Professional Documents
Culture Documents
Abstract
The authors have carried out investigation of lightning tripout of 150 kV transmission lines in West Sumatra in Indonesia. The results of the
investigation in this paper show a positive correlation between the number of lightning tripouts on a 150 kV transmission line and the tower-footing
resistance, and also reveal that the main cause of the tripouts is back-flashover. Moreover, it turns out that the flashover at the lower arm increases
in case of high tower-footing resistance. The result of the investigation is in good agreement with the results of a simulation by the IEEE FLASH
program. As the result, it is recommended that the length of an arching horn, in the 150 kV line in West Sumatra, is 1.1 m. When the tower-footing
resistance at all towers is arranged to be 10 and the horn length is arranged 1.1 m, the critical current becomes about 80 kA. The tripout rate is
expected to be less than 15 tripout/ 100 km/ year.
2
Figure 5 shows the rate of lightning tripouts for tower-number Figure 7 shows the tripout rate dependent on the arm location.
groups before and after the improvement of tower-footing The high rate of lightning tripouts before the improvement of the
resistance. The location of the flashover resulting in tripouts was tower-footing resistance arises at the lower arm. After the
estimated by the fault locator. The highest rate of lightning tripouts improvement of tower-footing resistance, the high tripout rate
before and after the improvement of tower-footing resistance, being occurs at the upper arm. Since the location of the tripout is not
found at No. 1 to No. 17 towers, were 234 and 57 tripouts/100 influenced by the tower-footing resistance and depends on the
km/year, respectively. This is due to the geographical condition that struck phase in case of shielding failure, the main cause of the
these towers stand on the hill about 225 m above the sea level in the flashover is inferred to be the back-flashover.
north where thunderstorm activity is high as shown by the IKL in
Figure 1. Before the improvement of tower-footing resistance, the
highest tripout rate was found at No. 16 tower with the tower-
footing resistance of 35 and the average tower-footing resistance
at the towers experiencing lightning tripouts was 48 . After the
improvement of the tower-footing resistance, the high tripout rate
occurred at No. 47 tower with the tower-footing resistance of 15
and the average tower-footing resistance of the towers experiencing
lightning tripouts, was 11 . The tower-footing resistance at the
towers experiencing tripout is more than 1.5 times as high as the
average tower-footing resistance.
3
improvement of tower-footing resistance. Such a trend cannot be Figure 1. In this way, the ground flash density is calculated to be
found after the improvement of tower-footing resistance, in the 12.7 flashes/km2 /year.
resistance range from 4 to 15 .
Figure 9 shows tower-footing resistance and the arching horn
𝑁𝑔 = 0.04 𝑇𝐷1.25 ............................................................ (2)
length in case of damage of insulators due to lightning after the
improvement of tower-footing resistance. The insulator damages
occur at the towers with the horn longer than 1.4 m regardless of
where 𝑵𝒈 is the ground flash density (flashes/𝐤𝐦𝟐 /𝐲𝐞𝐚𝐫), 𝑻𝑫 is
the tower-footing resistance.
the thunderstorm days (days/year).
Lightning incidence to overhead lines was calculated to be 293
flashes/100 km/year through (3) (21)–(23).
𝑁𝑔
N𝑠 = (28ℎ𝑡0.6 + 𝑑𝑂𝐻𝐺𝑊 ) ............................................. (3)
10
1
P(I) = ................................................................. (4)
𝐼 2.6
1+( )
31
Fig. 9. Tower-footing resistance and arching horn length at
towers with insulator damage after improvement of tower-
where I is lightning current amplitude in units of kA, P is
footing resistance.
probability of occurrence of lightning current amplitude higher than
4. Analysis I.
.
The back-flashover rate BFR is given as the product of this
4.1 Method of Analysis The authors estimated the
probability and the number of strokes that terminate on the towers.
lightning tripout rate by the IEEE FLASH program (19) and by the
For simplicity, the number of strokes to the towers is assumed to be
analytical method (20) to study the tripout rate dependent on the
60% of all strokes to the overhead wires (23), (25).
location of phase conductors.
4.2 Line Model and Lightning Incidence to
BFR = 0.6 𝑁𝑠 𝑃(𝐼𝐶 ) ....................................................... (5)
Transmission Line A 47 km – long double-circuit line with the
span length of 333 m, simulating the line from No. 1 to No. 140
where 𝐼𝐶 is the critical current resulting in back-flashover (23).
towers, was selected to estimate the lightning performance of the
transmission line under study. The surge impedance of the towers 5. Results and Discussion
calculated by using (1) (20) is shown in Table 2. Regardless of the
5.1 Tripout Rates Figure 10 shows the comparison of
tower types, values of surge impedance are almost the same.
investigation results with the calculation by the analytical method
Table 2. Surge impedance dependent on tower types. in (20) and by the IEEE FLASH program version 1.81 (19) with the
Surge average tower-footing resistance before and after the improvement
Type of Tower Height Tower Base
Impedance of the tower-footing resistance at No. 1 to No. 140 towers of 33 and
Tower (ℎ𝑡 ) (m) (𝑟𝑇𝑜𝑤𝑒𝑟 ) (m)
(𝑍𝑡 ) () 5.6 , respectively. The tripout rates by the analytical method in
A 32.2 2.5 174
(20) or the IEEE Flash program is smaller than the investigated
result, and such a trend is significant after the improvement of the
B 31.7 2.7 169
tower-footing resistance. The calculated lightning tripout rate
C 31.7 2.7 169 dependent on flashover location by the analytical method is also
D 31.7 2.8 167 less than the investigated results before and after the improvement
of the tower-footing resistance.
Figure 11 shows the comparison of investigation results with
2(ℎ𝑡2 +(𝑟𝑇𝑜𝑤𝑒𝑟 )2 )
𝑍𝑡 = 30 𝑙𝑛 [ ] ............................................. (1) the calculation by the analytical method in (20) and by the IEEE
(𝑟𝑇𝑜𝑤𝑒𝑟)2
FLASH program with the average tower-footing resistance of
towers experiencing lightning resulting in tripouts.
where 𝑍𝑡 is the surge impedance of the tower (), ℎ𝑡 and
The average tower-footing resistance before and after the
𝑟𝑡𝑜𝑤𝑒𝑟 is the tower height and the tower base radius (m) in Figure 2,
respectively. improvement were 48 and 11 , respectively. The results of the
investigation are almost the same with the simulation results. These
The ground flash density is calculated from the IKL by (2) (21)-
(23). The No. 1 to No. 140 towers located in a high lightning activity results show that the overall performance of an entire transmission
line was influenced by the individual performance of the tower (22).
area. Therefore, the thunderstorm day is assumed 100 days/year
The calculated flashover rate dependent on the location reasonably
almost equal to the average values of the IKL at two sections in
4
agrees with investigated results in Figure 11. The tripout rate increases with the decrease of the horn length
and the increase of tower-footing resistance. When the tower-
footing resistance at all towers is reduced to 10 , as is regulated in
Japan, the tripout rate is expected to decrease from 29 tripouts/ 100
km/ year to 26 tripouts/ 100 km/ year.
Figure 13 shows the critical flashover voltage (CFO)
calculated by using the IEEE FLASH program for the horn length
from 0.9 – 1.3 m resulting in the flashover at the arching horn. The
flashover at the surface of the insulators occurs when the CFO
becomes equal to or higher than the insulation strength under
standard lightning impulse voltages (BIL).
From the result in Figure 13, it is recommended aching horn
length in the 150 kV Payakumbuh – Koto Panjang line is 1.1 m to
avoid the insulator damages. This result is supported by the result
in Figure 9 where insulator damages occurred at the arching horn
longer than 1.4 m regardless of tower-footing resistance. When the
Fig. 10. Rate of lightning tripouts calculated by using tower-footing resistance at all towers is arranged to be less than 10
average tower-footing resistance at No. 1 to No. 140
and the horn length is arranged 1.1 m, the tripouts rate is expected
towers. to be less than 15 tripout/ 100 km/ year, about half of the present
tripout rate.
Figure 14 shows that the critical current and the tripout rate
depend on tower-footing resistance calculated by using the
Fig. 12. Rate of tripouts depend on tower-footing analytical method (21) for the horn length of 1.1 m. The result shows
resistance and horn length. that when the tower-footing resistance at all towers is arranged to
be less than 10 , the critical current is about 80 kA, and the tripout
5
rate is expected to be less than 15 tripout/ 100 km/ year. (14) Y. Warmi and K. Michishita, “A Study on Lightning Outages on 150 kV
Transmission Line of Payakumbuh – Koto Panjang in West Sumatra in
6. Conclusion Indonesia,” in Proc. 19th ISH August 2015, number. 170.
(15) Subcommittee for transmission lines, Lightning protection design committee,
Based on the investigation of the 150 kV transmission line in “Guide to Lightning Protection Design for Transmission Line, ”CRIEPI
Report T-72 2002 (in Japanese).
West Sumatra in Indonesia, the following insights are obtained:
(16) Shozo Sekioka,“A Study on Lightning Surge with Special Reference to
1. The rate of lightning tripouts before and after the Multiphase Flashover,” Doctoral Thesis, Faculty of Engineering Doshisha
improvement of tower-footing resistance are 114 and 22 University, Japan, March, 1997.
tripouts/100 km/year, respectively. (17) K. Michishita, M. Ishii, A. Asakawa, S. Yokoyama, and K. Kami, “Voltage
induced on a test distribution line by negative winter lightning strokes to a
2. The rate of lightning tripouts at the lower arm increases tall structure,” IEEE Trans. Electromagn. Compat., vol. 45, no. 1, pp.135 –
with the increase of the tower-footing resistance. The high 140, February 2003.
rate of lightning tripouts before the improvement of the (18) W. A. Chisholm and W. Janischewskyj, “Lightning surge response of ground
electrodes,” IEEE Trans. Power Delivery, vol. 4, no. 2, pp.1329 – 1337, April
tower-footing resistance arises at the lower arm, with the
1989.
tower-footing resistance being more than 30 . After the (19) T. E. Mc Dermott, “Using IEEE Flash to estimate transmission and
improvement of tower-footing resistance, the high tripout distribution line lightning performance,” Proc. IEEE Power Eng. Soc.
rate occurs at the upper arm. Transm. Distrib. Conf., vol. 15236, pp. 8–9, May 2012.
(20) Anderson, J.G., ”Lightning Performance of Transmission Line,”
3. The result of the investigation in this paper reasonably Transmission Line References Book 345 and Above, California, 1982, pp.
agrees with the calculated results by using average tower- 545–597.
footing resistance of the towers experiencing lightning (21) IEEE Working group report Lightning Performance of Transmission Lines,
“IEEE Working Group Report – Estimating Lightning Performance of
tripouts. Transmission Line II – Updates to Analytical Models,” IEEE Trans. Power
4. The recommended arching horn length, in the 150 kV line Deliv., vol. PWRD-8, no. 3, pp. 1254 – 1267, July 1993.
in West Sumatra, is 1.1 m. When the tower-footing (22) IEEE Working group Estimating Lightning Performance of Transmission
Lines, “A simplified Method for Estimating Lightning Performance of
resistance at all towers is arranged to be less than 10 , and
Transmission Lines,” IEEE Trans. Power Appar. Syst., vol. PAS-104, pp.
the horn length is arranged 1.1 m, the critical current is less 919 – 932, July 1985.
than 80 kA, and the tripout rate is expected to decrease to (23) Hileman, A.R.,” Insulation co-ordination for Power System,”, Marcel
half of the present rate. Dekker Inc., New York, 1999.
(24) T. Udo, “Estimating of Shielding Failure and Mid-Span Back-flashover
Based on the Performance of EHV Double Circuit Transmission Lines,”
IEEE Trans. Power Deliv., vol. 12, no. 2, pp.832 – 836, 45, April 1997.
References (25) A. C. Report, “A Method of Estimating Lightning Performance of
Transmission Lines,” Trans. Am. Inst. Electr. Eng., vol. 69, no. 2, pp. 1187–
(1) Meteorological and Geophysical of Padang Panjang, “Annual report,”
1196, Jan 1950.
BMKG Padang Panjang, Indonesia, Dec. 2010.
(26) Z. G. Datsios, P. N. Mikropoulos, T. E. TSovilis, and S. I. Angelakidou,
(2) J. He, X. Wang, Z. Yu, and R. Zeng, “Statistical Analysis on Lightning
“Estimation of the Minimum Backflashover Current of Overhead Lines of
Performance of Transmission Lines in Several Regions of China,” IEEE
the Hellenic Transmission System through ATP – EMTP Simulations,”
Trans. Power Deliv., vol. 30, no. 3, pp. 1543–1551, 2014.
CRIEPI Report F-75008 2016.
(3) R. de la Rosa, G. Enriquez, and J. L. Bonilla, “Contributions to lightning
research for transmission line compaction,” IEEE Trans. Power Deliv., vol.
3, no. 2, pp. 716 – 723, Apr. 1988.
(4) A. H. A. Bakar, D. N. A. Talib, H. Mokhlis, and H. A. Illias, “Lightning back
flashover double circuit tripping pattern of 132 kV lines in Malaysia,” Int. J.
Electr. Power Energy Syst., vol. 45, no. 1, pp. 235–241, 2013.
(5) Subcommittee for transmission lines, study committee an lightning risk,
“Application Guide for Transmission Line Surge Arrester,” CRIEPI Report
H-07 2012 (in Japanese).
(6) IEEE Guide for Improving the Lightning Performance of Transmission
Lines, IEEE Std 1243-1997, pp. 1 – 44, Dec. 1997.
(7) F. M. Gatta, A. Geri, S. Lauria, M. Maccioni, and F. Palone, “Tower
Grounding Improvement vs. Line Surge Arresters: Comparison of Remedial
Measures for High-BFOR Subtransmission Lines,” IEEE Trans. Ind. Apl.,
vol. 51, no. 6, pp. 4952 – 4960, June 2015.
(8) S. Wu and W. Sun, “Back flashover protection performance analysis of
220kV double circuit transmission line,” in Proc. Asia-Pacific Conference
Power and Energy Engineering, (APPEEC), Wuhan, Cina, March 2011, pp.
1 – 4.
(9) A. Ametani and T. Kawamura, “A method of a lightning surge analysis
recommended in Japan using EMTP,” IEEE Trans. Power Deliv., vol. 20, no.
2, pp. 867–875, Apr. 2005.
(10) J. Sardi and M. Z. A. Ab Kadir, “Investigation on the effects of line
parameters to the lightning performance of 132 kV Kuala Krai-Gua Musang
transmission line,” in Proc. 7th International Symposium on Power
Engineering and Optimization, (PEOCO), Langkawi, Malaysia, June 2013,
pp. 594 – 599.
(11) E. F. KONCEL, “Potential of a Transmission-Line Tower Top When Struck
by Lightning,” Trans. Am. Inst. Electr. Eng., vol. 75, no. 3, pp. 457 – 462,
Jan. 1956.
(12) A. Holdyk and B. Gustavsen, “Inclusion of Field Solver-Based Tower
Footing Grounding Models in Electromagnetic Transients Programs,” IEEE
Trans. Ind. Apl., vol. 51, no. 6, pp. 5101 – 5106, 2015.
(13) The Distribution and Load Control Center Sumatra (Sumatra P3B), “monthly
report,” Sumatra P3B, Padang UPT, Indonesia, July 2013.