Schaffner Maintenance Instruction For Power Module
Schaffner Maintenance Instruction For Power Module
www.myecosine.com
English version
© All rights reserved, even and especially in cases of proprietary rights applications.
We also retain sole power of disposal, including all rights relating to copying, transmission and
dissemination.
The most current edition of these instructions (PDF format) can be obtained from your contact
of the Schaffner service organization.
Other technical documentation of our products is also available in the download area of our
website www.schaffner.com
Document name:
Maintenance Manual for FN35xx Power Module
Version history
Table of Contents
1 Introduction 4
1.1 Purpose 4
1.2 Additional Resources 4
2 General Safety Notes and Installation Guidelines 5
3 Environmental Conditions / Exclusion of warranty 6
4 Welcome 8
4.1 About this manual 8
4.2 Who should read this guide 8
4.3 Personnel qualification 8
4.4 Get help 8
4.5 Get training 8
4.6 Contact us 9
5 POWER MODULE 380VAC-415/480VAC 3-/4-WIRE 10
5.1 Maintenance schedule 10
5.2 Wear parts 10
5.3 Maintenance instruction 11
5.3.1 Check operation, clean fans, fan guard and air path 11
5.3.2 Replace fans 1 to 3 17
5.3.3 Replace PDB board fuses F100, F101 & F102 21
5.3.4 Replace PDC board fuses F701 & F705 24
5.3.5 Replace control board battery 27
4 Ecosine® Active Harmonic Sync Filters – Maintenance Manual for FN35xx Power Module
1 Introduction
1.1 Purpose
The ecosine active sync User and Installation Manual provide information for unpacking,
installation and commissioning of the filter and describe mechanical and electrical installation
of the filters. It contains basic information about parameters and communication as well as
troubleshooting information.
The instructions are intended for use by qualified personnel. Reading and following these
instructions is mandatory. Particular attention need to be given to the general safety notes
and installation guidelines (cautions and warnings)! Keep these instructions available with
the filter(s) at all times.
Installation of the ecosine active sync filter, inspections for proper operation, and certain
troubleshooting measures may only be performed by qualified personnel. All other measures
may be performed by people who have read these instructions.
The ecosine active sync filter maintenance manual provides information on maintenance and
testing for field service technicians, as well as disassembly and assembly instructions for
wear parts.
5 Ecosine® Active Harmonic Sync Filters – Maintenance Manual for FN35xx Power Module
Important Ecosine active sync harmonic filters (AHF) listed below are IP20
or IP54 devices to be installed in an environment in compliance
with the requirements named in this document.
All AHF must be installed in a clean, dry location, e.g. in
sufficiently ventilated or air-conditioned electric cabinets or closed
electric rooms. Contaminants such as oils, liquids, corrosive
vapors, abrasive debris, dust and aggressive gases must be kept
out of the filter enclosure.
WARNING: Conductive dust may cause damage to ecosine
active sync harmonic filters. Ensure that installation site of
ecosine active sync is free of conductive dust.
Corrosive levels Corrosive levels for storage, transport and operation Class
3C2(3):
(IEC 60721-3-3)
• Applies to locations with normal levels of contaminants,
experienced in urban areas with industrial activities
• Levels:
Environmental parameter Units(1) Class 3C2(2)
Mean value Max value
Sea salt Salt mist
ppm 0.3 1.0
Sulphur dioxide
cm3/m3 0.11 0.37
ppm 0.1 0.5
Hydrogen sulphide
cm3/m3 0.071 0.36
ppm 0.1 0.3
Chlorine
cm3/m3 0.034 0.1
ppm 0.1 0.5
Hydrogen chloride
cm3/m3 0.066 0.33
ppm 0.01 0.03
Hydrogen fluoride
cm3/m3 0.012 0.036
ppm 1.0 3.0
Ammonia
cm3/m3 1.4 4.2
ppm 0.05 0.1
Ozone
cm3/m3 0.025 0.05
ppm 0.5 1.0
Nitrogen oxides
cm3/m3 0.26 0.52
(1)The values given in cm3/m3 have been calculated from the values
given in mg/m3 and refer to a temperature of 20 °C and a pressure
of 101,3 kPa. The table uses rounded values.
(2)Mean values are expected long-term values. Maximum values are
limit or peak values, occurring over a period of time of not more than
30 min per day.
(3)IEC 60721-3-3 is only applied to the coated PCB covered areas
4 Welcome
4.1 About this manual
This manual is meant to provide comprehensive information on maintenance requirements of
Ecosine® active harmonic filters. The issues discussed in this guide cover the basic
maintenance schedule, necessary wear parts as well as practical aspects of working with
Ecosine® active harmonic filters. The guide will familiarize you with the required hardware
checks and settings to conduct various maintenance tasks.
Caution
Maintenance tasks should only be performed by trained and skilled personnel to
avoid damages to the unit or injuries of personnel.
CAUTION
Warning
Changing of wear parts may cause malfunction of device and can cause injuries
of personnel if not properly performed.
WARNING
4.6 Contact us
Schaffner – More than just filters. Schaffner is in the unique position of being able to support
the user with problem analyses, engineering advice, testing and measurement support,
custom products, and a worldwide customer service organization. Our goal is to ensure that
you obtain the level of support you actually need. Toward this objective, we invite you to
contact your local Schaffner representative at any time that we may be of service to you. You
can find out more about us and your local contact on our corporate website or you may
contact us via email:
Replace fans 1 to 3
5.3.1 Check operation, clean fans, fan guard and air path
5.3.1.1 Tool List
1. Gloves
2. Brush
3. Cleaning paper
4. Alcohol
5. Compressed air
6. Vacuum cleaner
Attention!
Do not go with the air gun closer than 30 cm
15 Ecosine® Active Harmonic Sync Filters – Maintenance Manual for FN35xx Power Module
Attention!
Ensure that the three fans are connected in
the right sequence:
Spare part
Attention!
Different cable length
Attention!
Ensure that the three fans are connected in
the right sequence:
Spare part
Spare part
Attention!
Ensure that the three fans are connected in
the right sequence:
Spare part
info@schaffner.com EMEA
www.schaffner.com Schaffner EMC S.A.S.
Rue du Luxembourg 16
68310 Wittelsheim
France
India
Schaffner India Pvt. Ltd
“ShriNivas” 26, 2nd Street,
Kasthuri Nagar Extension,
Ondipudur, Coimbatore - 641 016
Tamil Nadu
India
North America
Schaffner EMC Inc.
52 Mayfield Avenue
Edison
New Jersey 08837
United State of America
®
2014 Schaffner Group