Professional Documents
Culture Documents
4, OCTOBER 2018
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1741
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1742 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018
where Z1j,C L = Z1j · 1 + P Ij /Z1j is the closed loop
impedance.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1743
Fig. 4. The photovoltaic (PV) plant with n current-controlled inverters connected in parallel modeled as Norton equivalent generators. The stability contributions
are highlighted and the grid voltage contribution in the output currents is considered. (a) Electrical scheme. (b) Block scheme.
HN j j = Nj · KN j j , HN j k = Nj · KN j k (13)
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1744 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018
Fig. 6. Equivalent inverter for equal parallel inverters case. (a) Electrical
scheme. (b) Block scheme.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1745
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1746 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018
experimental setup parameters are reported in Table I. The setup A. Stability Analysis
consists of three single-phase inverters with LCL output filter The controller Gc adopted in this experimental validation
controlled by corresponding digital signal processors (DSPs) is the one referred to in Section III, with the same crossover
TI TMS320F2810. The controller described in the following frequency and phase margin. On the other hand, a symmetrical,
paragraph together with PWM and the synchronization block unitary amplitude, triangular carrier modulation is now used,
based on a PLL are implemented in the DSPs. Grid impedances which can be modeled as [27]:
Zg are implemented by real, ferrite core inductors with ade-
quate saturation current and size, so that their equivalent series Gdpw m j = e−sT s w /2 (25)
resistances are negligible with respect to the reactance values
around and above the grid frequency. The VCI is equipped with where Tsw is the switching period (see Table I). The current
additional external capacitances and with a properly designed open loop gain results:
voltage controller in order to reduce the output impedance ZoV 1
and reach the condition ZoV Zg in the frequency range of TO L = P I · ; (26)
Z1j + Z3j // (Z2j + (3Zg + ZoV ))
interest. The experimental waveforms of grid voltage and cur-
rent in case of instability (reported in Fig. 12) are acquired with P I defined in (1) and Z1j , Z2j , and Z3j defined in (2).
by a Tektronics DPO 7054. The disturbances for grid sensi- The behavior of TO L for different values of xL (i.e., the nor-
tivity measurements are added to the reference of the VCI malized grid inductance Lg with respect to ZB A S E ) is displayed
and the resulting voltages and currents are measured with a in Fig. 11. By analyzing Fig. 11(a), it is possibile to notice that
sampling frequency of 100 kS/s for an observation window of the crossing frequency and the phase margin of TO L decrease
1 s. The post-processing is performed by a Matlab script that as the applied inductance increases.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1747
Fig. 12. Test case for the stability and the grid sensitivity analysis: three
CCI in parallel connected to the grid impedance and a VCI that emulates the
grid. Blue traces represent voltage v g , 30 V/div, red traces represent current ig
(3 A/div); and the time-scale is 50 ms/div. (a) Experimental results for the case
in Fig. 10(a). (b) Experimental results for the case in Fig. 10(b).
Fig. 11. Stability analysis. (a) Bode diagram of the current open loop gain
T O L given by (26). (b) Corresponding Nyquist diagram of the impedance ratio
according to the impedance-based approach.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
1748 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 9, NO. 4, OCTOBER 2018
B. Grid Sensitivity
The grid sensitivity is studied for different inductances and
considering the cases of i) three independent inverters and ii)
one corresponding equivalent inverter, to show the equivalence
described in Section II-D.
In Fig. 14 the analytical model is compared with simulation
and experimental results (except for the unstable case). The
obtained results show a good match between simulation and
experimental behaviors. Notably, Fig. 14(a) and (b) show that
by increasing the grid inductance the resonance associated with
the instability shown in Fig. 12 appears at lower frequencies
and with higher magnitudes. Indeed, the black curves show a
phase lead in the range of the resonance peak, which indicates
the presence of a couple of unstable poles.
The analysis of the grid sensitivity can be used to describe the
total harmonic distortion (THD) increase in [5], [12], applying
the analysis to the adopted control. The resonance frequencies
in Fig. 12(a) are close to the crossing frequencies of the current
loop gain and can cause an increase of the THD when the ap-
plied impedance changes, that is, when the number of parallel
inverters increases. As discussed in [13], a system which guar-
antees a good stability margin for all the crossing frequencies
considered has a lower variation in the THD.
V. CONCLUSION
This paper presents a complete modeling of a PV plant, with
n-parallel grid-connected inverters. It is shown that existing
MIMO approaches give all the stability contributions with a high
complexity analysis, while impedance-based approaches have
the advantage of being modular, but they do not comprehend
all the relevant stability contributions. The stability analysis
Fig. 14. Simulation and experimental sensitivity measures for different values presented in this work features: i) accuracy and ii) scalability,
of connected impedances, for the cases in Fig. 10(a) and (b). (a) Sensitivities
MN e q for the equivalent inverter case in Fig. 10(a). (b) Sensitivities MN of (18) as MIMO approaches, and iii) flexibility as the conventional
for the parallel inverters case in Fig. 10(b). impedance-based approach. Moreover, the presented analysis
provides a clear explanation and separation of the stability con-
tributions.
The xL values chosen for the unstable case guarantee the The impedance multiplication effect, which can be noticed in
same stability conditions in the two test cases depicted in the equivalent inverter, is extended to the case of different paral-
Fig. 10, where ZoV Zg , and the impedance ratio is shown in lel inverters. The latter is analyzed through simulations results,
Fig. 11(b) for the equivalent inverter case. As can be noticed, where the detrimental effects of the parallelization of inverters
when the normalized inductance is xL = 0.65 p.u. the instabil- with a large line impedance or a large power rating are shown
ity point −1 + j · 0 is encircled by the curve, and the system from the perspective of the reference inverter. Moreover, an ex-
described becomes unstable as found from the current open loop ternal instability is presented and the grid sensitivity, namely,
gain considerations: this instability can be found from both the the influence of the grid voltage on the converter output current,
MIMO analysis in [10], [11] and the impedance-based analysis is analyzed in case of multiple equal parallel inverters. Simula-
[21]–[23]. This confirms that the external poles are related to the tion and experimental results are presented for both the stability
interactions between the inverters and the grid, or equivalently analysis and the grid sensitivity, using three parallel inverters
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.
CAVAZZANA et al.: ANALYSIS OF CURRENT CONTROL INTERACTION OF MULTIPLE PARALLEL GRID-CONNECTED INVERTERS 1749
and the equivalent inverter. Both the analyses highlight the need [21] J. Sun, “Impedance-based stability criterion for grid-connected inverters,”
of a suitable controller design, in order to prevent instabilities, to IEEE Trans. Power Electron., vol. 26, no. 11, pp. 3075–3078, Nov. 2011.
[22] M. Cespedes and J. Sun, “Renewable energy systems instability involving
reduce the harmonic distortion and to improve the power quality grid-parallel inverters,” in Proc. IEEE Appl. Power Electron. Conf. Expo.,
of the distribution grid. 2009, pp. 1971–1977.
[23] J. Sun, “AC power electronic systems: Stability and power quality,” in
Proc. Workshop Control Model. Power Electron., 2008, pp. 1–10.
REFERENCES [24] T. Kato, K. Inoue, and H. Kawabata, “Stability analysis of a grid-connected
inverter system,” in Proc. IEEE Workshop Control Model. Power Electron.,
[1] J. H. R. Enslin et al., “Harmonic interaction between large numbers of
2012, pp. 1–5.
photovoltaic inverters and the distribution network,” in Proc. IEEE Power
[25] C. Yoon, H. Bai, X. Wang, C. L. Bak, and F. Blaabjerg, “Regional modeling
Tech Conf. Proc., 2003, vol. 3, pp. 1–6.
approach for analyzing harmonic stability in radial power electronics based
[2] C. Yoon, H. Bai, R. N. Beres, X. Wang, C. L. Bak, and F. Blaabjerg, “Har-
power system,” in Proc. IEEE Int. Symp. Power Electron. Distrib. Gener.
monic stability assessment for multiparalleled, grid-connected inverters,”
Syst., 2015, pp. 1–5.
IEEE Trans. Sustain. Energy, vol. 7, no. 4, pp. 1388–1397, Oct. 2016.
[26] F. Cavazzana, P. Mattavelli, M. Corradin, and I. Toigo, “On the stability
[3] F. Fuchs and A. Mertens, “Prediction and avoidance of grid-connected
analysis of multiple parallel inverters using the impedance multiplication
converter’s instability caused by wind park typical, load-varying grid
effect,” in Proc. IET Int. Conf. Power Electron., Mach. Drives, 2016,
resonance,” in Proc. IEEE Energy Convers. Congr. Expo., 2014,
pp. 1–6.
pp. 2633–2640.
[27] S. Buso and P. Mattavelli, Digital Control in Power Electronics, 2nd ed.
[4] J. Xu, S. Xie, and T. Tang, “Evaluations of current control in weak grid
San Rafael, CA, USA: Morgan & Claypool, 2015.
case for grid-connected LCL-filtered inverter,” IET Power Electron., vol. 6,
[28] J. Zhang and H. Xu, “Online identification of power system equivalent
no. 2, pp. 227–234, Feb. 2013.
inertia constant,” IEEE Trans. Ind. Electron., vol. 64, no. 10, pp. 8098–
[5] J. Wang, Y. Song, and A. Monti, “A study of feedforward control on
8107, Oct. 2017.
stability of grid-parallel inverter with various grid impedance,” in Proc.
[29] C. Yoon, X. Wang, C. L. Bak, and F. Blaabjerg, “Stabilization of mul-
IEEE Int. Symp. Power Electron. Distrib. Gener. Syst., 2014, pp. 1–8.
tiple unstable modes for small-scale inverter-based power systems with
[6] R. Teodorescu, M. Liserre, and P. Rodrı́guez, Grid Converters for Photo-
impedance-based stability analysis,” in Proc. IEEE Appl. Power Electron.
voltaic and Wind Power Systems. Hoboken, NJ, USA: Wiley, 2011.
Conf. Expo., 2015, pp. 1202–1208.
[7] A. Nagliero, R. Mastromauro, M. Liserre, and A. Dell’Aquila, “Moni-
[30] S. Skogestad and I. Postlethwaite, Multivariable Feedback Control: Anal-
toring and synchronization techniques for single-phase PV systems,” in
ysis and Design. Hoboken, NJ, USA: Wiley, 2005.
Proc. Int. Symp. Power Electron. Elect. Drives Autom. Motion, 2010,
[31] M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and
pp. 1404–1409.
wind turbine grid-connected inverters for a large set of grid impedance val-
[8] C. Zhang, X. Wang, F. Blaabjerg, W. Wang, and C. Liu, “The influence of
ues,” IEEE Trans. Power Electron., vol. 21, no. 1, pp. 263–272, Jan. 2006.
phase-locked loop on the stability of single-phase grid-connected inverter,”
in Proc. IEEE Energy Convers. Congr. Expo., 2015, pp. 4737–4744.
[9] D. Dong, B. Wen, D. Boroyevich, P. Mattavelli, and Y. Xue, “Analysis of
phase-locked loop low-frequency stability in three-phase grid-connected Francesco Cavazzana (S’15) received the M.S. degree in electronic engineering
power converters considering impedance interactions,” IEEE Trans. Ind. from the University of Padova, Vicenza, Italy, in 2014, where he is currently
Electron., vol. 62, no. 1, pp. 310–321, Jan. 2015. working toward the Ph.D. degree at the Graduate School in Mechatronics and
[10] J. Agorreta, M. Borrega, J. Lòpez, and L. Marroyo, “Modeling and control Product Innovations Engineering. In 2017, he was a Visiting Ph.D. Student with
of n-paralleled grid-connected inverters with LCL filter coupled due to grid the Center for Power Electronics Systems, Virginia Polytechnic Institute and
impedance in PV plants,” IEEE Trans. Power Electron., vol. 26, no. 3, State University, Blacksburg, VA, USA. His current research interests include
pp. 770–785, Mar. 2011. distributed generation, microgrids, and stability analysis.
[11] M. Lu, X. Wang, P. C. Loh, and F. Blaabjerg, “Interaction and aggregated
modeling of multiple paralleled inverters with LCL filter,” in Proc. IEEE
Energy Convers. Congr. Expo., 2015, pp. 1954–1959. Tommaso Caldognetto (S’10–M’16) received the Ph.D. degree in information
[12] W. Choi, W. Lee, and B. Sarlioglu, “Effect of grid inductance on grid engineering from the University of Padova, Vicenza, Italy, in 2016. In 2014,
current quality of parallel grid-connected inverter system with output LCL he was a Visiting Ph.D. student with the Institute for Automation of Complex
filter and closed-loop control,” in Proc. IEEE Appl. Power Electron. Conf. Power Systems, University of Aachen, Aachen, Germany. He is currently a
Expo., 2016, pp. 2679–2686. Postdoctoral Research Fellow with the University of Padova. His main research
[13] F. Cavazzana, P. Mattavelli, M. Corradin, and I. Toigo, “Grid sensitivity interests include control of grid-tied converters and distributed resources in
considerations on multiple parallel inverters systems,” in Proc. IEEE Int. microgrids.
Power Electron. Motion Control Conf., 2016, pp. 993–999.
[14] Y. Wang, X. Wang, F. Blaabjerg, and Z. Chen, “Harmonic resonance
assessment of multiple paralleled grid-connected inverters system,” in Paolo Mattavelli (S’95–A’96–M’00–SM’10–F’14) received the Ph.D. degree
Proc. IEEE 3rd Int. Future Energy Electron. Conf. ECCE Asia, Jun. 2017, in electrical engineering from the University of Padova, Vicenza, Italy, in 1995.
pp. 2070–2075. He had faculty positions with the University of Padova, the University of
[15] Y. Wang, X. Wang, F. Blaabjerg, and Z. Chen, “Frequency scanning-based Udine, and Virginia Tech. He is currently a Professor with the University of
stability analysis method for grid-connected inverter system,” in Proc. Padova. His major research interests include analysis, modeling, and control
IEEE 3rd Int. Future Energy Electron. Conf., Jun. 2017, pp. 1575–1580. of power converters, grid-connected converters for renewable energy systems,
[16] M. K. Bakhshizadeh, F. Blaabjerg, J. Hjerrild, X. Wang, L. Kocewiak, and microgrids.
and C. L. Bak, “A numerical matrix-based method for stability and power
quality studies based on harmonic transfer functions,” IEEE J. Emerg. Sel.
Topics Power Electron., vol. 5, no. 4, pp. 1542–1552, Dec. 2017. Michele Corradin received the Ph.D. degree from the University of Padova,
[17] M. Lu, X. Wang, P. C. Loh, and F. Blaabjerg, “Resonance interaction Vicenza, Italy, in 2005. He has been with the Socomec Sicon Group, Vicenza,
of multiparallel grid-connected inverters with LCL filter,” IEEE Trans. since 2005. From 2005 to 2013, he led the R&D Firmware Department. Since
Power Electron., vol. 32, no. 2, pp. 894–899, Feb. 2017. 2013, he has been an expert of the Socomec Power Conversion Division in
[18] J. Kwon, X. Wang, C. L. Bak, and F. Blaabjerg, “Harmonic interaction Digital Power Control. His major research interests include simulation and
analysis in grid connected converter using harmonic state space (HSS) control of power electronic converters.
modeling,” in Proc. IEEE Appl. Power Electron. Conf. Expo., Mar. 2015,
pp. 1779–1786.
[19] E. Ebrahimzadeh, F. Blaabjerg, X. Wang, and C. L. Bak, “Dynamic res- Igino Toigo received the M.S. degree in electrical engineering from the Uni-
onance sensitivity analysis in wind farms,” in Proc. IEEE 8th Int. Symp. versity of Padova, Vicenza, Italy, in 1986. He has been with the Socomec Sicon
Power Electron. Distrib. Gener. Syst., Apr. 2017, pp. 1–5. Group, Vicenza, since 1991. From 1991 to 2008, he led an R&D Division for the
[20] R. Middlebrook, “Input filter considerations in design and application of design of medium-power uninterruptible power systems, rectifiers, and power
switching regulators,” in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, 1976, stations for telecom applications. Since 2008, he has been a Senior R&D Engi-
pp. 366–382. neer with Socomec Sicon.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO DE JANEIRO. Downloaded on March 31,2020 at 18:56:19 UTC from IEEE Xplore. Restrictions apply.