Trip setting configuration detail for 1250 A Air Circuit Breaker

(A) Breaker details (B) SPV Details


Type of Breaker Air Circuit Breaker Watt Peak of PV Module
Make ABB Qty. of PV Module
Model No. SACE PR121/P
Capacity of inverter
Rated Current, A 1250
Total DC capacity
Total AC capacity

Max. Load current as per Inverter datasheet for 100kW Inverter


Max. Load current as per Inverter datasheet for 50kW Inverter
Calculated max. load current as per inverter quantity, In

(C) Trip settings of Breaker


Present setting for Over Current protection, I1 (0.8 + 0.05) x In

Power, P (kW) I1 x V X 1.732

NOTE: Present setting is not suitable as total AC capacity of Inverter is 550 kW and breaker setting is limited to 533
only. Hence breaker setting for Over Current (I1) shall be modified as follows.

New setting for Over Current protection, I1 new (0.9 + 0.0) x In

Power, P (kW) I1 new x V X 1.732


ker

(B) SPV Details


330 Wp
2122 Nos
100 kW 5 nos
50 kW 1 nos
700.26 kWp
550 kW

158.8 A
80 A
874 A

742.9 A

533.98 kW

er setting is limited to 533.98 kW


as follows.

786.6 A

565.39 kW