Typical chiller issues we encounter include low refrigerant, Resources for Energy
which is more prevalent on high-pressure machines; fouled
Engineers
condenser and evaporator tubes; or issues with Variable
CO2 Calculator
Geometry Diffusers (VGDs), Inlet Guide Vanes (IGVs),
(/co2-equivalency-
sensors, and Variable Frequency Drives (VFDs). We also
calculator)
occasionally see liquid carryover and excessive compressor
Training Guides
oil. We’ve even run across an older chiller control board
(/resources-for-
causing reduced chiller performance. It all points to the need
energy-
for chiller plant monitoring and analyses of analytics.
engineers/training-
guides)
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 2/8
2/4/2021 Finding Hidden Energy Waste in Water-cooled Chillers with Monitoring and Data Analytics | Chiller & Cooling Best Practices
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 3/8
2/4/2021 Finding Hidden Energy Waste in Water-cooled Chillers with Monitoring and Data Analytics | Chiller & Cooling Best Practices
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 4/8
2/4/2021 Finding Hidden Energy Waste in Water-cooled Chillers with Monitoring and Data Analytics | Chiller & Cooling Best Practices
The top graph in this diagram shows Chiller No. 2 (red line) with a
discharge superheat in excess of 20 °F, which kept it from increasing
capacity throughout the day. Once the VGD actuator was corrected,
the discharge superheat reduced significantly, and Chiller No. 2 was
able to match the load and efficiency of the equivalent Chiller No. 1
(blue line) as shown in the bottom two graphs.
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 5/8
2/4/2021 Finding Hidden Energy Waste in Water-cooled Chillers with Monitoring and Data Analytics | Chiller & Cooling Best Practices
Figure 2: Shown are Chillers No. 5 (blue line) and No. 6 (red line)
operating at the same level of efficiency before a trigger board
malfunctioned on Chiller No. 6 on Friday and how a repair on the
same chiller on Sunday corrected the issue.
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 6/8
2/4/2021 Finding Hidden Energy Waste in Water-cooled Chillers with Monitoring and Data Analytics | Chiller & Cooling Best Practices
Chillers are the largest energy user in the heating and cooling
system and many of them waste a considerable amount of
energy, i.e., dollars. It’s even more of a reason for having
detailed chiller monitoring and analytics solutions in place.
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 7/8
2/4/2021 Finding Hidden Energy Waste in Water-cooled Chillers with Monitoring and Data Analytics | Chiller & Cooling Best Practices
(/magazine/subscription)
CONTACT US (/INDEX.PHP/CONTACT_US)
MEDIA KIT (HTTPS://COOLINGBESTPRACTICES.COM/SITES/DEFAULT/FILES/CCBP_MEDIAKIT_2021_REV2.PDF)
ADVERTISE (/INDEX.PHP/ADVERTISE) PRIVACY POLICY (/INDEX.PHP/PRIVACY_POLICY)
TERMS AND CONDITIONS (/INDEX.PHP/TERMS_AND_CONDITIONS)
https://coolingbestpractices.com/system-assessments/chillers/finding-hidden-energy-waste-water-cooled-chillers-monitoring-and-data 8/8