A three-phase rotary converter supplies 175A of current to a 1.4 ohm DC resistive load. It draws 100A of AC current at 0.8 power factor lagging. To determine the minimum transformer size needed, you calculate that at 100A and 0.8 power factor lagging, the apparent power is 100 * 1.25 = 125 kVA. The real power required is the DC load power of 175A * 1.4 ohms = 245 kW. The minimum transformer size must be greater than 245 kW, so the answer is B, 24.7 kVA.
A three-phase rotary converter supplies 175A of current to a 1.4 ohm DC resistive load. It draws 100A of AC current at 0.8 power factor lagging. To determine the minimum transformer size needed, you calculate that at 100A and 0.8 power factor lagging, the apparent power is 100 * 1.25 = 125 kVA. The real power required is the DC load power of 175A * 1.4 ohms = 245 kW. The minimum transformer size must be greater than 245 kW, so the answer is B, 24.7 kVA.
A three-phase rotary converter supplies 175A of current to a 1.4 ohm DC resistive load. It draws 100A of AC current at 0.8 power factor lagging. To determine the minimum transformer size needed, you calculate that at 100A and 0.8 power factor lagging, the apparent power is 100 * 1.25 = 125 kVA. The real power required is the DC load power of 175A * 1.4 ohms = 245 kW. The minimum transformer size must be greater than 245 kW, so the answer is B, 24.7 kVA.
An open delta bank is serving a three-phase rotary converter. The
converter supplies 175 A of current to 1.4 ohm dc resistive load. If the machine draws an AC current of 100 A at 0.8 pf lagging, determine minimum size of transformer needed.
A. 15.0 kVA
B. 24.7 kVA
C. 25.9 kVA
D. 19.4 kVA
382. The percent slip of an induction motor is the ratio