator current transducer secondary current [A]; 1 0.000 65.535 11 10
Converter
a IfNom Nominal Field Current [A] 14.1 0.0 6553.5 21 1
a UfNom Nominal Field Voltage [V] 147 0.0 6553.5 21 2
a UsynNom Nominal Synchronous voltage [V] 200 0.0 6553.5 21 3
a ITransducNomConf Converter Current Transducer Configuration Word; 3 0 8 21 4
a UVoltDiviNomConf Converter Voltage Configuration Word; 1 0 3 21 5
a ConvertTypeConf Converter Type Configuration Word. [1..5] = [D1..D5] 1 0 5 21 6
a IfAGL Air gap line current [A]; 3.8 0.0 6553.5 21 12
a UsynFreqNom Nominal synchronous voltage frequency 50 0.0 480.0 21 39
ExcitationSystem
a ChannelDefWord Channel definition word. 0=not defined, 1=Ch1, 2=Ch2, 3=BFCR; 1 OR 2 0 3 23 17
Document No. Rev.No.
E O IP PE - - GENERAL INFORMATIONS
\STANDARDS RELAY SETTING
\MRQ1
2 of 2 Information#59TN 0
Project: JINDAL TOWMCL 1X21MW
Protection Parameters:
Element Parameter Setting Range Setting Value
2 - 110V
U< 93
(EXIT - blocks the function)
U<
0.04 - 50 sec
t U< 2.5
(EXIT: t = ∞)
Z1A -300 - - - 300% of Zn 18
0 - - - 600% of Zn
Z1 Z1B (Z1B = 0 blocks the 202
function)
0.04 - 50 sec
t Z1 1
(EXIT: t = ∞)
Z2A -300 - - - 300% of Zn 18
0 - - - 600% of Zn
Z2 Z2B (Z2B = 0 blocks the 101
function)
0.04 - 50 sec
t Z2 0.25
(EXIT: t = ∞)
______________________________________________________________________________________________________________________________________
Format No.: IP-Q-F-2002
Rev./Date : B / 30.03.2010