Professional Documents
Culture Documents
SYSTEMS
T OF
PRODUC
03 SFFECO FIRE PUMPS SYSTEMS
MANUFACTURING
The Fire Pumps undergo various processes in our modern well organized manufacturing and assembly line.
Before delivering to our customers, each pump undergoes necessary inspection, tests and production control,
during the Assembly process, for which all records are maintained.
TESTING FACILITY
SFFECO has established a fully equipped state of the art, UL/FM and NFPA 20 compliant Pump Testing
facility with advance testing and calibration devices that enable to accurately inspect and test the operation
of each Centrifugal Stationery Fire Pump to the required level of compliance standard.
PERFORMANCE TESTS
Each pump produced, undergoes performance testings as follows
a) OPERATION TEST
Performance curves are plotted showing the Efficiency, Brake-Horsepower (kW), and Total Head
developed at shutoff, at rated capacity, at 150 percent of rated capacity, and at selected intermediate
capacities between shutoff and maximum capacities exceeding 150%
of rated capacity.
b) HYDROSTATIC TEST
Each pump is tested hydrostatically for not less than 5 minutes. The
test pressure is to be upto 2 times the maximum working pressure of
the pump, but in no case less than 250 psi (1724 kPa) to ensure no
rupture or leakage through the castings at the test pressure.
c) IMPELLER BALANCING
The impellers of each pump are dynamically balanced to the G6.3
balance quality grade in accordance with the requirements for pump
impellers in the Standard for Mechanical Vibration – Balance Quality
File No.FSP-2016-0370
100%
horizontal
listed/approved example :
© 2016. SFFECO FIRE PUMPS & SYSTEMS
05 CENTRIFUGAL FIRE PUMPS
HORIZONTAL SPLIT CASE 50/60 Hz
Approx Speed Head Bar - (PSI) Head Bar - (PSI) Max Working
Model Dsg Flow (GPM) Size (in.)
(RPM) UL Listing FM Approved Pressure (PSI)
3500 114-208 114-208 6x4
SFP150-25SH 300
3600 121 - 220 121 - 220 6x4
2900 206 - 289 206 - 289 6x4
SFP150-40SM 385
3000 221 - 310 221 - 310 6x4
3500 226 - 316 226 - 316 6x4
SFP150-SN31SH 150 GPM 3600 239 - 334 239 - 327 6x4
405 File No.FSP-2016-0370
SFP300-28SM
2900
3000
100 - 156
107 - 167
100 - 156
107 - 167
5X3
5X3
239 Horizontally Split Casing Design
Efficiently Designed Shaft
2900 120-219 120-219 5X3
SFP400-35SM 319
3000 129-234 129-234 5X3
2900 98-155 98-155 5X3
SFP400-28SM 239
3000 105-166 105-166 5X3
3500 114-206 113-206 6x4
SFP400-25SH 400 GPM 3600 120 - 218 120 - 218 6x4
300
SFP500-25SH
3000
3500
102-165
113-205
102-165
113-205
5X3
6x4
300
150 GPM to 2000 GPM
88 335
3600 120-217 120-217 6x4
500 GPM 2900 119-198 119-198 6x4
SFP500-32SM 290
3000 128-212 128-212 6x4
2900 204 - 284 204 - 284 6x4
SFP500-40SM 385
3000 219 - 304 219 - 304 6x4
SFP500-SN31SH
3500
3600
224 - 312
237 - 330
224 - 312
237 - 324
6x4
6x4
405 405
2900 137 - 203 130 - 197
SFP500-31SM 220
3000 - 139 - 212
SFP750-31SM 2900 131 - 201 131 - 201 6X4 220
3500 106-199 106-199 6x4
SFP750-25SH 300
3600 113-211 113-211 6x4
2900 111-194 111-194 6x4
SFP750-32SM 290
3000 120-208 120-208 6x4
2900 148-182 148-182 8X5
SFP750-29SM 268
3000 159-196 159-196 8X5
SFP750-12SH
3500
3600
148 - 266
157 - 281
148 - 266
157 - 281
8x5
8x5
362 applications.
3500 190 - 290 190 - 290 6x4
SFP750-EL31SH 377
3600 201 - 306 201 - 299 6x4
SFP1000-31SM
SFP1000-29SM
2900
2900
134 - 195
143-181
134 - 204
143-181
6X4
8X5
220
268
UL LISTED & FM APPROVED PUMPS
SFP1000-30SM
3000
2900
154-194
98-172
154-194
98-172
8X5
8X5 275 Compliance to NFPA 20 Design &
3000 106-185 106-185 8X5 275
SFP1000-40SM
2900
3000
191 - 272
206 - 292
191 - 272
206 - 292
6x4
6x4
385 Installation Requirements.
SFP1000-12SH 1000 GPM 3500 146 - 264 146 - 264 8x5
362
3600 155 - 280 155 - 280 8x5
3500 152 - 205 152 - 205 8x5
SFP1000-15SH 300
3600 160 - 217 160 - 217 8x5
2900 163 - 278 163 - 278 8x5
SFP1000-36SM 375
3000 175 - 298 175 - 285 8x5
3500 187 - 289 187 - 289 6x4
SFP1000-EL31SH 377
3600 199 - 306 199 - 306 6x4
2900 137-177 137-177 8X5
SFP1250-29SM 268
3000 148-191 148-191 8X5
SFP1250-30SM
2900 94-170 94-170 8X5
275
1. All Pumps are Hydrostatically Tested to minimum of 150% of
3000 101-182 101-177 8X5
3500 207 - 264 207 - 264 8x5 its Maximum Working Pressure and canwith stand Double the
SFP1250-12SH 362
1250 GPM
3600
3500
219 - 279
150 - 205
219 - 279
150 - 205
8x5
8x6
Max. Working Pressure.
SFP1250-15SH 300
3600 159 - 217 159 - 217 8x6 2. All Pump have Clock-Wise Rotation when viewed from the
2900 155 - 278 155 - 278 8x5
SFP1250-36SM
3000 168 - 298 168 - 280 8x5
375
driver side.
SFP1250-EL31SH
3500
3600
178 - 287
190 - 304
178 - 287
190 - 296
6x4
6x4
377 3. All Pumps are horizontal Single Stage Pumps.
SFP1500-30SM
2900 88-167 88-167 8X5
239 4. “ The rated speed marked on the pump can vary within +/-4%
3000 95-179 95-174 8X5
SFP1500-15SH
3500 149 - 207 149 - 207 8x6
300
of the listed/approved rated speed example : 3000 RPM pump
3600 158 - 218 158 - 218 8x6
1500 GPM 2900 153 - 275 153 - 275 8x5 can be driven with 2900 RPM Drivers.”
SFP1500-36SM 375
3000 164 - 295 164 - 295 8x5
SFP2000-15SH 3500 145-203 145-203 8X6 300
2000 GPM
SFP2000-15SH 3600 154 - 215 154 - 215 8x6 300
© 2016. SFFECO FIRE PUMPS & SYSTEMS
06 CENTRIFUGAL FIRE PUMPS
VERTICAL TURBINE 50/60 Hz COMPLIANT EX26983
File No.FSP-2016-0370
listed/approved example :
1480 1450 © 2016. SFFECO FIRE PUMPS & SYSTEMS
07 SFFECO FIRE PUMP
SYSTEMS END SUCTION COMPLIANT
BARE SHAFT PUMPS MOTOR DRIVEN DETAILS DIESEL DRIVEN DETAILS JOCKEY PUMP
Flow APPROX SPEED Head Bar (PSI) Head Bar (PSI) POWER RANGE (HP) POWER RANGE (HP) Motor Rating (HP)
Model Dsg.
(GPM) (RPM) UL Listing FM APPROVED
File No.FSP-2016-0370
6.97 (101)
50 GPM
9.31 (135)
10.76 (156)
11
NOT POSSIBLE WITH DIESEL ENGINE
SFP 150-26 EH 3500 50-60 3-7.5
12 ARRANGEMENTS
13.17 (191)
7.03 (102)
7.17 (104) 7.17 (104)
7.5 7.5 NOT POSSIBLE WITH DIESEL ENGINE
SFP 150-20 EH 3500 25-30 3-7.5
8 8 ARRANGEMENTS
8.69 (126) 8.69 (126)
8.89 (129)
300 GPM 250 GPM 200 GPM
6.62 (96)
6.76 (98) 6.76 (98)
7 7 NOT POSSIBLE WITH DIESEL ENGINE
SFP 200-20 EH 3500 25-40 3-7.5
8 8 ARRANGEMENTS
8.28 (120) 8.28 (120)
8.55 (124)
7.93 (115) 7.93 (115)
SFP 200-65 EM 2900 9 9 30-40 30-57 2-5.5
9.38 (136) 9.38 (136)
7.72(112)
7.79 (113) 7.79 (113)
SFP 250-26 EM 2900 8 8 40-50 30-57 2-5.5
9 9
9.24 (134) 9.24 (134)
7.1 (103)
7.24(105) 7.24(105)
NOT POSSIBLE WITH DIESEL ENGINE
SFP 250-20 EH 3500 8 8 40-50 3-7.5
ARRANGEMENTS
8.55 (124) 8.55 (124)
8.62 (125)
7.45 (108)
7.59 (110) 7.59 (110)
SFP 300-26 EM 2900 8 8 40-50 30-57 2-5.5
8.97 (130) 8.97 (130)
9.1 (132)
6.97 (101)
7.03 (102) 7.03 (102)
NOT POSSIBLE WITH DIESEL ENGINE
SFP 300-20 EH 3500 7.5 7.5 40-50 3-7.5
ARRANGEMENTS
8 8
8.48 (123) 8.48 (123)
NOTES
TORNATEC CONTROLLERS
ELECTRIC MOTOR - GPx Series (Alternatively GPL for 30 HP and below)
DIESEL ENGINE - GPD © 2016. SFFECO FIRE PUMPS & SYSTEMS
JOCKEY PUMP - JP3
08 SFFECO FIRE PUMP
SYSTEMS END SUCTION COMPLIANT
BARE SHAFT PUMPS MOTOR DRIVEN DETAILS DIESEL DRIVEN DETAILS JOCKEY PUMP
Flow APPROX SPEED Head Bar (PSI) Head Bar (PSI) POWER RANGE (HP) POWER RANGE (HP) Motor Rating (HP)
Model Dsg.
(GPM) (RPM) UL Listing FM APPROVED
7.45 (108)
File No.FSP-2016-0370
7.59 (110) 7.59 (110)
SFP 400-26 EM 2900 8 8 50-75 57-71 2-5.5
8.5 8.5
9.17 (133) 9.17(133)
400 GPM
10.9 (158)
11.17 (162) 11.17 (162)
12 12
SFP 400-32 EM 2900 100-125 71-118 2-5.5
13 13
13.58 (197) 13.58 (197)
13.79 (200)
7.24 (105)
7.93 (115) 7.93 (115)
8 8
9 9
NOT POSSIBLE WITH DIESEL ENGINE
SFP 400-80 EH 3500 10 10 50-100 3-7.5
ARRANGEMENTS
11 11
12 12
13.31 (193) 13.31 (193)
13.45 (195)
7.24 (105)
7.52 (109) 7.52
SFP 450-26 EM 2900 8 8 60-75 57-71 2-5.5
8.5 8.5
9.1 (132) 9.1 (132)
No Available Engine on
450 GPM
10.62 (154)
10.96 (159) 10.96 (159)
11 11
SFP 450-32 EM 2900 12 12 100-125 118-128 3.-10
13 13
13..44(195) 13..44(195)
13.66 (198)
7.03 (102)
7.65 (111) 7.65 (111)
8 8
9 9
NOT POSSIBLE WITH DIESEL ENGINE
SFP 450-80 EH 3500 10 10 60-125 3-7.5
ARRANGEMENTS
11 11
12 12
13.1 (190) 13.1
13.45(195)
7.17(104)
7.45(108) 7.45(108)
SFP 500-26 EM 2900 60-75 57-71 2-5.5
8 8
9.03(131) 9(131)
6.83 (99) No Available Engine on
7.59(110) 7.59(110)
8 8
9 9
NOT POSSIBLE WITH DIESEL ENGINE
SFP 500-80 EH 3500 10 10 60-125 3-7.5
ARRANGEMENTS
11 11
12 12
12.97 (188) 12.97 (188)
13.38(194)
500 GPM
10.28 (149)
10.76(156) 10.76(156)
11 11
SFP 500-32 EM 2900 100-125 71-118 2-5.5
12 12
13 13
13.38 (194) 13.38(194)
7.66 (111)
7.79 (113) 7.79 (113)
SFP 500-12 EM 2900 8 8 75-100 71-118 2-5.5
9.17 (133)
9.59(139)
8.41 (122)
8.69(126) 8.69(126)
9 9
10 10
SFP 500-13 EM 2900 11 11 75-150 118-128 2-5.5
12 12
13 13
14.48 (210) 14.48 (210)
14.89 (216)
7.03 (102)
7.45(108) 7.45(108)
SFP 750-26 EM 2900 100-125 71-118 2-5.5
750 GPM
8 8
8.76 (127) 8.76 (127)
9.38 (136)
8.07 (117)
8.41 (122) 8.41
9 9
10 10
SFP 750-32 EM 2900 11 11 100-200 118-209 3.-10
12 12
13 13
14.28 (207) 14.27
14.76(214)
NOTES
TORNATEC CONTROLLERS
ELECTRIC MOTOR - GPx Series (Alternatively GPL for 30 HP and below)
DIESEL ENGINE - GPD © 2016. SFFECO FIRE PUMPS & SYSTEMS
JOCKEY PUMP - JP3
09 SFFECO FIRE PUMP
SYSTEMS SPLIT CASE File No.FSP-2016-0370
17.00 17.00
SFP150-SN31SH 3500 18.00 18.00 100-150 5.5-7.5
19.00 19.00
20.00 20.00
21.00 21.00
21.79 (316) 21.79 (316) NOT POSSIBLE WITH DIESEL
16.48 (239) 16.13 (234) ENGINE ARRANGEMENTS
17.00 17.00
18.00 18.00
SFP150-SN31SH 3600 19.00 19.00 100-150 5.5-7.5
20.00 20.00
21.00 21.00
22.00 22.00
23.03 (334) 22.55 (327)
6.96 (101) 6.96 (101)
8.00 8.00
SFP150-28SM 2900 9.00 9.00 40-60 57-71 2--4
10.00 10.00
10.76 (156) 10.76 (156)
7.45 (108) 7.45 (108)
8.00 8.00
SFP150-28SM 3000 9.00 9.00 40-75 57-71 2--4
10.00 10.00
11.00 11.00
11.51 (167) 11.51(167)
8.62 (125) 8.62 (125)
10.00 10.00
11.00 11.00
SFP150-35SM 2900 12.00 12.00 50-100 57-118 3--5.5
13.00 13.00
14.00 14.00
15.44 (224) 15.44 (224)
9.17 (133) 9.17 (133)
10.00 10.00
11.00 11.00
12.00 12.00
SFP150-35SM 3000 13.00 13.00 50-125 57-118 3--5.5
14.00 14.00
15.00 15.00
16.00 16.00
16.55 (240) 16.55 (240)
7.86 (114) 7.86 (114)
9.00 9.00
10.00 10.00
SFP200-25SH 3500 11.00 11.00 60-125 3--5.5
12.00 12.00
13.00 13.00
14.27 (207) 14.27 (207) NOT POSSIBLE WITH DIESEL
8.34 (121) 8.34 (121)
9.00 9.00 ENGINE ARRANGEMENTS
10.00 10.00
SFP200-25SH 3600 11.00 11.00 60-125 3--5.5
12.00 12.00
13.00 13.00
14.00 14.00
15.1 (219) 15.1 (219)
14.2 (206) 14.2 (206)
15.00 15.00
16.00 16.00
SFP200-40SM 2900 17.00 17.00 125-250 118-259 4--5.5
18.00 18.00
19.00 19.00
19.93 (289 ) 19.93 (289 )
15.17 (220) 15.17 (220)
16.00 16.00
17.00 17.00
SFP200-40SM 3000 18.00 18.00 150-250 128-259 4--5.5
19.00 19.00
20.00 20.00
21.3 (309) 21.3 (309)
15.58 (226) 15.58 (226)
16.00 16.00
200 GPM
17.00 17.00
SFP200-SN31SH 3500 18.00 18.00 100-150 5.5--7.5
19.00 19.00
20.00 20.00
21.00 21.00
21.86 (317) 21.86 (317) NOT POSSIBLE WITH DIESEL
16.48 (239) 16.13(234) ENGINE ARRANGEMENTS
17.00 17.00
18.00 18.00
SFP200-SN31SH 3600 19.00 19.00
20.00 20.00 100-200 5.5--7.5
21.00 21.00
22.00 22.00
23.1 (335) 22.68(329)
6.96 (101) 6.96 (101)
8.00 8.00
SFP200-28SM 2900 9.00 9.00 40-75 57-71 2--4
10.00 10.00
10.76 (156) 10.76 (156)
7.45 (108) 7.45 (108)
8.00 8.00
SFP200-28SM 3000 9.00 9.00 40-75 57-71 2--4
10.00 10.00
11.00 11.00
11.51 (167) 11.51 (167)
8.55 (124) 8.55 (124)
10.00 10.00
11.00 11.00
ELECTRIC MOTOR - GPx Series (Alternatively GPL for 30 HP and below)
10.00 10.00
SFP250-25SH 3600 11.00 11.00
12.00 12.00
75-125 3--5.5
TORNATEC CONTROLLERS
13.00 13.00
14.00 14.00
DIESEL ENGINE - GPD
19.00 19.00
19.86 (288) 19.86 (288)
15.17 (220) 15.17 (220)
16.00 16.00
17.00 17.00
SFP250-40SM 3000 18.00 18.00 150-250 128-259 4--5.5
19.00 19.00
20.00 20.00
21.24 (308) 21.24 (308)
10 SFFECO FIRE PUMP
SYSTEMS SPLIT CASE File No.FSP-2016-0370
14.21(206) 14.2(206)
15.00 15.00
16.00 16.00
SFP300-40SM 2900 17.00 17.00 150-250 128-259 4-5.5
18.00 18.00
19.00 19.00
19.72(286) 19.72(286)
15.17(220) 15.17(220)
16.00 16.00
17.00 17.00
SFP300-40SM 3000 18.00 18.00 150-250 186-259 4-5.5
19.00 19.00
20.00 20.00
21.17(307) 21.17(307)
15.58(226) 15.58(226)
16.00 16.00
17.00 17.00
SFP300-SN31SH 3500 18.00 18.00
19.00 19.00 100-200 5.5-7.5
20.00 20.00
21.00 21.00
21.79(316) 21.79(316) NOT POSSIBLE WITH DIESEL
16.48(239) 16.13(234) ENGINE ARRANGEMENTS
17.00 17.00
18.00 18.00
19.00 19.00
SFP300-SN31SH 3600 20.00 20.00 125-200 5.5-7.5
21.00 21.00
22.00 22.00
23.03(334) 22.61(328)
6.90(100) 6.89(100)
8.00 8.00
SFP300-28SM 2900 9.00 9.00 40-75 57-71 2--4
10.00 10.00
10.76(156) 10.76(156)
7.38(107) 7.38(107)
8.00 8.00
9.00 9.00
SFP300-28SM 3000 10.00 10.00 40-100 57-118 2--4
11.00 11.00
11.51(167) 11.51(167)
8.28(120) 8.27(120)
9.00 9.00
10.00 10.00
SFP400-35SM 2900 11.00 11.00
12.00 12.00 60-150 71-128 3-5.5
13.00 13.00
14.00 14.00
15.10(219) 15.10(219)
8.89(129) 8.89(129)
10.00 10.00
11.00 11.00
12.00 12.00
SFP400-35SM 3000 13.00 13.00 75-150 71-186 3-5.5
14.00 14.00
15.00 15.00
ELECTRIC MOTOR - GPx Series (Alternatively GPL for 30 HP and below)
16.13(234) 16.13(234)
6.76(98) 6.76(98)
7.00 7.00
SFP400-28SM 2900 8.00 8.00
9.00 9.00 50-100 57-118 2--3
10.00 10.00
10.69(155) 10.69(155)
© 2016. SFFECO FIRE PUMPS & SYSTEMS
7.24(105) 7.24(105)
400 GPM
8.00 8.00
9.00 9.00
SFP400-28SM 3000 10.00 10.00 60-100 57-118 2--4
11.00 11.00
11.45(166) 11.45(166)
7.86(114) 7.79(113)
9.00 9.00
10.00 10.00
SFP400-25SH 3500 11.00 11.00 75-125 3--5.5
12.00 12.00
13.00 13.00
14.2 (206) 14.2 (206) NOT POSSIBLE WITH DIESEL
8.27(120) 8.27(120)
9.00 9.00 ENGINE ARRANGEMENTS
10.00 10.00
SFP400-25SH 3600 11.00 11.00
75-150
TORNATEC CONTROLLERS
14.00 14.00
JOCKEY PUMP - JP3
15.03(218) 15.03(218)
14.2 (206) 14.2 (206)
15.00 15.00
16.00 16.00
SFP400-40SM 2900 17.00 17.00 150-250 186-259 4--5.5
NOTES
18.00 18.00
19.00 19.00
19.65(285) 19.65(285)
15.24(221) 15.24(221)
16.00 16.00
17.00 17.00
SFP400-40SM 3000 18.00 18.00 150-250 186-259 4--5.5
19.00 19.00
20.00 20.00
21.03(305) 21.03(305)
11 SFFECO FIRE PUMP
SYSTEMS SPLIT CASE File No.FSP-2016-0370
10.00 10.00
SFP500-25SH 3600 11.00 11.00 75-150 3--5.5
12.00 12.00
13.00 13.00
14.00 14.00
14.96(217) 14.96(217)
8.2 (119) 8.2 (119)
9.00 9.00
10.00 10.00
SFP500-32SM 2900 11.00 11.00 75-150 118-186 2-7.5
12.00 12.00
13.00 13.00
13.65(198) 13.65(198)
8.83(128) 8.83(128)
9.00 9.00
10.00 10.00
ELECTRIC MOTOR - GPx Series (Alternatively GPL for 30 HP and below)
21.00 21.00
21.51(312) 21.51(312) NOT POSSIBLE WITH DIESEL
DIESEL ENGINE - GPD
17.00 17.00
18.00 18.00
SFP500-SN31SH 3600 19.00 19.00 150-250 5.5--7.5
20.00 20.00
21.00 21.00
NOTES
22.00 22.00
22.76(330) 22.34(324)
12 SFFECO FIRE PUMP
SYSTEMS SPLIT CASE File No.FSP-2016-0370
14.00 14.00
15.00 15.00
SFP750-40SM 2900 16.00 16.00 200-300 186-259 7.5--10
17.00 17.00
18.00 18.00
19.37(281) 19.37(281)
14.75(214) 14.75(214)
15.00 15.00
16.00 16.00
SFP750-40SM 3000 17.00 17.00 200-300 209-300 7.5--10
18.00 18.00
19.00 19.00
20.00 20.00
20.75(301) 20.75(301)
15.03(218) 15.03(218)
16.00 16.00
17.00 17.00
SFP750-SN31SH 3500 18.00 18.00 200-250 5.5--10
19.00 19.00
20.00 20.00
21.3(309) 21.3(309) NOT POSSIBLE WITH DIESEL
15.93(231) 15.65(227)
17.00 17.00 ENGINE ARRANGEMENTS
18.00 18.00
SFP750-SN31SH 3600 19.00 19.00 200-300 5.5--10
20.00 20.00
21.00 21.00
22.00 22.00
22.55(327) 22.13(321)
10.21(148) 10.2(148)
11.00 11.00
12.00 12.00
13.00 13.00
SFP750-12SH 3500 14.00 14.00 150-300 5.5--15
15.00 15.00
16.00 16.00
17.00 17.00
18.34(266) 18.34(266) NOT POSSIBLE WITH DIESEL
10.82(157) 10.82(157) ENGINE ARRANGEMENTS
12.00 12.00
13.00 13.00
14.00 14.00
SFP750-12SH 3600 15.00 15.00 200-300 5.5--15
16.00 16.00
17.00 17.00
18.00 18.00
19.37(281) 19.37(281)
13.10(190) 13.10(190)
14.00 14.00
15.00 15.00
SFP750-EL31SH 3500 16.00 16.00 200-300 5.5--15
17.00 17.00
18.00 18.00
19.00 19.00
20.00(290) 20.00(290) NOT POSSIBLE WITH DIESEL
13.86(201) 13.52(196) ENGINE ARRANGEMENTS
15.00 15.00
16.00 16.00
SFP750-EL31SH 3600 17.00 17.00 200-300 5.5--15
18.00 18.00
19.00 19.00
20.00 20.00
21.10(306) 20.62(299)
9.24(134) 8.55(124)
10.00 10.00
SFP1000-31SM 2900 11.00 11.00 150-200 128-209 3--10
12.00 12.00
13.45(195) 13.10(190)
9.17(133)
10.00
SFP1000-31SM 3000 N/A 11.00 150-200 128-209 3--10
12.00
13.00
14.07(204)
9.86(143) 9.86(143)
SFP1000-29SM 2900 11.00 11.00 150-200 186 3--10
12.00 12.00
12.48(181) 12.48(181)
10.62(154) 10.62(154)
SFP1000-29SM 3000 11.00 11.00 200-250 186-209 3--10
12.00 12.00
13.38(194) 13.38(194)
6.76(98) 6.76(98)
8.00 8.00
SFP1000-30SM 2900 9.00 9.00 125-250 118-259 3-5.5
10.00 10.00
11.00 11.00
ELECTRIC MOTOR - GPx Series (Alternatively GPL for 30 HP and below)
11.86(172) 11.86(172)
7.31(106) 7.10(103)
8.00 8.00
9.00 9.00
SFP1000-30SM 3000 10.00 10.00 125-250 118-259 3-5.5
1000 GPM
11.00 11.00
12.00 12.00
12.76(185) 12.41(180)
13.17(191) 13.17(191)
© 2016. SFFECO FIRE PUMPS & SYSTEMS
14.00 14.00
15.00 15.00
SFP1000-40SM 2900 16.00 16.00 200-300 209-300 7.5--10
17.00 17.00
18.00 18.00
18.75(272) 18.75(272)
14.2(206) 14.2(206)
15.00 15.00
16.00 16.00
SFP1000-40SM 3000 17.00 17.00 200-350 209-350 7.5--10
18.00 18.00
19.00 19.00
20.13(292) 20.13(292)
10.07(146) 10.07(146)
11.00 11.00
12.00 12.00
13.00 13.00 NOT POSSIBLE WITH DIESEL
TORNATEC CONTROLLERS
17.00 17.00
JOCKEY PUMP - JP3
18.2(264) 18.2(264)
10.69(155) 10.69(155)
11.00 11.00
12.00 12.00
13.00 13.00
NOTES
12.07(175) 11.38(165)
13.00 13.00
14.00 14.00
15.00 15.00
SFP1000-36SM 3000 16.00 16.00 200-350 186-350 5.5--10
17.00 17.00
18.00 18.00
19.00 19.00
20.00 20.00
20.55(298) 19.31(280)
12.89(187) 12.89(187)
14.00 14.00
15.00 15.00
SFP1000-EL31SH 3500 16.00 16.00 200-350 7.5--15
17.00 17.00
18.00 18.00
19.00 19.00
19.93(289) 19.93(289) NOT POSSIBLE WITH DIESEL
13.72(199) 13.31(193) ENGINE ARRANGEMENTS
15.00 15.00
16.00 16.00
SFP1000-EL31SH 3600 17.00 17.00 250-350 7.5--15
18.00 18.00
19.00 19.00
20.00 20.00
21.10(306) 20.55(298)
9.45(137) 9.45(137)
SFP1250-29SM 2900 10.00 10.00 200-250 186-259 5.5-10
11.00 11.00
12.21(177) 12.2(177)
10.2(148) 10.2(148)
SFP1250-29SM 3000 11.00 11.00 200-250 186-259 5.5-10
12.00 12.00
13.17(191) 13.17(191)
6.48(94) 6.48(94)
7.00 7.00
8.00 8.00
SFP1250-30SM 2900 9.00 9.00 125-250 118-259 4-5.5
10.00 10.00
11.00 11.00
11.72(170) 11.72(170)
6.97(101) 6.76(98)
8.00 8.00
9.00 9.00
SFP1250-30SM 3000 10.00 10.00 125-250 118-259 4-5.5
11.00 11.00
12.00 12.00
12.55(182) 12.20(177)
14.27(207) 14.27(207)
15.00 15.00
SFP1250-12SH 3500 16.00 16.00 250-350 10--15
17.00 17.00
18.2(264) 18.2(264) NOT POSSIBLE WITH DIESEL
15.10(219) 15.10(219) ENGINE ARRANGEMENTS
16.00 16.00
SFP1250-12SH 3600 17.00 17.00 300-400 10--15
18.00 18.00
19.24(279) 19.24(279)
10.34(150) 10.34(150)
11.00 11.00
1250 GPM
11.00 11.00
12.34(179) 12.00(174)
10.28(149) 10.27(149)
11.00 11.00
1500 GPM
12.00 12.00
SFP1500-15SH 3600 13.00 13.00 300-450 7.5--10
14.00 14.00
15.03(218) 15.03(218)
10.55(153) 10.55(153)
11.00 11.00
12.00 12.00
13.00 13.00
SFP1500-36SM 2900 14.00 14.00 200-400 209-400 5.5--15
15.00 15.00
16.00 16.00
17.00 17.00
18.00 18.00
18.96(275) 18.96(275)
11.31(164) 10.62(154)
12.00 12.00
13.00 13.00
TORNATEC CONTROLLERS
14.00 14.00
15.00 15.00
SFP1500-36SM 3000 16.00 16.00
250-400 259-400 5.5--15
DIESEL ENGINE - GPD
17.00 17.00
JOCKEY PUMP - JP3
18.00 18.00
19.00 19.00
20.34(295) 19.10(277)
10.00(145) 10.00(145)
NOTES
11.00 11.00
SFP2000-15SH 3500 12.00 12.00 300-450 10--15
GPM
2000
DIESEL TANKS
All Sffeco Steel Aboveground Tanks for flammable and combustible Liquid are assembled and tested to all
requirements as follows
* ANSI/UL-142 – Compliant.
* Installation standard compliance to NFPA 30, NFPA 30A and NFPA 31
PRIMARY CONTAINMENT TANKS
1. Horizontal Cylindrical Construction (Capacity Upto 75000 Gallon)
2. Vertical Cylindrical Construction (Capacity Upto 60000 Gallon)
3. Rectangular Construction (Capacity Upto 550 Gallon)
All Fire Pump Controllers are factory assembled, wired, tested as a unit and
confirmed to all requirements of the latest edition of NFPA-20 (Centrifugal
Fire Pumps) and NFPA-70 (National Electrical Code). Controllers are listed
by Underwriters Laboratories, Inc., in accordance with UL218, Standard for
Fire Pump Controllers, CSA, and Standard for Industrial Control Equipment
(CUL) and approved by Factory Mutual (FM). All controllers are Y2K
compliant.
This component plays a vital role in fire pumps as it controls the entire
system. It is selected as per customer choice if any, otherwise it can be
either TORNATECH, FIRETROL, HUBBLE LEXINGTON OR JOSLYN CLARKE. © 2016. SFFECO FIRE PUMPS & SYSTEMS
15 FIRE PUMP SKIDS
DIESEL DRIVEN SKIDS
SFFECO is an established well reputed manufacturer of Premium Custom Engine Driven
Centrifugal Fire Pump Skids. We specialized in designing and developing packages in
compliance to NFPA 20 requirements with Listed & Approved Drivers.
SFFECO offers listed Centrifugal Fire Pump Skids that meet every fire protection need.
“
with Listed Diesel Engine Drivers
SFFECO maintains its standard with using it’s proudly own listed & approved Black Stallion Diesel
Engines and Centrifugal Fire Pumps to package Heavy Duty and High Quality Compact Skids.
Our Listed and Approved Fire Pumps can also be coupled with any other Listed Diesel Engine of
any specific brand as per customers requirement.
SFFECO offers listed Centrifugal Fire Pump Skids that meet every fire protection need.
“
Motors.
SFFECO maintains its standard with using it’s proudly own listed & approved WEG High Efficiency
Fire Pump Motors and Centrifugal Fire Pumps to package Heavy Duty and High Quality Compact
Skids.
Our Listed and Approved Fire Pumps can also be coupled with any other Listed Diesel Engine of
any specific brand as per customers requirement.
© 2016. SFFECO FIRE PUMPS & SYSTEMS
LEGEND OF
ACCESSORIES ACCESSORIES AND 17
ECCENTRIC REDUCER
CHECK VALVE
FLEXIBLE JOINT
ELBOW
TEE
-1 10
COMPOUND PRESSURE GAUGE
0 30
DISCHARGE PRESSURE GAUGE
FLOW METER
BUTTERFLY VALVE
GATE VALVE OS&Y CAN BE USED OPTIONAL
GATE VALVE
WASTE CONE
HOSE VALVE
ELECTRIC CONNECTION
PIPES
SENSING LINE
The Arrangement Drawing Shown Above is for Visual and Information Purposes only.
For detailed information regarding accessories please contact SFFECO Technical Team.
All Accessories used should be UL Listed/FM Approved as per NFPA 20.
© 2016. SFFECO FIRE PUMPS & SYSTEMS
File No.FSP-2016-0370