You are on page 1of 7

SEWAGE TREATMENT PLANT LALPANI, SHIMLA

WALL DESIGN (7M propped cantilever) with 6.5 m water HT


Section properties and Material properties 2000
B = 1000 mm 3000
D = 700 mm 3500
H = 7000 mm 4000
Cover = 40 mm 4600
Bar dia on tenstion face = 20 mm
d = 650 mm
d at center of wall = 400
Ka = 1 For water
density of water = 10
Cubical compressive strength Fck = 20 MPa
Fe500 = 415 MPa

Loading applied

Effective Water Pressure @ Bottom


W.p = Ka X v X h = 65 KN/m2
LOAD APPLIED

MOMENT 211 AT THE BOTTOM


93 AT THE CENTER
SHEAR

Ast req. at distance h/3 on water side = 1498.48 mm2


Provide T16 @ 200mm C/C+ T12 @ 200mm C/C 1564 mm2

Ast req. at centre = 1073.26 mm2


Provide T12 @ 100mm C/C 1128 mm2
HILTI REQUIRED FOR REBARING T12 MM BAR AT 100 MM C/C
According to flexure Requirement
Ast provided = 1564 mm2

Design for shear at distance d

Vmax Service shear force = 147 KN

Vmax ultimate shear force = 220.5 KN

Tv Vmax. / B*d = 0.339 MPa


Pt % OF STEEL = 0.24062
Tc = 0.35
Remark = Tv>Tc ,ok = OK
Tv<Tc,not ok
BM SF SF AT D
13.3 20
45 45
63 110 98
107 80
64 85
SEWAGE TREATMENT PLANT LALPANI, SHIMLA
WALL DESIGN ( 7 M CANTILEVER WITH 4.85 M WATER FILL )
Section properties and Material properties
B = 1000 mm
D = 700 mm
H = 7000 mm
Cover = 40 mm
Bar dia on tenstion face = 12 mm
d = 654 mm
Ka = 1 For water
density of water = 10
Cubical compressive strength Fck = 20 MPa
Fe550 = 415 MPa

Loading applied

Effective Water Pressure @ Bottom


W.p = Ka X v X h = 48..5 KN/m2
LOAD APPLIED =

MOMENT 195

SHEAR 119
Ast req. = 1376.38 mm2
Provide T16 @ 200mm C/C+T12 @ 200mm C/C 1564 mm2

According to flexure Requirement


Ast provided = 1564 mm2

Design for shear at distance d

Vmax Service shear force = 97 KN

Vmax ultimate shear force = 145.5 KN

Tv Vmax. / B*d = 0.222 MPa


Pt % OF STEEL = 0.23914
Tc = 0.35
Remark = Tv>Tc ,ok = OK
Tv<Tc,not ok