You are on page 1of 10

1740 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO.

4, OCTOBER 2018

Analysis of Current Control Interaction of Multiple


Parallel Grid-Connected Inverters
Francesco Cavazzana, Student Member, IEEE, Tommaso Caldognetto , Member, IEEE,
Paolo Mattavelli , Fellow, IEEE, Michele Corradin, and Igino Toigo

Abstract—The parallel connection of multiple electronic power


converters is typically used to connect renewable power sources
to the electricity grid, like often done, for example, in photovoltaic
farms. This interconnection of systems can be affected by instability
issues above the fundamental grid frequency, which has detrimen-
tal effects on power quality, protection effectiveness, and reliability.
This paper proposes an accurate multi-input multi-output method-
ology to stability analysis that allows us to highlight and analyze
all the relevant stability contributions linked to converters as well
as grid dynamics. The analytical study of a generic system repre-
sentation is first discussed to introduce the approach. Then, the
impedance multiplication effect, commonly applied when all the
parallel connected inverters are equal, is herein extended to
the case of converters with different parameters. The outcome of Fig. 1. Typical architecture of a large photovoltaic plant.
the study is an approach featuring both accurate stability analysis,
as in multi-input-multi-output-based approaches, and modularity,
as in impedance-based approaches. The results of the study are val- at inverters output [1] and, potentially, to instability issues [2],
idated by means of extensive simulation and experimental tests on [3] as the number of inverters increases.
an experimental setup composed of three 5-kVA parallel inverters. The stability of single inverters connected to the grid is widely
Index Terms—Multiparalleled grid-connected inverters, discussed in the literature. The effect of the different control as-
impedance, photovoltaic systems, power system harmonics, pects are specifically analyzed, for what concerns current control
renewable energy sources, stability analysis. parameters, disturbance rejection by grid voltage feedforward,
passive or active damping [4], [5]. The effect of grid synchro-
nization via phase-locked loops (PLLs) [6], [7] on inverter out-
I. INTRODUCTION
put impedance is also documented in the literature; in [8], [9] it
OWER generation from renewables is continuously in-
P creasing due to new connections to the grid of both small
scale distributed generators and medium to large scale renewable
is shown, in particular, a negligible effect of PLLs when looking
at dynamics above the grid frequency.
While the reported studies allow to design robust controllers
power plants. In the latter case renewable sources are typically for converters considered individually, when many inverters are
connected to a point of common coupling (PCC) with the grid connected in parallel additional interactions arise, which call for
by using a large number of relatively small converter modules, specific system-level stability analysis approaches that should
for scalability and reliability reasons. Fig. 1 shows the exam- feature i) accuracy, to take into account all the dynamics rele-
ple of a photovoltaic (PV) farm. In such system architectures vant to stability study, ii) scalability, to easily scale the modeling
the parallel connected converters interact among each other and and the analysis to systems having an arbitrary number of con-
with the grid bringing to increased harmonic current distortion verters, and iii) flexibility, to allow the description of systems
composed of converters of even different kinds (e.g., having
different parameters, line connections or power ratings). Rele-
Manuscript received May 23, 2017; revised October 30, 2017; accepted
February 22, 2018. Date of publication March 1, 2018; date of current ver- vant approaches have been recently proposed in [10]–[18]. The
sion September 18, 2018. Paper no. TSTE-00479-2017. (Corresponding author: method described in [10] approaches stability analysis by clas-
Tommaso Caldognetto.) sifying system poles as internal (i.e., those associated to the
F. Cavazzana and P. Mattavelli are with the Department of Manage-
ment and Engineering, University of Padova, 36100 Vicenza, Italy (e-mail: single inverters) and external (i.e., those due to the interaction
francesco.cavazzana@unipd.it; paolo.mattavelli@unipd.it). between the converters and the grid), therefore introducing two
T. Caldognetto is with the Interdepartmental Center Giorgio Levi Cases and kinds of stability, namely, internal (related to internal poles)
the Department of Management and Engineering, University of Padova, 36100
Vicenza, Italy (e-mail: tcaldognetto@gmail.com). and external (related to external poles). An equivalent inverter
M. Corradin and I. Toigo are with Socomec Sicon UPS Italia, 36033 Vicenza, model representing the parallel of n identical inverters is also
Italy (e-mail: michele.corradin@socomec.com; igino.toigo@socomec.com). proposed, giving an important result in terms of external stabil-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. ity, namely, that each inverter module perceives a higher applied
Digital Object Identifier 10.1109/TSTE.2018.2811505 impedance due to the presence of the other inverters connected
1949-3029 © 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1741

in parallel, effect herein referred to as impedance multiplica-


tion. In [11] a similar study is proposed, also introducing the
concepts of interactive current, associated with the interactions
between inverters, disregarding the grid impedance, and of com-
mon current, related to the interaction with the grid impedance;
the physical meaning of the internal poles is attributed to the
interactive current.
In [19] the interaction between the active impedances due
to the inverters and the passive impedances is discussed in the
case of a wind farm. Such interaction occurs also in PV farms,
as discussed in [12], [13], where the analysis of the sensitivity
of inverters current quality with respect to the value of grid
impedances due to parallel operation is presented.
The analysis in [10], [11] has the advantage of giving an accu-
rate description of the system, but becomes difficult to use when
the inverters are not equal and lacks in modularity, because the
addition of different inverters requires a reformulation of the
system description. On the other hand, impedance-based ap-
proaches [20]–[23] can overcome these disadvantages, as shown Fig. 2. The photovoltaic (PV) plant with n current-controlled inverters con-
nected in parallel. The grid voltage contribution is considered.
in [2], [24], [25], but do not give all the stability contributions,
notably, the internal stability is missing.
This paper aims at giving a stability study of a PV plant with grid sensitivity is also verified by simulation and experimental
parallel inverters, possibly having different parameters, consid- results. Section V concludes the paper.
ering also the grid contribution and combining both the com-
pleteness of the multi-input multi-output (MIMO) approaches II. THEORETICAL ANALYSIS
and the modularity of impedance-based analyses in a unifying A typical photovoltaic plant consists of parallel three-phase
framework. Moreover, the impedance multiplication effect oc- inverter modules. Assuming a symmetrical and balanced three-
curring in the equivalent inverter case [10] is revised with the phase system, it is possible to consider the equivalent single-
source/load impedance approach, which allows to focus specif- phase inverter [10]. Hence, the system under investigation in
ically on the external stability. An extension of this effect to the Fig. 2 describes a PV farm with n-paralleled grid-connected
case of parallel connected inverters with different parameters current-controlled inverters, where the PCC with voltage vP C C
is presented, allowing to evaluate the current loop gain and the is indicated. The grid is modeled as an equivalent Thèvenin
grid sensitivity considering the impedance perceived by the in- generator, where vg is the grid voltage and Zg = Rg + sLg is
verters, providing in this way a valuable tool for the design of the grid impedance.
inverter controllers. Finally, the equivalent inverter is also used In this paper the j-th inverter module (for j = 1, . . . , n) is
to analyze the influence of the grid voltage on the currents in- equipped with an internal current control where the error is pro-
jected by the PV inverters, herein referred to as grid sensitivity. cessed by a controller Gcj , which drives the digital pulse width
The proposed method is useful to analyze possible detrimental modulator (DPWM) Gdpw m j . By considering the linearized av-
effects on system stability arising when many converters, that erage model of a grid connected voltage source inverter [27],
are stable if taken singularly, are connected and operated in par- these contributions can be collected in the term:
allel. This is a matter of practical importance, for example, in
PV farms, for which the current trend is to implement power P Ij = Gcj · Gdpw m j · VD C (1)
plants in the range of megawatt by the parallel connection of a where the gain VD C (i.e., the bus voltage) results from the
large number of smaller inverter modules with power rating of average model of the inverter. The current references i1j r ef
tens of kilowatt. are given by phase-locked loops (PLLs), whose effect in the
The paper is organized as follows. Section II presents a frequency range that is herein of interest can be neglected; the
generic PV plant using the Norton equivalent generator and same holds for slow power systems dynamics [28]. The voltage
then combining the inverters in a MIMO system. Extending v0j imposed by each inverter leg is then filtered by the LCL-
[13], [26], the grid voltage effect on the inverters output cur- filter modeled by Z1j , Z2j , and Z3j , where:
rent is included in the analysis. The equivalent single inverter
is then described, applying the impedance multiplication effect Z1j = R1j + sL1j , Z2j = R2j + sL2j
also to the general case with parallel inverters with different pa-
Z3j = R3j + 1/ (sC3j ) (2)
rameters. Section III presents an example of application of the
described methodology to the case of inverters that are different Equivalently, each converter module can be represented by the
among each other. Section IV presents the simulation and the Norton equivalent circuit, namely, by an independent equivalent
experimental results for the stability analysis, where an external current generator isj with a parallel output impedance Zoj (for
instability is replicated in laboratory. Finally, the analysis on the j = 1, . . . , n) [26], as shown in Fig. 4(a), whose expressions are

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1742 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018

 
where Z1j,C L = Z1j · 1 + P Ij /Z1j is the closed loop
impedance.

B. Modeling of the Whole Plant


In Fig. 4(a), n-inverters modeled with the Norton equivalent
generator derived in Section II-A1 are connected in parallel.
The resulting system can be represented as a MIMO system, as
shown in Fig. 4(b). The block scheme is divided in two parts:
1) the first part consists of n single-input single-output
(SISO) systems combined together using all diagonal ma-
trices PI(s), GN (s), LN (s) and the resulting N(s);
2) the second part consists of two non-diagonal matrices
KN (s) and MN (s), which represent, respectively, the
output current contributions from the inverters and from
the grid.
Before going into the PV plant analysis, the most important
vectors (with dimension n × 1) are defined next:
1) i1nref = [i11r ef , . . . , i1n r ef ]T : inverters current refer-
ences;
Fig. 3. Inverter for the determination of the short-circuit current transfer func-
tion and the output impedance. (a) Electrical scheme. (b) Block scheme.
2) v0n = [v01 , . . . , v0n ]T : voltages impressed by inverters
bridges of switches;
3) i1n,s = [i11,s , . . . , i1n ,s ]T : controlled inverters currents in
derived in Section II-A. Finally, in Section II-B all the inverters
short-circuit condition;
are connected at the PCC, in order to analyze the stability of the
4) isn = [is1 , . . . , isn ]T : inverters output currents in short-
whole plant.
circuit condition;
5) ion = [io1 , . . . , ion ]T : inverters contributions to the out-
A. Equivalent Model of a Single Inverter
put currents;
Norton equivalent models of the parallel connected inverters 6) ion = [io1 , . . . , ion ]T : grid contributions to the output cur-
can be used for stability analysis. The short circuit current and rents;
the output impedance of the equivalent model of the generic 7) ion = [io1 , . . . , ion ]T : total output currents.
j-th inverter are derived as follows. All the matrices defined hereafter have dimension n × n.
1) Short-Circuit Current isj : Referring to Fig. 3(a), it is 1) Internal Stability: The matrix N(s) (see Fig. 4(b)) col-
possible to calculate the transfer function of the inverter short- lects all the terms to obtain the output short-circuit currents:
circuit current. To this end, let us determine the admittance GN j
from the voltage voj to the current on the inverter side inductance isn = TN (s) · LN (s) · i1nref = N(s) · i1nref (8)
i1j,s , when the output is short-circuited, and the current partition where the transfer function matrix TN (s) is given by
LN j from the inverter side inductance to the output:
TN (s) = [I + GN (s) · PI(s)]−1 · GN (s) · PI(s) (9)
i1j,s Z2j + Z3j
GN j = = (3)
voj Z1j · (Z2j + Z3j ) + Z2j · Z3j The terms of the matrices GN (s) = diag{GN 1 , . . . , GN n },
LN (s)=diag{LN 1 , . . . , LN n }, TN (s)=diag{TN 1 , . . . , TN n }
isj Z3j
LN j = = (4) and N(s) = diag{N1 , . . . , Nn } are defined in (3), (4), (5) and
i1j,s Z2j + Z3j
(6), respectively (for j = 1, . . . , n).
By referring to the block diagram in Fig. 3(b), the loop transfer It is worth observing that all the considered matrices are
function can be expressed as: diagonal: this stems from the fact that there is no coupling
P Ij · GN j between the inverters, due to the short-circuit condition. For
i1j,s
TN j = = (5) this reason the poles of TN (s) are related to the stability of the
i1j r ef 1 + P Ij · GN j
inverters considered individually [10] and are called internal
and the total transfer function from the reference current i1j r ef poles.
to the short-circuit output current isj is given by: 2) External Stability: The output currents are determined by
the contributions coming from all the inverters, through the ma-
isj P Ij · GN j
Nj = = · LN j (6) trix KN (s), and the grid voltage, through the matrix MN (s) (see
i1j r ef 1 + P Ij · GN j Fig. 4(b)). External stability concerns the interaction between
2) Output Impedance Zo : Similarly, by referring to Fig. 2, the parallel inverters and the grid [10], therefore, as shown in
the output impedance Zo can be expressed as: the following of this subsection, the corresponding poles to look
at for this stability analysis are common to all the inverters. In
Zoj = Z2j + Z1j,C L //Z3j (7) the general case of different inverters, the matrix KN (s) has all

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1743

Fig. 4. The photovoltaic (PV) plant with n current-controlled inverters connected in parallel modeled as Norton equivalent generators. The stability contributions
are highlighted and the grid voltage contribution in the output currents is considered. (a) Electrical scheme. (b) Block scheme.

where HN (s) = N(s) · KN (s) and

HN j j = Nj · KN j j , HN j k = Nj · KN j k (13)

for j = 1, . . . , n and k = 1, . . . , n and j = k.


The grid voltage contribution to the inverter output currents,
here called grid sensitivity, as in [5], according to Fig. 4(b) can
be determined as:

ion = MN (s) · vg (14)

where MN (s) = [MN 1 , . . . , MN n ]T is the vector for the grid


sensitivity transfer functions. The term MN j , for j = 1, . . . , n,
can be calculated according to Fig. 5(b) as:
Yoj
MN j = − n
Yo h . (15)
Fig. 5. Electrical scheme for the contribution calculation from (a) the inverters 1+ h=1
Yg
and (b) the grid.
The equivalence of the denominators in (11) and (15) can be
non-equal terms: noticed. In particular, the two matrices have the same poles, thus,
⎛ ⎞ as depicted in Fig. 4(b), the external stability can be equivalently
KN 11 KN 12 ··· KN 1n studied by looking at the poles of KN (s) or MN (s).
⎜ ⎟
⎜ KN 21 KN 22 · · · KN 2n ⎟ Finally, considering both the inverters and the grid voltage
⎜ ⎟
ion = ⎜ . .. .. .. ⎟ · isn (10) contributions, the total output currents can be calculated as:
⎜ .. . . . ⎟
⎝ ⎠
ion = ion + ion = HN (s) · i1nref + MN (s) · vg (16)
KN n 1 KN n 2 · · · KN n n


K N (s)
The poles of KN (s) and MN (s) are called external poles
and are related to the interaction between the inverters and the
where, by using the admittances Yoj = 1/Zoj and Yg = 1/Zg grid [10], [11] or equivalently to the impedance ratio [20], [21],
of the scheme in Fig. 5(a), it yields: [25], [29].
n When a new inverter is added to the system:
Yo h
1+ h=1 , h= j
Yg − YYogk 1) the short-circuit current stability contribution of the new
KN j j = n , KN j k = n (11)
1+ h=1 Yo h
1+ h=1 Yo h inverter N(s) is added as a new diagonal term;
Yg Yg
2) the terms in the matrices K(s) and M(s) change because
for j = 1, . . . , n and k = 1, . . . , n. Notably, the two terms have of the new impedance connected to the system, according
the same denominator and the stability is determined by the to (11) and (15), respectively.

impedance ratio nh=1 Yoh /Yg = Zg /(Zo1 // . . . //Zon ), as re- The main advantage of the modeling presented above, as
ported in Fig. 4(a) [20]. Hence, the output currents contributions compared to [10], is the possibility to accurately describe the
ion due to the inverters can be determined as: entire system by a modular approach, also in case of inverters
with different parameters connected in parallel. This analysis
ion = HN (s) · i1nref (12) can be applied also to other systems of parallel converters.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1744 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018

Fig. 6. Equivalent inverter for equal parallel inverters case. (a) Electrical
scheme. (b) Block scheme.

C. Equal Parallel Inverters


In case of equal inverters connected in parallel, all the short-
circuit currents, output impedances, and, consequently, ad-
mittances, are equal (i.e., is = isj , Zo = Zoj , Yo = Yoj , for Fig. 7. Application of the impedance multiplication effect for the different
parallel inverters case, inverter#1 as reference (Z o∗ = Z o 1 ). (a) Isolation of the
j = 1, . . . , n). In this particular condition, because of the equiv- difference contribution (Z x = Z x 2 // . . . //Z x n ). (b) Equivalent inverter with
alence between inverters, the terms (6) composing N(s) become the multiplied impedance.
all equal. The matrix KN (s) in (10) becomes symmetric, with
the diagonal and non-diagonal terms KN d and KN n d :
in (17) and MN in (18) for n = 1 and then substituting Zg with
Zo + (n − 1) · Zg Zg
KN d = , KN n d = − (17) n · Zg .
Zo + n · Zg Zo + n · Zg
Internal Poles Cancellation: As stated in [10], in this equiva-
Finally, the matrix MN (s) in (14) has all equal terms lent representation the internal stability poles disappear. By the
proposed approach the cancellation of these poles can be ana-
1 lytically proven. Indeed, in the following expression of HN eq :
MN = . (18)
Zo + n · Zg
The matrix HN (s) can be easily calculated. The resulting terms HN eq = Neq · KN eq
can be compared to the analysis in [10], adding an additional  
P I  · Z3
matrix to obtain the inverter output currents, as done in [26]: = · KN eq (19)
Z2 · Z3 + (P I  + Z1 ) · (Z2 + Z3 )
the two analyses give the same results. However, contrarily
to the analysis in [10], the main advantage of this approach
lies on the possibility of modeling the inverters independently the internal poles—given by the denominator of Neq —cancel
from each other and finally combine them in a comprehensive out with the numerator of KN eq . This derivation shows why
MIMO system. Moreover, this approach analyzes the internal impedance-based representations of the equivalent single in-
and external poles separating distinctly the two contributions verter case do not have any of these internal poles. These poles
(i.e., internal and external), as highlighted in Fig. 4(b). are those of the minimal realization of the system HN (s), which
cancel out also in case they are unstable (i.e., lying in the right-
D. The Impedance Multiplication Effect half plane) [30]. In case of equal multi-paralleled inverters,
where the internal poles affect the overall system stability, the
In this section, the impedance multiplication effect is applied term (n − 1) · Zg in the numerator of KN d in (17) is not null
for the case of equal and different parallel inverters. and the cancellation described above does not take place.
1) Equal Parallel Inverters: As discussed in [10], by con- 2) Different Parallel Inverters: It is possible to apply the
necting n-paralleled equal inverters to Zg , the impedance per- impedance multiplication effect in a general case following
ceived by each inverter is n · Zg . Hence, it is possible to establish these steps:
the stability conditions of n inverters in an equivalent single in- a) consider a generic j-th inverter (for j = 1, . . . , n) and its
verter system with the impedance multiplied by n, as depicted in output impedance as the reference impedance:
Fig. 6. This is true because the systems in Figs. 2 and 4(a) present
at the PCC the same impedance ratio n · Zg /Zo of the system
in Fig. 6. In Fig. 6(b) the terms GN eq , LN eq , TN eq , Neq in the Zo∗ = Zoj , Yo∗ = Yoj (20)
block scheme are equal to the terms in (3)–(6), respectively. The
remaining terms KN eq and MN eq can be evaluated from KN d In Fig. 7(a), j = 1 (i.e., Zo∗ = Zo1 ).

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1745

b) express all the other n − 1 inverters output impedances as TABLE I


TEST CASE PARAMETERS
Zok = Zo∗ //Zxk (or Yok = Yo∗ + Yxk ), thus:
Zo∗ · Zok
Zxk = , Yxk = Yok − Yo∗ (21) Parameter Symbol Value Unit
Zo∗ − Zok
Nominal power PN 5 kW
for k = 1, . . . , n and k = j. Nominal voltage VN 230 V
Base impedance ZB A S E 10.58 Ω
c) since the difference contributions Zxk are in parallel: Frequency PWM 1/T s w 12.5 kHz
⎛ ⎞−1 DC voltage VD C 400 V
 n
1 n Normalized L 1 j of (2) xL 1 0.047 p.u.
Zx = ⎝ ⎠ , Yx = Yxk Normalized L 2 j of (2) xL 2 0.002 p.u.
Zxk Normalized C 3 j of (2) xC 3 0.033 p.u.
k =1,k = j k =1,k = j
Proportional gain kP 1 , kP 2 0.028, 0.657 −
(22) Integral gain kI 1 , kI 2 43, 667 −

d) put the resulting Zx next to the grid impedance Zg : now


all the inverters have the same output impedance. The calculated as in (22) and the impedance multiplication effect
impedance multiplication effect can be applied to the new is applied, as in Fig. 7(b), which finally allows to evaluate the
grid impedance Z̃g , in Fig. 7(a): impedance ratio n Z̃g /Zo1 .
a) Case I: two equal parallel inverters are considered in a sta-
Z̃g = Zx //Zg , Ỹg = Yx + Yg . (23)
ble configuration. The impedances of the lines connecting the
With this process it is possible to evaluate the impedance inverters to the PCC are considered both equal to pure inductors
perceived by each inverter, due to parallelization, also in case of value 0.2 mH, while the capacitive behavior of the lines is
of unequal parallel inverters: the current loop gain and the grid negligible at the considered frequencies. The grid impedance
sensitivity can be evaluated as in the case of equal parallel Zg = Rg + sLg is, typically, determined mainly by the LV/HV
inverters substituting Z̃g to Zg . To be noticed that the short- transformer leakage inductance, referred to the LV side, here
circuit equivalent generators in Fig. 6(a) are different (i.e., the Lg = 3 mH and X/R = 8. The influence of this impedance is
internal poles are different). further emphasized because of the multiplication effect, espe-
cially in case of a large number of inverters, and so it is one
III. APPLICATION EXAMPLE of the most crucial parameters of the system. The admittance
(I)
defined in (22) is Yx = 0, because the control, the power rat-
The theoretical framework presented in Section II-D2 is now
ing, and the line impedances are equal. Hence, the impedance
applied to an example case composed of two different inverters (I)
connected to the PCC by means of interconnection impedances perceived by the first inverter is 2Z̃g = 2Zg as discussed in
(e.g., cable impedance). The interconnecting impedance for the Fig. 7(b) for n = 2. The reference impedance Zo1 and the per-
j-th inverter is indicated as ZC j and it can be easily taken into ceived impedance 2Zg can be observed in Fig. 8, where a stable
account by inclusion in the term Z2j in Fig. 2 and, therefore, intersection is achieved. This is confirmed by the plot of the
in the output impedance Zoj . The effect on system stability of impedance ratio displayed in Fig. 9(a), in which the critical
the interconnecting impedances and of different inverters power point −1 + j0 is not encircled.
ratings are analyzed, showing, in particular, the effectiveness b) Case II: inverter#2 is now connected through a distribution
(II) (II)
of the approach in highlighting how the impedance perceived line ten times longer: ZC 1 = 0.2 mH, ZC 2 = 2 mH, therefore,
(II)
by single inverters change due to parallelization. As shown, in- Zx = 0. The resulting impedance perceived by inverter#1
creasing inverter power ratings and impedances ZC j will create (II) (II)
is then 2Z̃g = 2(Zx //Zg ). As visible in Fig. 8, a low-
a resonance on the multiplied impedance, bringing the system frequency resonance intersecting the reference impedance ap-
to instability. pears. The correspondent impedance ratio is shown in Fig. 9(b),
Specifically, three configuration cases are considered: Case I which shows that the critical point is encircled in this configu-
refers to the basic case of equal parallel inverters, Case II con- ration.
siders the effect of connection impedance with different values, c) Case III: in this case inverter#2 is considered with a
Case III considers a different power rating for the second in- (III)
power rating five times bigger than in Case I: PN 2 = 5PN =
verter. To more clearly show the effectiveness of the developed (III)
25 kW. Because of this variation Zx = 0, and the perceived
analysis, a double PI controller in the form: (III) (III)
    impedance is 2Z̃g = 2(Zx //Zg ), which is reported in
kI 1 kI 2 Fig. 8. As in Case II, a resonance appears in the perceived
Gc (s) = kP 1 + · kP 2 + (24)
s s impedance, causing an unstable intersection with the reference
impedance. The resulting impedance ratio is shown in Fig. 9(c),
with a designed crossing frequency of fc = 700 Hz and a phase
where the instability point is encircled.
margin of φM = 40° is used for Gc in (1). For this example
of application, an analog implementation with Gdpw m = 1 is
IV. EXPERIMENTAL RESULTS
assumed. System parameters are listed in Table I.
In the following, the three cases are analyzed, taken inverter#1 This section presents the simulation and experimental re-
as reference converter, as in Fig. 7(a). Impedance Zx is then sults for stability and grid sensitivity analysis. The main

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1746 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018

Fig. 10. Configurations of the experimental setup (Z o V  Z g ). (a) Equiva-


lent inverter case. (b) Three paralleled inverters case.
Fig. 8. Bode diagram of the reference inverter impedance and of the perceived
grid impedance for impedance ratio analysis in Case I two equal parallel in-
verters, Case II equal inverter connected with different cable impedances, and
Case III inverters of different power ratings. System configuration like in Fig. 2 automatically generates grid sensitivity plots. A correspond-
with two inverters (i.e., n = 2). ing, accurate model of the system has been developed in Mat-
lab/Simulink and the obtained results compared with the theo-
retical analysis and the experimental measurements.
An external instability case is studied in the following subsec-
tions. At first, the open-loop gain TO L of the equivalent inverter
case in Fig. 10(a) is analyzed for different values of normalized
grid impedance, identifying those values that bring to instabil-
ity. The unstable case is then evaluated by comparing the results
obtained in the two configurations displayed in Fig. 10. Fi-
nally, the predicted from the theoretical modeling, the simulated,
Fig. 9. Nyquist plot of the impedance ratio in (a) Case I two equal parallel
inverters. (b) Case II equal inverter connected with different cable impedances. and the measured grid sensitivity for the equivalent inverter case
(c) Case III inverters of different power ratings. and the three inverters case are reported and discussed.

experimental setup parameters are reported in Table I. The setup A. Stability Analysis
consists of three single-phase inverters with LCL output filter The controller Gc adopted in this experimental validation
controlled by corresponding digital signal processors (DSPs) is the one referred to in Section III, with the same crossover
TI TMS320F2810. The controller described in the following frequency and phase margin. On the other hand, a symmetrical,
paragraph together with PWM and the synchronization block unitary amplitude, triangular carrier modulation is now used,
based on a PLL are implemented in the DSPs. Grid impedances which can be modeled as [27]:
Zg are implemented by real, ferrite core inductors with ade-
quate saturation current and size, so that their equivalent series Gdpw m j = e−sT s w /2 (25)
resistances are negligible with respect to the reactance values
around and above the grid frequency. The VCI is equipped with where Tsw is the switching period (see Table I). The current
additional external capacitances and with a properly designed open loop gain results:
voltage controller in order to reduce the output impedance ZoV 1
and reach the condition ZoV  Zg in the frequency range of TO L = P I  · ; (26)
Z1j + Z3j // (Z2j + (3Zg + ZoV ))
interest. The experimental waveforms of grid voltage and cur-
rent in case of instability (reported in Fig. 12) are acquired with P I  defined in (1) and Z1j , Z2j , and Z3j defined in (2).
by a Tektronics DPO 7054. The disturbances for grid sensi- The behavior of TO L for different values of xL (i.e., the nor-
tivity measurements are added to the reference of the VCI malized grid inductance Lg with respect to ZB A S E ) is displayed
and the resulting voltages and currents are measured with a in Fig. 11. By analyzing Fig. 11(a), it is possibile to notice that
sampling frequency of 100 kS/s for an observation window of the crossing frequency and the phase margin of TO L decrease
1 s. The post-processing is performed by a Matlab script that as the applied inductance increases.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1747

Fig. 12. Test case for the stability and the grid sensitivity analysis: three
CCI in parallel connected to the grid impedance and a VCI that emulates the
grid. Blue traces represent voltage v g , 30 V/div, red traces represent current ig
(3 A/div); and the time-scale is 50 ms/div. (a) Experimental results for the case
in Fig. 10(a). (b) Experimental results for the case in Fig. 10(b).

Fig. 11. Stability analysis. (a) Bode diagram of the current open loop gain
T O L given by (26). (b) Corresponding Nyquist diagram of the impedance ratio
according to the impedance-based approach.

For xL = 0.65 p.u., in correspondence to the TO L cross-


ing frequency the phase margin is negative and the system in
Fig. 10(a) becomes unstable; the corresponding time domain
waveforms obtained from experimental measurements are re-
ported in Fig. 12(a) (the described unstable control is activated
as reported in the figure), causing an unstable mode. The diver- Fig. 13. Frequency spectrum of the experimental results during instability
gence of the current stops because of the saturation of the double shown in Fig. 12(a) and (b).
PI controller and a waveform superimposed to the fundamen-
tal frequency appears on both current and voltage. The same
instability also occurs for xL = 0.22 p.u.  0.65 p.u./3 in the the equivalent inverter case, and 112 Hz, for the three inverters
case in Fig. 10(b), whose time domain waveforms are reported case, can be observed. The difference between the measured
in Fig. 12(b). Fig. 13 reports the spectrum of the measured cur- oscillating frequencies is due to the tolerances of the adopted
rent waveforms, where an oscillation frequency of 130 Hz, for real inductances used in the implementation of the setups.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1748 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018

to the impedance ratio of the considered circuit. The internal


poles are stable by design.
It is worth remarking that, although the values of xL seem
relatively high as compared to those of a typical weak grid (see,
e.g., [31], where a single grid-connected inverter is analyzed),
the values used in the test considered herein are realistic; indeed,
a very high number of parallel connected inverters causes a
particularly high perceived grid impedance.

B. Grid Sensitivity
The grid sensitivity is studied for different inductances and
considering the cases of i) three independent inverters and ii)
one corresponding equivalent inverter, to show the equivalence
described in Section II-D.
In Fig. 14 the analytical model is compared with simulation
and experimental results (except for the unstable case). The
obtained results show a good match between simulation and
experimental behaviors. Notably, Fig. 14(a) and (b) show that
by increasing the grid inductance the resonance associated with
the instability shown in Fig. 12 appears at lower frequencies
and with higher magnitudes. Indeed, the black curves show a
phase lead in the range of the resonance peak, which indicates
the presence of a couple of unstable poles.
The analysis of the grid sensitivity can be used to describe the
total harmonic distortion (THD) increase in [5], [12], applying
the analysis to the adopted control. The resonance frequencies
in Fig. 12(a) are close to the crossing frequencies of the current
loop gain and can cause an increase of the THD when the ap-
plied impedance changes, that is, when the number of parallel
inverters increases. As discussed in [13], a system which guar-
antees a good stability margin for all the crossing frequencies
considered has a lower variation in the THD.

V. CONCLUSION
This paper presents a complete modeling of a PV plant, with
n-parallel grid-connected inverters. It is shown that existing
MIMO approaches give all the stability contributions with a high
complexity analysis, while impedance-based approaches have
the advantage of being modular, but they do not comprehend
all the relevant stability contributions. The stability analysis
Fig. 14. Simulation and experimental sensitivity measures for different values presented in this work features: i) accuracy and ii) scalability,
of connected impedances, for the cases in Fig. 10(a) and (b). (a) Sensitivities
MN e q for the equivalent inverter case in Fig. 10(a). (b) Sensitivities MN of (18) as MIMO approaches, and iii) flexibility as the conventional
for the parallel inverters case in Fig. 10(b). impedance-based approach. Moreover, the presented analysis
provides a clear explanation and separation of the stability con-
tributions.
The xL values chosen for the unstable case guarantee the The impedance multiplication effect, which can be noticed in
same stability conditions in the two test cases depicted in the equivalent inverter, is extended to the case of different paral-
Fig. 10, where ZoV  Zg , and the impedance ratio is shown in lel inverters. The latter is analyzed through simulations results,
Fig. 11(b) for the equivalent inverter case. As can be noticed, where the detrimental effects of the parallelization of inverters
when the normalized inductance is xL = 0.65 p.u. the instabil- with a large line impedance or a large power rating are shown
ity point −1 + j · 0 is encircled by the curve, and the system from the perspective of the reference inverter. Moreover, an ex-
described becomes unstable as found from the current open loop ternal instability is presented and the grid sensitivity, namely,
gain considerations: this instability can be found from both the the influence of the grid voltage on the converter output current,
MIMO analysis in [10], [11] and the impedance-based analysis is analyzed in case of multiple equal parallel inverters. Simula-
[21]–[23]. This confirms that the external poles are related to the tion and experimental results are presented for both the stability
interactions between the inverters and the grid, or equivalently analysis and the grid sensitivity, using three parallel inverters

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1749

and the equivalent inverter. Both the analyses highlight the need [21] J. Sun, “Impedance-based stability criterion for grid-connected inverters,”
of a suitable controller design, in order to prevent instabilities, to IEEE Trans. Power Electron., vol. 26, no. 11, pp. 3075–3078, Nov. 2011.
[22] M. Cespedes and J. Sun, “Renewable energy systems instability involving
reduce the harmonic distortion and to improve the power quality grid-parallel inverters,” in Proc. IEEE Appl. Power Electron. Conf. Expo.,
of the distribution grid. 2009, pp. 1971–1977.
[23] J. Sun, “AC power electronic systems: Stability and power quality,” in
Proc. Workshop Control Model. Power Electron., 2008, pp. 1–10.
REFERENCES [24] T. Kato, K. Inoue, and H. Kawabata, “Stability analysis of a grid-connected
inverter system,” in Proc. IEEE Workshop Control Model. Power Electron.,
[1] J. H. R. Enslin et al., “Harmonic interaction between large numbers of
2012, pp. 1–5.
photovoltaic inverters and the distribution network,” in Proc. IEEE Power
[25] C. Yoon, H. Bai, X. Wang, C. L. Bak, and F. Blaabjerg, “Regional modeling
Tech Conf. Proc., 2003, vol. 3, pp. 1–6.
approach for analyzing harmonic stability in radial power electronics based
[2] C. Yoon, H. Bai, R. N. Beres, X. Wang, C. L. Bak, and F. Blaabjerg, “Har-
power system,” in Proc. IEEE Int. Symp. Power Electron. Distrib. Gener.
monic stability assessment for multiparalleled, grid-connected inverters,”
Syst., 2015, pp. 1–5.
IEEE Trans. Sustain. Energy, vol. 7, no. 4, pp. 1388–1397, Oct. 2016.
[26] F. Cavazzana, P. Mattavelli, M. Corradin, and I. Toigo, “On the stability
[3] F. Fuchs and A. Mertens, “Prediction and avoidance of grid-connected
analysis of multiple parallel inverters using the impedance multiplication
converter’s instability caused by wind park typical, load-varying grid
effect,” in Proc. IET Int. Conf. Power Electron., Mach. Drives, 2016,
resonance,” in Proc. IEEE Energy Convers. Congr. Expo., 2014,
pp. 1–6.
pp. 2633–2640.
[27] S. Buso and P. Mattavelli, Digital Control in Power Electronics, 2nd ed.
[4] J. Xu, S. Xie, and T. Tang, “Evaluations of current control in weak grid
San Rafael, CA, USA: Morgan & Claypool, 2015.
case for grid-connected LCL-filtered inverter,” IET Power Electron., vol. 6,
[28] J. Zhang and H. Xu, “Online identification of power system equivalent
no. 2, pp. 227–234, Feb. 2013.
inertia constant,” IEEE Trans. Ind. Electron., vol. 64, no. 10, pp. 8098–
[5] J. Wang, Y. Song, and A. Monti, “A study of feedforward control on
8107, Oct. 2017.
stability of grid-parallel inverter with various grid impedance,” in Proc.
[29] C. Yoon, X. Wang, C. L. Bak, and F. Blaabjerg, “Stabilization of mul-
IEEE Int. Symp. Power Electron. Distrib. Gener. Syst., 2014, pp. 1–8.
tiple unstable modes for small-scale inverter-based power systems with
[6] R. Teodorescu, M. Liserre, and P. Rodrı́guez, Grid Converters for Photo-
impedance-based stability analysis,” in Proc. IEEE Appl. Power Electron.
voltaic and Wind Power Systems. Hoboken, NJ, USA: Wiley, 2011.
Conf. Expo., 2015, pp. 1202–1208.
[7] A. Nagliero, R. Mastromauro, M. Liserre, and A. Dell’Aquila, “Moni-
[30] S. Skogestad and I. Postlethwaite, Multivariable Feedback Control: Anal-
toring and synchronization techniques for single-phase PV systems,” in
ysis and Design. Hoboken, NJ, USA: Wiley, 2005.
Proc. Int. Symp. Power Electron. Elect. Drives Autom. Motion, 2010,
[31] M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and
pp. 1404–1409.
wind turbine grid-connected inverters for a large set of grid impedance val-
[8] C. Zhang, X. Wang, F. Blaabjerg, W. Wang, and C. Liu, “The influence of
ues,” IEEE Trans. Power Electron., vol. 21, no. 1, pp. 263–272, Jan. 2006.
phase-locked loop on the stability of single-phase grid-connected inverter,”
in Proc. IEEE Energy Convers. Congr. Expo., 2015, pp. 4737–4744.
[9] D. Dong, B. Wen, D. Boroyevich, P. Mattavelli, and Y. Xue, “Analysis of
phase-locked loop low-frequency stability in three-phase grid-connected Francesco Cavazzana (S’15) received the M.S. degree in electronic engineering
power converters considering impedance interactions,” IEEE Trans. Ind. from the University of Padova, Vicenza, Italy, in 2014, where he is currently
Electron., vol. 62, no. 1, pp. 310–321, Jan. 2015. working toward the Ph.D. degree at the Graduate School in Mechatronics and
[10] J. Agorreta, M. Borrega, J. Lòpez, and L. Marroyo, “Modeling and control Product Innovations Engineering. In 2017, he was a Visiting Ph.D. Student with
of n-paralleled grid-connected inverters with LCL filter coupled due to grid the Center for Power Electronics Systems, Virginia Polytechnic Institute and
impedance in PV plants,” IEEE Trans. Power Electron., vol. 26, no. 3, State University, Blacksburg, VA, USA. His current research interests include
pp. 770–785, Mar. 2011. distributed generation, microgrids, and stability analysis.
[11] M. Lu, X. Wang, P. C. Loh, and F. Blaabjerg, “Interaction and aggregated
modeling of multiple paralleled inverters with LCL filter,” in Proc. IEEE
Energy Convers. Congr. Expo., 2015, pp. 1954–1959. Tommaso Caldognetto (S’10–M’16) received the Ph.D. degree in information
[12] W. Choi, W. Lee, and B. Sarlioglu, “Effect of grid inductance on grid engineering from the University of Padova, Vicenza, Italy, in 2016. In 2014,
current quality of parallel grid-connected inverter system with output LCL he was a Visiting Ph.D. student with the Institute for Automation of Complex
filter and closed-loop control,” in Proc. IEEE Appl. Power Electron. Conf. Power Systems, University of Aachen, Aachen, Germany. He is currently a
Expo., 2016, pp. 2679–2686. Postdoctoral Research Fellow with the University of Padova. His main research
[13] F. Cavazzana, P. Mattavelli, M. Corradin, and I. Toigo, “Grid sensitivity interests include control of grid-tied converters and distributed resources in
considerations on multiple parallel inverters systems,” in Proc. IEEE Int. microgrids.
Power Electron. Motion Control Conf., 2016, pp. 993–999.
[14] Y. Wang, X. Wang, F. Blaabjerg, and Z. Chen, “Harmonic resonance
assessment of multiple paralleled grid-connected inverters system,” in Paolo Mattavelli (S’95–A’96–M’00–SM’10–F’14) received the Ph.D. degree
Proc. IEEE 3rd Int. Future Energy Electron. Conf. ECCE Asia, Jun. 2017, in electrical engineering from the University of Padova, Vicenza, Italy, in 1995.
pp. 2070–2075. He had faculty positions with the University of Padova, the University of
[15] Y. Wang, X. Wang, F. Blaabjerg, and Z. Chen, “Frequency scanning-based Udine, and Virginia Tech. He is currently a Professor with the University of
stability analysis method for grid-connected inverter system,” in Proc. Padova. His major research interests include analysis, modeling, and control
IEEE 3rd Int. Future Energy Electron. Conf., Jun. 2017, pp. 1575–1580. of power converters, grid-connected converters for renewable energy systems,
[16] M. K. Bakhshizadeh, F. Blaabjerg, J. Hjerrild, X. Wang, L. Kocewiak, and microgrids.
and C. L. Bak, “A numerical matrix-based method for stability and power
quality studies based on harmonic transfer functions,” IEEE J. Emerg. Sel.
Topics Power Electron., vol. 5, no. 4, pp. 1542–1552, Dec. 2017. Michele Corradin received the Ph.D. degree from the University of Padova,
[17] M. Lu, X. Wang, P. C. Loh, and F. Blaabjerg, “Resonance interaction Vicenza, Italy, in 2005. He has been with the Socomec Sicon Group, Vicenza,
of multiparallel grid-connected inverters with LCL filter,” IEEE Trans. since 2005. From 2005 to 2013, he led the R&D Firmware Department. Since
Power Electron., vol. 32, no. 2, pp. 894–899, Feb. 2017. 2013, he has been an expert of the Socomec Power Conversion Division in
[18] J. Kwon, X. Wang, C. L. Bak, and F. Blaabjerg, “Harmonic interaction Digital Power Control. His major research interests include simulation and
analysis in grid connected converter using harmonic state space (HSS) control of power electronic converters.
modeling,” in Proc. IEEE Appl. Power Electron. Conf. Expo., Mar. 2015,
pp. 1779–1786.
[19] E. Ebrahimzadeh, F. Blaabjerg, X. Wang, and C. L. Bak, “Dynamic res- Igino Toigo received the M.S. degree in electrical engineering from the Uni-
onance sensitivity analysis in wind farms,” in Proc. IEEE 8th Int. Symp. versity of Padova, Vicenza, Italy, in 1986. He has been with the Socomec Sicon
Power Electron. Distrib. Gener. Syst., Apr. 2017, pp. 1–5. Group, Vicenza, since 1991. From 1991 to 2008, he led an R&D Division for the
[20] R. Middlebrook, “Input filter considerations in design and application of design of medium-power uninterruptible power systems, rectifiers, and power
switching regulators,” in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, 1976, stations for telecom applications. Since 2008, he has been a Senior R&D Engi-
pp. 366–382. neer with Socomec Sicon.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.

You might also like