You are on page 1of 1

1756 ControlLogix I/O Specifications

1756-OW16I

ControlLogix AC (10…240V) DC (5…125V) isolated contact module

Simplified Schematic 1756-OW16I


+24V Isolated Wiring
L1-0 L1-0 2 1 L2-0
L1 OUT-0
Display L1-1 4 3 OUT-1 N.O.
L1-2 L1-2 6 5 OUT-2 N.O. L2-2
ControlLogix OUT L1-3 8 7 OUT-3 N.O.
DC-4 (+) 10 9 DC-4 (-)
Backplane L1-4 OUT-4 N.O.
L1-5 12 11 OUT-5 N.O.
Interface
L1-6 14 13 OUT-6 N.O.
Jumper Bar L1-7 16 15 OUT-7 N.O.
(Cut to Length) L1-8 18 17 OUT-8 N.O.
L1-9 20 19 OUT-9 N.O.
L1-10 22 21 OUT-10 N.O.
L1-11 24 23 OUT-11 N.O.
Nonisolated L1-12 26 25 OUT-12 N.O.
Additional jumper bars are available Wiring L1-13 28 27 OUT-13 N.O.
as catalog number 1756-JMPR. L1-14 30 29 OUT-14 N.O.
L1-15 32 31 OUT-15 N.O
L1 L1-15 34 33 Not Used
Not Used 36 35 Not Used
RELAY OUTPUT L2
Daisy Chain
ST 0 1 2 3 4 5 6 7 O to Other RTBs
ST 8 9 10 11 12 13 14 15 K

Technical Specifications - 1756-OW16I


Attribute 1756-OW16I
Outputs 16 N.O. individually isolated
Pilot duty C300/R150
5…125V DC
Operating voltage range
10…240V AC
1 A @ 5…30V DC
0.5 A @ 48V DC
Output voltage range (load dependent) 0.22 A @ 125V DC
1.5 A @ 120V AC 50/60 Hz
0.75 A @ 240V AC 50/60 Hz
Output delay time
Off to On 10 ms max
On to Off 10 ms max
Current draw @ 5.1V 150 mA
Current draw @ 24V 150 mA
Total backplane power 4.4 W
Power dissipation, max 4.5 W @ 60 °C (140 °F)
Thermal dissipation 15.35 BTU/hr
Off-state leakage current per point, max 1.5 mA per point
Minimum load current 10 mA per point
Initial contact resistance, max 100 mΩ @ 6V 1 A

244 Rockwell Automation Publication 1756-TD002M-EN-E - December 2019