DOMESTIC HOT WATER CALORIFIERS SIZES CALCULATIONS

Project Name
DHWC Reference DHWC-1
Calculated By Z.Q
Checked By Z.Q
Date

The below data regarding Fixtues and flow (L/hr) for each fixture is taken from Table 9 Chapter 45 of ASHRAE"HVAC App

Building Type VILLA


Demand Factor 0.3
Storage Capacity Factor 1.25

FLOOR no. of private bas. no. of puplic bas. no. of bath tub no. of shower
Ground 2 0 0 1
1st 5 0 3 2
Total 7 0 3 3

Flow Rate L/h/Fixture) 7.5 0 76 114


Total Flow Rate (L/hr) 52.5 0 228 342

Total Hot Water Flow Rate (L/hr) 660.5


Total Storage Capacity 247.6875 Liter
No. of Cylinders 1
Cylinder Capacity 247.6875 Liter

Selection of Cylinder From Catalogs


Manufacturer
Capacity 250 Liter
Length 1000 mm
Diamter 3000 mm
Number of Cylinders Required 1

Domestic Hot Water Heating Load Calculation

Item Reference

Time Required to Heat Cylinder 1 hours


Cold Water Temperature 10 C
Required Hot Water Temperature 65 C

Heating Water Inlet temperature 80 C


Heating Water Outlet temperature 70 C

Heating System Efficiency 80%

Heating Coil Capacity 16 kW Per Cylinder


Heating Circuit Flow Rate 0.4 L/s per Cylinder

TOTAL HEATING CAPACITY 20 kW


TOTAL FLOW RATE 0.4 L/s
45 of ASHRAE"HVAC Applications" Handbook

no. of sinks no. of BD


1 1
0 4
1 5

38 7.5
38 37.5