PRELIMINARY PROPOSAL REV:1

SCHEDULE OF DIGITAL & ANALOGUE INPUT (DI&AI) POINTS AT PUMP HOUSE, SUCTION & STORAGE TANK

Building Supervisory System (BSS) Physical Point Via Hardware.


Digital Input (DI) Analogue Input (AI)
Total
Electricall Equipment Mechanical Equipment Electrical ModBus Interface Mechanical Equipment

Engine/Pump/ System Trip Status


Engine/Pump Run/Stop Status

Power MD kWatt/Hrs (DPM)


Change Over Position (N/E)

Frequency/ speed (RPM)


Bil Item

Power kWatt/Hrs (DPM)


Phase Squence (DPM)
High Pressure Alarm

Power Factor (DPM)

Bearing temperature
Low Pressure Alarm

Analogue Input (AI)


Harmonics (DPM)
Frequency (DPM)
DC Supply Status
Status of Breaker

Suction Pressure
High Level Alarm
Low Level Alarm

Digital Input (DI)


Overflow Alarm

Water Flowrate
Trip/Fail Status

Running Hours
Voltage (DPM)
Current (DPM)
Battery Status
On/Off Status

Charger Trip

Water Level
AC Status

Vibration
A Pump House

1 Main Switch Board (MSB) c/w Starter Panel


Main Incomer Breaker MSB X X 2
Outgoing MCCB for Pump, Sub-DB, Telemetry Panel & others X 1
Automatic & Manual Change Over X 1
MSB Digital Power Meter (DPM) X 1
Pump Digital Power Meter (DPM) X 1
Surge Protection Devices (SPD) X 1
Capacitor Bank X 1
Bus Coupler X 1

2 Genset
Genset-Diesel Engine X X 2
Genset Battery X X X X X 5
AMF Board X X 2
Fuel Tank X X 2

3 Pump
Booster Pump X X X X X 1 4

B Suction Tank
Tank X X X X 3 1
Valve (Motorised Actuator/control inlet valve) X 1
Piping X X X X 2 2

C Storage Tank
Tank X X X X 3 1
Valve (Motorised Actuator/control inlet valve) X 1
Piping X X X X 2 2
TOTAL 31 12