Since these controllers are not specified by NFPA regulations, Selection criteria include the motor horsepower, and voltage and
they are built to NEMA industrial standards. frequency of the system.
FEATURES AND SELECTIONS In addtion to the devices mentioned, the control contains a
fusible 3-pole disconnect switch, magnetic motor contactor and
Jockey Pump Controllers offer the convenience of dependable thermal overload relays with external reset. For voltages above
factory-wired and tested units, all in one enclosure. Providing 480 volts, a control transformer is supplied. The controller is
automatic type operation, the pressure switch is identical to that furnished in a sturdy wall-mounted enclosure with hinged door.
used in the Main Fire Pump Controller with the start point set An optional running period timer is available.
about five pounds higher to cause the jockey pump to operate
AVAILABLE FOR USE AT TOP ONLY
2-3/16 2-3/4 3 2-3/4
(56) (70) (76) (70)
3
1/2 (13) & 3/4 (19) (76) KNOCKOUTS TOP AND BOTTOM
FOR CONDUIT SIZES SHOWN
1 (25)
KNOCKOUTS FOR
1/2 (13) & 3/4 (19)
CONDUIT EACH SIDE 1-15/16 (49)
24
(610)
26
(660)
RESET
7-15/16 (202)
1-7/16 (37)
3-1/2 (89) 3-1/2 (89)
KNOCK OUTS IN REAR FOR
CONDUIT SIZES SHOWN 11-1/2 (292) 4-11/32 DIA. MTG. HOLES
Section 936 Page 202
Date April 2006
L1 L2 L3
GROUNDING
SCREW
DISCONNECT
MEANS
H1 H3 H2 H4
Y W Y
W
L1 L2 L3
3
W
SIDE 2 SIDE
MTD. M MTD.
AUX. AUX.
CONT. CONT.
4 OL
0
H A
*
T1 T2 T3 *
AUTOMATIC RESET
CONTACTS CLOSE OPERATION SHOULD NOT
ON LOW PRESSURE BE USED WITH TWO
WIRE CONTROL
MOTOR
REMOVE GREEN
GROUND JUMPER
VOLTAGE CONNECT L1 L2
IF TRANSFORMER
230 H1 TO H3 H1 H4
IS NOT USED
H2 TO H4
460 H2 TO H3 H1 H4
DUAL VOLTAGE TRANSFORMER IS FOR SINGLE PRIMARY TRANSFER H1 H2
SHIPPED AS SHOWN CONNECTED
FOR HIGHER VOLTAGE. RECONNECT
JUMPERS "J" PER TABLE FOR
LOWER VOLTAGE.
Section 936 Page 302 FAIRBANKS NIJHUIS™ FIRE PUMPS
Date April 2006 JOCKEY PUMP CONTROLLER
Supersedes Section 936 Page 302
Dated March 1982 WITH RUNNING PERIOD TIMER
"J"
T
C H1 H3 H2 H4
T
O
I
T
Y Y
W W
L1 L2 L3
SIDE SIDE
MTD. M MTD.
AUX. AUX.
CONT. CONT.
4 OL
0
H A
*
T1 T2 T3 *
CONTACTS CLOSE
ON LOW PRESSURE AUTOMATIC RESET
MOTOR OPERATION SHOULD NOT
BE USED WITH TWO
REMOVE GREEN WIRE CONTROL
GROUND JUMPER
IF TRANSFORMER
IS NOT USED VOLTAGE CONNECT L1 L2
230 H1 TO H3 H1 H4
H2 TO H4
DUAL VOLTAGE TRANSFORMER IS
SHIPPED AS SHOWN CONNECTED 460 H2 TO H3 H1 H4
FOR HIGHER VOLTAGE. RECONNECT FOR SINGLE PRIMARY TRANSFER H1 H2
JUMPERS "J" PER TABLE FOR
LOWER VOLTAGE.