Test Number 1
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°] Frequency Input C. 1 [s] Result Date
1.3 0 1.3 240 1.3 120 [Hz]
50 5.0694 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:29:58 PM
Trip Time
I1Ini=1.3A I2Ini=1.3A I3Ini=1.3A t1 5.0694 s
ΦI1Ini=0° ΦI2Ini=240° ΦI3Ini=120°
ΔI1=0.0001A ΔI2=0.0001A ΔI3=0.0001A
ΔΦI1=0° ΔΦI2=0° ΔΦI3=0°
I1Fin=1.3A I2Fin=1.3A I3Fin=1.3A
ΦI1Fin=0° ΦI2Fin=240° ΦI3Fin=120°
Signature : Approval :
Header : MICOM P122 (TRAFO-1) Serial Number : 39706749/08/1 Print Date : 09-Dec-19 9:35:38PM
Page 1 of 3
Test Number 2
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°] Frequency Input C. 1 [s] Result Date
3.25 0 3.25 240 3.25 120 [Hz]
50 2.1786 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:30:17 PM
Trip Time
I1Ini=3.25A I2Ini=3.25A I3Ini=3.25A t1 2.1786 s
ΦI1Ini=0° ΦI2Ini=240° ΦI3Ini=120°
ΔI1=0.0001A ΔI2=0.0001A ΔI3=0.0001A
ΔΦI1=0° ΔΦI2=0° ΔΦI3=0°
I1Fin=3.25A I2Fin=3.25A I3Fin=3.25A
ΦI1Fin=0° ΦI2Fin=240° ΦI3Fin=120°
Test Number 3
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°]
Frequency Input C. 1 [s] Result Date
6.5 0 6.5 240 6.5 120 [Hz]
50 1.5132 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:30:27 PM
Trip Time
I1Ini=6.5A I2Ini=6.5A I3Ini=6.5A t1 1.5132 s
ΦI1Ini=0° ΦI2Ini=240° ΦI3Ini=120°
ΔI1=0.0001A ΔI2=0.0001A ΔI3=0.0001A
ΔΦI1=0° ΔΦI2=0° ΔΦI3=0°
I1Fin=6.5A I2Fin=6.5A I3Fin=6.5A
ΦI1Fin=0° ΦI2Fin=240° ΦI3Fin=120°
Test Number 4
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°] Frequency Input C. 1 [s] Result Date
3.0000 0 3.0000 240 3.0000 120 [Hz]
50 0.0496 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:31:22 PM
Trip Time
I1Ini=2.8A I2Ini=2.8A I3Ini=2.8A t1 0.0496 s
ΦI1Ini=0° ΦI2Ini=240° ΦI3Ini=120°
ΔI1=0.01A ΔI2=0.01A ΔI3=0.01A
ΔΦI1=0° ΔΦI2=0° ΔΦI3=0°
I1Fin=3.0000A I2Fin=3.0000A I3Fin=3.0000A
ΦI1Fin=0° ΦI2Fin=240° ΦI3Fin=120°
Test Number 5
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°] Frequency Input C. 1 [s] Result Date
0.2 0 0 240 0 120 [Hz]
50 3.0556 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:32:38
Trip Time PM
I1Ini=0.2A t1 3.0556 s
ΦI1Ini=0°
ΔI1=0.0001A
ΔΦI1=0°
I1Fin=0.2A
ΦI1Fin=0°
Test Number 6
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°] Frequency Input C. 1 [s] Result Date
0.5 0 0 240 0 120 [Hz]
50 1.3238 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:32:48
Trip Time PM
I1Ini=0.5A t1 1.3238 s
ΦI1Ini=0°
ΔI1=0.0001A
ΔΦI1=0°
I1Fin=0.5A
ΦI1Fin=0°
Signature : Approval :
Header : MICOM P122 (TRAFO-1) Serial Number : 39706749/08/1 Print Date : 09-Dec-19 9:35:38PM
Page 2 of 3
Test Number 7
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°] Frequency Input C. 1 [s] Result Date
1 0 0 240 0 120 [Hz]
50 0.9322 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:32:56 PM
Trip Time
I1Ini=1A t1 0.9322 s
ΦI1Ini=0°
ΔI1=0.0001A
ΔΦI1=0°
I1Fin=1A
ΦI1Fin=0°
Test Number 8
I1 [A] I1 Phase [°] I2 [A] I2 Phase [°] I3 [A] I3 Phase [°]
Frequency Input C. 1 [s] Result Date
0.3000 0 0 240 0 120 [Hz]
50 0.2624 09-Dec-19
Ramp 1 Ramp 2 Ramp 3 Ramp 4 Ramp 5 9:34:33 PM
Trip Time
I1Ini=0.2A t1 0.2624 s
ΦI1Ini=0°
ΔI1=0.01A
ΔΦI1=0°
I1Fin=0.3000A
ΦI1Fin=0°
Notes
Test 1 : Checking of IDMT Characteristics of Over Current Protection (I>), Current Setting: 0.65 A, TMS: 0.5,
Characteristics : IEC Standard Inverse, Injected Current 2 x Current Setting, Action: 86, LED 5,Annunciation.
Test 2 : Checking of IDMT Characteristics of Over Current Protection (I>), Current Setting: 0.65 A, TMS: 0.5,
Characteristics : IEC Standard Inverse, Injected Current 5 x Current Setting, Action: 86,LED 5,Annunciation.
Test 3 : Checking of IDMT Characteristics of Over Current Protection (I>), Current Setting: 0.65 A, TMS: 0.5,
Characteristics : IEC Standard Inverse, Injected Current 10 x Current Setting, Action: 86,LED 5,Annunciation.
Test 4 : Checking of Pick up level and operating time of Definite Time Over Current Protection (I>>), Current Setting: 3.0 A,
Time Settings : 0.04 Sec, Characteristics : DT, Action: 86,LED 6,Annunciation.
Test 5 : Checking of IDMT Characteristics of Earth Fault Protection (I>), Current Setting: 0.1 A, TMS: 0.3,
Characteristics : IEC Standard Inverse, Injected Current 2 x Current Setting, Action: 86, LED 7,Annunciation.
Test 6 : Checking of IDMT Characteristics of Earth Fault Protection (I>), Current Setting: 0.1 A, TMS: 0.3,
Characteristics : IEC Standard Inverse, Injected Current 5 x Current Setting, Action: 86, LED 7,Annunciation.
Test 7 : Checking of IDMT Characteristics of Earth Fault Protection (I>), Current Setting: 0.1 A, TMS: 0.3,
Characteristics : IEC Standard Inverse, Injected Current 10 x Current Setting, Action: 86, LED 7,Annunciation.
Test 8 : Checking of Pick up level and operating time of Definite Time Earth Fault Protection (Ie>), Current Setting: 0.3 A,
Time Settings : 0.04 Sec, Characteristics : DT, Action: 86,LED 7,Annunciation.
Signature : Approval :
Header : MICOM P122 (TRAFO-1) Serial Number : 39706749/08/1 Print Date : 09-Dec-19 9:35:38PM
Page 3 of 3