Professional Documents
Culture Documents
0 Date 14/12/2020
SECTION 1: INTRODUCTION
S1.4 IGEM/TD/13 standard applies to the safe design, construction, inspection, testing,
operation and maintenance of pressure regulating installations (PRIs) in accordance
with current knowledge and operational experience.
This supplement provides additional requirements for new PRIs to be used for the
transmission of hydrogen including Natural Gas/hydrogen blended mixtures
(subsequently referred to as NG/H blends), and for the repurposing of Natural Gas
(NG) PRIs for hydrogen service. The section numbers in this supplement (preceded
by ‘S’) refer to the section numbers in the main document and specify the
requirements and qualifications which are in addition to those in the main
document. Where there is no numbered section in this supplement corresponding
to a section in the main document, the requirements of the main document apply
in full.
The term hydrogen service is used to indicate PRI plant and equipment transporting
hydrogen or a NG/H blend. The requirements for hydrogen service apply equally to
NG/H blends, unless the text indicates that the requirement depends upon the
concentration of hydrogen in the blend.
SECTION 2: SCOPE
S2.1 NG/H blends shall be considered to be equivalent to 100 mol.% hydrogen with
respect to limits on design stresses and the potential effect on the material
properties, unless an additional technical evaluation is carried out to qualify the
materials. NG/H blends containing in excess of 10 mol.% hydrogen shall be
considered to be equivalent to 100 mol.% hydrogen with respect to all other
requirements.
• with an upstream Maximum Operating Pressure (MOP) not greater than 100
bar
• with an outlet pressure greater than or equal to 7 bar
• for use with hydrogen or NG/H blends with a hydrogen content greater than
10%
• operating with a temperature range between -20°C and 120°C
S2.2 This supplement also gives additional recommendations relating to the repurposing
of NG PRIs to hydrogen service. These recommendations are in addition to those
in the main body of the document, which should continue to be applied except
where explicitly superseded by the recommendations of this supplement.
Note: The material performance factors defined in ASME B31.12 are based on limiting the hoop
stress, not derating the tensile properties. The design factors in Table S1 are based on the
material performance factors for pressures not exceeding 137.9 barg (2,000 psig).
S3.1 Hydrogen and NG/H blends have significantly differed properties to NG, and
therefore additional precautions and training are required to ensure operators are
1
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
competent to design, construct, inspect, test, operate and maintain PRIs and
installations in hydrogen service.
S3.2 The key difference in the parameters of NG and NG/H blends are the higher ignition
probability, poor flame visibility and higher leakage rate.
Risk assessments and procedures will need to be prepared and reviewed to reflect
the specific hydrogen service to be used.
Note: The following are some of the differences between NG and hydrogen which will need to be
considered
S5.1 Where possible all PRIs and installations operating in hydrogen service should be
located outside to allow good ventilation throughout the PRI and ensuring there is
no congested pipework which would allow gas to accumulate.
S5.2 Where the main pipework or part of the main pipework of a PRI or installation is to
be installed inside a housing then the housing shall be suitable for use with
hydrogen meeting the general requirements of IGEM/TD/13 and addressing the
following issues:
• the housing shall have good low and high-level natural ventilation to the open
air
• include an outlet opening located at the highest point in the housing in exterior
walls or the roof
• in areas where natural ventilation is not possible, consideration shall be given
for the installation of permanent atmosphere analysis equipment at suitably
located point (s) and/or forced ventilation
• explosion relief shall be designed so that if an explosion occurs the pressure will
be relieved without generating dangerous missiles.
S5.3 PRI and installation layout shall consider the hazardous areas generated by all
equipment, with careful consideration given to the location of vent or relief systems
and the hazardous area generated. Further guidance on hazardous areas resulting
from vent or relief systems can be found in EI IP-MCSP-P15 and section S10.1.
SECTION 6: HOUSINGS
S6.1 Instrumentation kiosks and cabinets are permitted to provide weather protection
for telemetry and control equipment including smallbore pipework. The guidance in
IGEM/TD/13 Section 6 shall be applied to these enclosures.
2
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
Note: The principles of IGEM/G/7 may be applied to the assessment of design risks for PRIs in
hydrogen service. The application should be extended to include the additional hazards posed
by hydrogen.
PRI outlet pipework shall be sized such that the gas velocity shall not exceed the
erosional velocity at peak conditions. High hydrogen gas velocities in piping
increases turbulence and pressure drop, contributes to excessive sound pressure
levels (aerodynamic noise) and can cause internal piping erosion and acoustically
induced vibration.
𝜌𝑆𝑇𝐷 𝑄𝑆𝑇𝐷
𝑣= 𝜋 2
𝜌𝐷
4 𝑖
v = velocity, ms-1
Di = internal dimeter, m
ρSTD = gas density at standard conditions, kg/m3
QSTD = volume flow rate at standard conditions m3/s
Ρ = gas density at pipeline conditions.
To estimate the highest velocity, the above equation is evaluated at the highest
temperature, lowest pressure and highest flowrate. Lower velocities are
recommended.
S7.3.1 The design of regulator streams shall take into consideration the flowrate and
pressure differential to ensure the critical flow limit is not exceeded in hydrogen
service.
Regulator impulse lines shall be located so that they are not affected by pressure
variations due to turbulence and flow instabilities (vortex shedding).
Regulators and other components should not vent process gas to the atmosphere
in an uncontrolled way.
A key consideration for hydrogen is to prevent leakage both across the valve and
to atmosphere.
Leakage to atmosphere is frequently caused by leaks through the valve body (such
as through the seal for the top works/bonnet or along the valve stem though the
3
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
• double block and bleed (DBB), single block and bleed with positive isolation
• each casting to be hydraulically leak tested
• soft seats in a metal retainer for in-line automatic valves and automatic
vents; specify bubble tight shut off (refer to standards API 598, API 6D, ISO
5208)
• metal to metal seat or soft seats in a retainer for in-line manual valves;
these should be combined with a means of positive isolation if used to block
the flow path before attempting invasive maintenance or inspection inside
the PRI
• metallic seat with valve outlet blocked
• no through bolting, body flanges or threaded connections in assembly of the
body of the valve.
S7.4.4.1 Valves having shell (body, bonnet, cover and/or end flange components) made of
cast or ductile iron shall not be used.
Flow control valves and pilot/control systems containing components made from
martensitic steels, cast iron, copper and nickel alloys shall be qualified for hydrogen
service.
The differential pressures across blocked filters in hydrogen service will be different
from NG. For similar energy flows the pressure drop will increase by a factor of
1.08 for hydrogen.
The limits for acceptable operation should be defined. Filter units shall not contain
hydrogen sensitive materials.
Note: To protect soft seats from possible damage from particulates carried with the gas, a strainer
of 300 microns (50 mesh) or finer should be installed upstream of valves or valve clusters with
soft seats which are normally open to flow during operation. Typically, this excludes vents,
drains, and pressure relief valves (pressure relief valves should not have a strainer upstream
since a partially blocked strainer would reduce the relieving capacity).
S7.6.1 For hydrogen, a reduction in pressure does not create a reduction in temperature
and for some operating parameters there will be a small increase in temperature.
Note: Hydrogen gas will increase in temperature approximately 5.6 oC when the pressure is reduced
from 137.9 bar (2,000 psig) to atmospheric pressure. The temperature increase is a function
of the starting temperature as well as the initial and final pressures.
The maximum and minimum outlet temperatures of the PRI should not exceed
the limits of the downstream connected pipeline or main.
S7.7.1 Velocities for hydrogen and NG/H blends will exceed the velocities in NG pipelines.
The sonic velocity of hydrogen is approximately four times that of NG so erosion
and abrasion shall be considered. Specific attention should be given to control
valves and relief valves which usually have sonic or near sonic velocities. The high
4
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
sonic velocity may result in problems at lower differential pressures than acceptable
for other gases. See section S7.2 for pipework sizing.
S7.7.2.1 High velocities in pipework systems increases turbulence and pressure drop,
contributing to excessive sound pressure levels (aerodynamic noise) and potentially
causing internal piping erosion. Acoustically induced vibration shall be avoided at
all times.
S7.7.3 Consideration of fatigue shall take account of the higher rate of fatigue crack growth
and degradation of endurance limits in hydrogen service.
Note: The rate of fatigue crack growth in hydrogen service may be 10 to 50 times higher than that
in air.
S7.7.4 The design of pipework systems should take into account the higher flow rates and
velocities in hydrogen service. Pipework systems that were well off resonance at
the highest NG flow rates might be affected by significant vibration in a high-speed
hydrogen flow.
S7.8.1 The design of vent lines should take into consideration the increase in temperature
which will occur when hydrogen is vented to atmosphere.
Note: Further guidance on hazardous areas resulting from vent or relief systems can be found in EI
IP-MCSP-P15 and CGA G-5.5. Hydrogen Vent Systems.
Manual and relief venting systems shall be designed for the temperature changes
which will occur when the gas is depressurised. Unlike NG, when hydrogen is
depressurised, a small increase in temperature may occur.
Note: Hydrogen gas will increase in temperature approximately 5.6oC when the pressure is reduced
from 137.9 bar (2,000 psig) to atmosphere. The temperature increase is a function of the
starting temperature as well as the initial and final pressures.
The principle measure for the potential of deflagration or detonation inside the vent
stack and pipework is the ratio of the length to internal diameter (L/d). The greater
the L/d ratio the more likely deflagration or detonation will occur.
The L/d ratio of the vent pipe shall be below 60:1. The number of turns and
connections to the vent stack shall be limited in order to reduce the possibility of
5
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
Note: Further information and guidance for venting systems can be found in CGA G-5.5. Hydrogen
Vent Systems.
S7.9.1 General
S7.9.1.1 Welded connections should be used where possible. Where welded connections are
not practical, leak resistant flange types such as raised face or ring type joint
flanges shall be used.
Threaded connections shall be used only where welded (including seal welded
threaded connections) and flanged connections are not practical. The sealant shall
be hydrogen compatible and shall be high temperature resistant to reduce the risk
of leaks during a fire. Typical uses of threaded connections are to match equipment,
especially instruments.
Erosion, abrasion and excessive noise shall be addressed in the design. The valve
seat ring shall be replaceable where erosion or abrasion might occur.
Grades higher than L485 (X70) shall not be used unless the pipe and weld material
is qualified for the intended service.
The maximum tensile strength of the pipe shall not exceed 690 N mm -2.
The maximum tensile strength of the weld metal shall not exceed 690 N mm -2.
S7.9.2.3 Material qualified for hydrogen service in accordance with ASME VIII Div 3 KD-10
may be used.
S7.9.2.5 The minimum wall thickness of line pipe shall be equal to or greater than the design
thickness as determined from:
t = PD(20fs)-1
Note 1: Design factors are based on the material performance factors given in ASME B31.12.
6
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
Pipe and fitting materials shall be qualified for use in hydrogen service in
accordance with the hydrogen supplement to IGEM/TD/1 Section S5.8.
S7.9.3 Fittings
S7.9.3.1 Fittings shall be suitable for hydrogen service, see hydrogen supplement to
IGEM/TD/1 Section S5.8.
The maximum hardness shall not exceed 250 HV10 (or HV5).
S7.9.4 Gaskets
Gasket materials shall be appropriate for the design pressures and temperatures,
be hydrogen compatible and leak resistant. In addition, consideration shall be given
to resistance to fire, due to the flammability of hydrogen. Teflon or graphite filled
spiral wound gasket with a raised face flange or a copper ring with a ring joint
flange should be used.
Bolting studs, nuts and washer shall be compatible for the fitting and suitable for
use with hydrogen, where they may be exposed to hydrogen.
S7.9.6.1 Pipework shall be stainless steel designed to minimise leakage by limiting the
number of compression fittings.
The use of screwed pipework and fittings should be avoided where possible.
S7.9.8 Pre-testing
S7.10 WELDING
Note: If the line pipe specification states the carbon equivalent is “as agreed” then the carbon
equivalent shall not exceed 0.43.
S7.10.1 Preparation
The hardness of the weld and heat affected zone shall not exceed 250 HV10 (or
HV5). The hardness determination is to be made via microhardness traverses on
mounted metallographic samples removed from process/operator weld qualification
samples. Production hardness testing also should be considered.
The maximum tensile strength of the weld metal shall not exceed 690 N mm -2.
Consideration shall be given to the need for stress relief using post-weld heat
treatment on thick sections and fittings or when the carbon equivalent is equal to
or greater 0.43.
S7.11.1 The hoop and longitudinal stresses are limited to 180 N mm-2.
7
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
Note: The steady state concentration of hydrogen in a stressed lattice is related to the hydrostatic
stress. The objective of this condition is to ensure consistency with the limit on the hoop stress.
S7.11.2 Fatigue analysis shall take into account the increased rate of fatigue crack growth
rates in hydrogen service. The rate of fatigue crack growth in hydrogen service may
be 10 to 50 times higher than that in air.
S7.11.3 Hydrogen stress cracking is associated with absorption of hydrogen and a delayed
time to failure during which hydrogen diffuses into regions of high triaxial stress.
The analysis of high stressed locations in thick components shall take into account
the risk of hydrogen stress cracking.
S7.12 METERING
S8.2.1 The effect of the high sonic velocity of hydrogen should be taken into account when
the pressure drop through the regulator is greater than 10%. Hardened seats and
plugs should be used.
Special attention should be given to the stability of the regulators which may be
affected by the time taken for the sensed pressure to be transferred back to the
regulator control arrangement which may be reduced for hydrogen. There is also
potential for reductions in regulator stability if the inlet to the impulse line is in a
location which is affected by pressure variations caused by turbulence and flow
instability.
Pressure safety system shall be suitable for use with hydrogen. Hardened seats and
plugs shall be used for relief valves.
The CP system shall be designed to ensure current limits and protection criteria
limits are appropriate for systems operating in hydrogen service.
Note: The steel grades that can be used for hydrogen service pipelines have a specified minimum
The protection criteria specified in BS EN 12954 for low alloyed carbon steels should
apply to pipeline systems in hydrogen service.
8
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
The instant OFF pipe to soil potential should not be more negative than -1.20V vs
Cu/CuSO4 to mitigate against the risk of cathodic disbondment on the pipeline
coating.
Areas that may become hazardous as the result of the presence of flammable gas
are classified in the UK as Zone 0, 1 and 2 and are defined in EI IP-MCSP-P15 and
the Research Report: Dispersion Modelling in support of EI IP-MCSP-P15
Note: “NG/H blends with >30% hydrogen content shall be considered to be equivalent to refinery
hydrogen (80% hydrogen mixture) and EL IP-MCSP-P15 can be used to assess hazardous
areas. EI research report provides dispersion modelling results for 100% hydrogen and can
used to assess the hazardous areas. Where the hydrogen content ≤ 30% it shall be considered
to be NG (methane) and SR/25 may be used for hazardous area assessment.”
Note: Hydrogen and NG/H blends are in explosion group Group IIC whereas NG is in
Group IIA.
The design of any flow metering system shall be in accordance with appropriate
standards for hydrogen service.
S13.1.4 Purging
Only indirect purging operations using an inert gas such as nitrogen are permitted
on PRI’s and installations in hydrogen service.
9
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S14.1 General
Any risk created by any undertaking and/or work practices, shall be assessed to
identify the measures that may be needed to eliminate them or to reduce them to
as low as reasonably practicable to comply legislative requirements. The following
steps should be incorporated in any risk assessment:
Note: Further guidance can be found in IGEM/G/7. Additional hazards posed by hydrogen must be
considered.
S14.2.3.1 The systems of work shall be suitable for the different hazards posed by the
transportation of hydrogen or NG/H blends:
Job instructions shall reflect the different hazards associated with hydrogen service
and the control measures required.
The permit to work system shall reflect the additional hazards associated with
hydrogen service.
S14.2.4.1 The emergency arrangements shall be appropriate for the hazards and risks posed
by PRI and installation operation in hydrogen service. Clear signage shall be
installed so that PRIs and installations operating in hydrogen service can be clearly
identified by the emergency services.
S14.2.4.2 Where a site contains a mixture of hydrogen service and NG equipment then there
shall be a clear demarcation of the areas in hydrogen service.
S14.2.5.1 Training should be designed so that relevant personnel have the appropriate
knowledge and understanding of the risks associated with hydrogen service and
the difference between NG PRIs and installations and PRIs and installations which
are used in hydrogen service.
10
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S14.2.5.2 Specific training shall be carried out for personnel working on PRI’s and installations
operating in hydrogen service incorporating the safety measures and procedures
necessary for the gas being transported.
S14.2.6 Records
S14.6.2.2 Detailed technical and operational records should be maintained including flow
diagrams and plans of all plant and equipment differentiating the type of gas being
transported through the PRI or installation.
S14.6.2.3 Any change or modification to PRIs and installation should be recorded including
the type of gas to be transported and where appropriate reference made to
IGEM/GL/5.
The site information shall clearly state the type of gas being transported through
the pipework, where more than one type of gas is being transported then drawings
and records should clearly differentiate between NG and hydrogen service
pipework.
S14.3.1 Procedures should be used to highlight certain safety aspects on maintenance and
in particular the additional hazards and precautions associated with hydrogen
service, for example:
11
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S14.5.1 General
S14.5.1.1 An assessment of the risks which may exist, or are foreseeable, during any
maintenance activity, should be carried out to help decide what measures are
necessary for safety.
S14.5.1.2 The assessment shall consider the additional hazards and control measures which
will be necessary to carry out maintenance safely.
S14.6 ISOLATIONS
S14.6.1 An isolation scheme for the PRI should be developed to ensure that the appropriate
level of safe isolation from all sources of danger is achieved taking into account the
increase leakage rate associated with hydrogen.
The risk of any uncontrolled gas escape or release should be reduced to a minimum
and attention paid to the disconnection and isolation of associated electrical
supplies, instrumentation and control equipment, cathodic protection, etc.
S14.7 VENTING
Note: Information and guidance for venting systems can be found in CGA G-5.5. Hydrogen Vent
Systems.
S14.8 PURGING
Only indirect purging operations using an inert gas such as nitrogen shall be
permitted on PRIs and installations in hydrogen service.
Note: Guidance on indirect purging is provided in IGE/SR/22. Attention should be given to the
asphyxiating effects of inert gas.
S14.9.1 Special attention should be paid to the final leak check to take account of the
increased leakage rate associated with hydrogen and NG/H blends. Leak testing of
mechanical joints should be in accordance with an appropriate standard (e.g. ISO
20484).
S14.10 RE-COMMISSIONING
S14.10.1 Special attention shall be paid to ensure flame detection and leakage detection
devices if installed are functioning correctly following the completion of
maintenance activities and prior to recommissioning.
The overall maintenance strategy shall be reviewed within 2 years of operating PRIs
and installations in hydrogen service to ensure maintenance is being applied
effectively.
12
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
• visual checks of the general condition and security of the PRI or installation
• possible leakage
• functional checks of safety devices.
S16.1 GENERAL
(g) change of service – introduce new gas and raise pressure to the new MOP.
13
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S16.3.1 The initial step to determining the suitability of a PRI for repurposing is to define
the type of gas to be transported along with the following parameters which will be
considered as part of the design review:
S16.4.1 To determine the suitability of a PRI for repurposing, the original design and
construction records for the PRI shall be reviewed along with the historical
operational, maintenance, inspection, modification and repair records.
S16.5.1 The design and construction records for the PRI shall be reviewed in accordance
with Table 2 Design Assessment checklist and Design Review Special
Considerations detailed in S16.6.
S16.5.2 Any areas which are identified as not being suitable for use with the proposed
operating parameters shall be recorded. For example, the hazardous area extends
beyond site boundary.
14
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
1 Location and Confirm the location and existing layout of the PRI is
layout suitable for the new gas blend as detailed in S5.
2 Hazardous area Complete a hazardous area analysis and plant layout for
assessment the new gas blend as per S5.3.
3 Housings, kiosks Review the housing to ensure they meet the
buildings requirements detailed in S6.
4 PRI Design Review the PRI design to ensure it is suitable for the
blend of gas and flowrate.
5 Flowrate Carry out flow analysis to confirm that the flow through
velocity the existing installation pipework can be maintained at
the required volume and velocity.
6 Pipework sizing Confirm the pipework sizing meets the requirements of
S7.2.
7 Pressure Ensure the design pressure boundaries meet the
boundaries requirements of S7.3.
8 Isolation valves Review the isolation valves to confirm they are suitable
for the desired flowrate and meet the requirements of
S7.4.
9 Gas Cleaning / Confirm the existing filters meet the desired flow rate
Filters and the gas cleaning requirements detailed in S7.5.
15
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S16.6.1 The minimum wall thickness of line pipe shall comply with Clause S7.9.2.
S16.6.2 The maximum allowable stress in the installation pipework shall comply with the
requirements of Clause S7.9.2.5.
S16.6.3 If a design pipework stress analysis is not available, this shall be carried out in
accordance with the methodology in IGEM/TD/12, subject to the requirements of
Clause S7.11.
S16.6.4 Fatigue analysis shall evaluate the total fatigue damage for the installation, taking
into account previous damage and possible future damage evaluated using
increased crack growth rates for hydrogen or NG/H blends, in accordance with
Clause S7.11. The minimum fatigue life for future operation in hydrogen service is
40 years.
S16.6.5 Materials records shall be reviewed to ensure all materials comply with the
restrictions in Section S7. The performance limits of any polymer materials
incorporated in equipment components and the effectiveness of seals and
lubricants, and the compatibility of auxiliary and impulse lines with hydrogen shall
be established.
S16.6.7 Steel and concrete supports shall be checked to ensure full support is provided and
no additional displacements or loadings are applied to pipework, components and
equipment.
S16.7.1 Assess the condition of the pipework and components and carry out appropriate
fitness for service assessment on any detected damage. Defect assessment
calculations should assume a reduction of 50% in fracture toughness and ductility
unless specific material qualification data is available.
S16.7.2 Assess the acceptability of any existing repairs and modifications for hydrogen
service. Particular attention should be applied to leak clamps, epoxy shells and
grouted tees.
S16.7.3 The potential susceptibility of the risk of pre-existing stress corrosion cracking
(SCC) which may be exacerbated by the presence of hydrogen in the steel shall be
assessed.
16
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S16.8.1 Functional and operability tests shall be carried out on the existing PRI operating
with NG to inform how the PRI would behave in hydrogen service. These tests shall
include the following:
Note: See IGEM/TD/13 Clause 14.2 for more detail on functional and operability tests.
S16.8.2 The function and operability tests shall be used to inform the design review of the
PRI and predict the function and operability of the PRI.
S16.9.1 The design review, condition assessment, integrity assessment and functional
operability studies shall be reviewed to determine if the PRI is suitable for use in
hydrogen service at the operating parameters required.
S16.9.2 In cases where it is not possible to achieve the requirements, such as where the
predicted hazardous area extends beyond the site, then a Quantified Risk
Assessment (QRA) shall be undertaken to determine the level of risks posed to the
general public in the vicinity of the PRI.
S16.9.3 Where the PRI is suitable for uprating with modifications, the modifications should
be carried out before the hydrostatic test is undertaken.
Note: The modifications which may be necessary are described in IGEM/TD/13 Clause 14.15.7.5.
S16.9.4 The PRI should then be subjected to a strength test, consistent with the revised
MOP, as described in Section 12.
S16.10.1 When all the requirements of IGEM/TD/13 Clauses 14.15.7.2 to 14.15.7.4 have
been taken into account and the PRI is suitable for change of service with
modifications, such modifications shall be carried out before any change in gas or
operating parameter is allowed.
S16.10.2 The modifications should be controlled and documented using the IGEM/GL/5
modification procedure.
S16.11.1 On completion of any modification required to the PRI and following all the design
reviews, functional and operability studies and commissioning plan there shall be a
formal review of all the documentation before a Competent Person approves the
PRI for operation in hydrogen service.
S16.11.2 Only after formal acceptance that the PRI is suitable for use in hydrogen service
shall the PRI be commissioned for use with the new gas blend and the operating
parameters be revised.
17
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.
Supplement to IGEM/TD/13 Edition 2 Draft rev 5.0 Date 14/12/2020
S16.12.1 Commissioning shall not commence until a detailed commissioning plan has been
developed and the PRI has been approved for change of service by a Competent
Person.
S16.12.2 Immediately prior to commissioning, the PRI shall be surveyed to ensure that no
operations are being carried out adjacent to the PRI and all equipment and signage
is suitable for the change of use.
S16.12.3 A leak detection survey of all joints and at valves and regulators, including internal
leakage due to backflow through slam shut valves, shall be carried out.
S16.12.4 The functional and operability tests detailed in S16.8 shall be repeated for the PRI
with new gas, to confirm the PRI is operating safely within the design limits.
S16.12.5 Metering equipment shall be checked to confirm accurate flow measurement for
hydrogen service.
• leakage surveys
• noise studies at night and during the daytime
• temperature measurement
• functional tests
• vibration.
S16.13.2 Following successful post change of service assessment, the PRI should revert to
revised inspection and maintenance frequencies developed for the PRI with the new
gas.
18
©IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk.