You are on page 1of 2

ALI50EN

Auxiliary power supply 24V 4A + 1A

ALI50EN is an additional power supply with


lead sealed batteries which guarantees a
greater autonomy to the installations of Rive-
automatic fire lazione in the case of the need
to have several activations in case of alarm
and also allows a saving in cable preparation
thanks to a delocalizzazio- it feeds.

General characteristics
• CPR Certificate in accordance with
Standard EN 54-4
• Reload two accumulators 17Ah
• Metallic container with indication of the
proper functioning LED
• Led for the presence of network
messages, low battery, battery ok,
overvoltage battery and general fault
• Micro contact for opening control Certifications and Standards
• Relay for sending error message and The Power Group ALI50EN is designed for
relay for mains failure signaling use as a power unit of energy reserves in the
• Ponticelli programming for delay of Sicurez- plants za fire door in accordance with
power failure signaling Regula- Chin 305/2011 / EU.

Its electrical and mechanical characteristics


that make it conform to the standard EN 54-4:
1997 + A1: 2002 + A2: 2006 (Rive- Systems
tion and of the fire signal. Part 4: Power supply
equipment).

All specifications are subject to change without notice. All rights in this publication are reserved. For more
information contact:
Notifier Italy Srl
Via Grandi, 22 20097 San Donato Milanese (MI)
Tel .: 02-51897.1 Fax: 02-51897.30 E-mail: notifier@notifier.it - www.notifier.it
QUALITY MANAGEMENT SYSTEM AND ENVIRONMENTAL
D-326.1-ALI50EN-ITARev.A.202-2016 CERTIFICATION
UNI EN ISO 9001: 2008 - ISO 14001: 2004
Electrical Specifications environmental Specifications
• Supply voltage: 230 Vac + 10% / -15% • Operating temperature: from -5 ° C to + 40 ° C

• Grid frequency ac: 50 Hz sine • Relative humidity: From 5% to 93% ± 2%


• Cooling down: convection
• current consumption from the network: 1.1 A max
• Output voltage: 27.6 Vdc (-15% / + 10%) installation environments sheltered from the weather
• Minimum Output Voltage: 20 Vdc at maximum load, in
the absence of the mains voltage and with a discharged available models
battery. ALI50EN: Power supply 5A
• Voltage switch-off threshold: 20 Vdc
• Output Current: 5 A max
• max current for battery charging: 1 A
• Maximum current for loads (Imax.a): 4 A
• Maximum current supplied without recharging
the battery: 4.5A
• Maximum current per output: 1.5A
• Minimum current to loads (I min): 0 A
• maximum in the absence of the network current
(230V)
4A
• Threshold of internal resistance of the battery alarm

• Relay output power failure and failure to clean
contacts:
25Vca or 60VDC 1A MAX

Mechanical Specification
• Dimensions (in mm): 430 x 375 x120 (L x H x D)
• Weight: 6.25 Kg

Via Grandi, 22 T: 02 51 897 1


20097 F: 02 51 897 30
San Donato Milanese IS:
D-326.1-ALI50EN-ITARev.A.2 02-2016 (MI)
All specifications are subject to change without notice. All rights in this publication are reserved. notifier@notifier.it
www.notifier.it

You might also like