  A 3- synchronous motor runs at full-load speed of 1200 rpm. If the


load is reduced to one-half of rated, calculate its speed regulation.

A.  100%

B.  50%

C.  0%

D.  86.6%

398.  An industrial load is taking 500 kW at 0.6 lagging p.f. is desired to


raise the p.f. to 0.866 lagging using a synchronous machine whose power
input is 300 kW. Calculate the kVA rating of the motor required for such
operation and the power factor at whuch the motor will operate.

A.  365 kVA, 0.826 leading

B.  365 kVA, 0.778 leading

C.  305 kVA, 0.826 leading

D.  380 kVA, 0.866 leading