Professional Documents
Culture Documents
net/publication/272479568
CITATIONS READS
10 4,952
3 authors:
Ghada M. Amer
Benha University
94 PUBLICATIONS 359 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Enhancement of Power Systems Stability Considering Nuclear Power Plants View project
All content following this page was uploaded by Osama E. Gouda on 18 February 2015.
44
[4-5]
(3)
Fig. 4 High Frequency lumped RLC circuit simulates the grounding electrode.
(4)
Fig. 3 ATP Model of 500kV transmission line tower
B. Tower Footing Ground System where is permeability of the soil in henries per meter.
In order to simulate behavior of different tower footing
ground system during lightning transient, a vertical or C. Lightning strike
horizontal electrode is used at each leg of the transmission line The lightning stroke is modeled by a current source and a
tower and simulated by ATP program as shown in Fig. 3. A parallel resistance, which represents the lightning-path
simple lumped circuit high frequency mode suggested by impedance. Lightning-path impedance is selected as 400 Ω
Rudenberg [3-4] is illustrated in Fig. 4. For the vertical according to [7]. Figure 5 shows the lightning stroke model
electrode, according to Dwight [4-5], the resistance (in Ohms) that simulated by ATP program. Typical stroke impulse
is calculated as: current waveform is shown in Fig. 6.
(1)
45
expression for the insulator voltage withstands capability can t is elapsed time after lightning stroke, µs.
be calculated as [8]
(5) The back flashover mechanism of the insulators can be
represented by volt-time curves. When a back flashover might
occur, a parallel switch is applied. If the voltage across the
where insulator exceeds the insulator voltage withstand capability,
the back flashover occurs. The back flashover is simulated by
closing the parallel switch. Once the back flashover occurs,
the voltage across insulator goes down to zero.
TABLE I
CHARACTERISTICS OF 500 KV LINE CONDUCTORS A. Striking Distance
Conductor Radius X- Y- Rdc at In this section, a lightning stroke, of which a current is 20
number (mm) Coordinate Coordinate 20°C
(m) (m) (Ω/km) kA, hits one of the two ground wires (G1). Figure 8 shows the
A1 15.3 -13.425 22.13 0.0511 induced voltage wave forms on phase A, which is the nearest
A2 15.3 -12.975 22.13 0.0511 phase to stroke point, at various striking distances; d=0, 400,
A3 15.3 -13.2 21.74 0.0511
800, 1200, 1600 m (towers 1, 2, 3, 4 and 5). It is noticed that
B1 15.3 -0.225 24.48 0.0511
B2 15.3 0.225 24.48 0.0511 the induced voltage magnitude decreases with increasing
B3 15.3 0 24.09 0.0511 striking distance, and they almost have the same wave form.
C1 15.3 12.975 22.13 0.0511 Also it is noticed that there is a delay introduced in the
C2 15.3 13.425 22.13 0.0511
induced voltage waveforms. The time delay seen in the
C3 15.3 13.2 21.74 0.0511
G1 5.6 -8 30 0.564 induced voltage waveforms corresponds to the time taken for
G2 5.6 8 30 0.564 the electromagnetic field produced by the lightning current to
travel to the respective observation points.
Figure 9 shows the induced voltage wave forms on the three
46
phases A, B and C of tower 1. It is noticed that, due to Backflash voltages are generated by multiple reflections
asymmetry, the induced voltages are not the same in the three along the struck tower and also along the ground. The
phases, but it is highest at phase A as it is nearest to the backflash voltage across insulator for the struck tower is not a
lightning strike point (G1), and it is smallest at phase C as it is straightforward. The peak voltage will be directly proportional
farther to the lightning strike point. to the peak current as shown in Fig. 11. From Fig. 11 it is
noticed that the transient-voltage withstands level of the
1.5 insulator is not a unique number. The insulator withstands a
[MV] high transient voltage for a short duration and it withstands a
1.0 low transient voltage for relatively longer duration.
0.5 2.0
*10 6
1.6
0.0
1.2
-0.5
0.8
-1.0
0 5 10 15 20 [us] 25 0.4
(file Lightning.pl4; x-var t) v:TWR1A v:TWR2A v:TWR3A v:TWR4A v:TWR5A
0.5
C. Front Time of Lightning Stroke
Figure 13 compares induced voltage wave form on the top of
0.0
tower 1 with various front time of lightning strokes; 1.2, 4,
6µs, with magnitude 40 kA, as shown in Fig. 12. It is noticed
-0.5
that the shorter front wave time increases the induced voltage.
Figure 14 compares the time for clearing the overvoltage
-1.0
0 5 10 15 20 [us] 25 (backflash over) at insulator of tower1 with various front time
(file Lightning.pl4; x-var t) v:TWR1A v:TWR1B v:TWR1C of lightning strokes, also it is noticed that as the front wave
Fig. 9 Induced voltage at phase A for various striking distances
time increases the induced overvoltage decreases and in turn
the time to clear the overvoltage increases.
B. Peak of the Lightning Current
D. Tail Time of Lightning Stroke
Figure 10 shows the induced voltage wave forms on the top
of tower 1 with a various peaks of lightning current. It is Figure 16 compares induced voltage wave form on the top of
noticed that the magnitude of the induced voltage increases tower 1 with various tail time of lightning strokes; 20, 30, 40
with increasing the peak of the lightning current. µs, with magnitude 40 kA, as shown in Fig. 15. It is noticed
that the shorter tail wave time decreases the induced voltage.
3.0 Figure 17 compares the time for clearing the overvoltage
[MV]
2.5
(backflash over) at insulator of tower1 with various tail time
2.0
of lightning strokes, also it is noticed that as the tail wave time
1.5
increases the induced overvoltage increases and in turn the
time to clear the overvoltage decreases.
1.0
0.5
0.0
-0.5
-1.0
0 5 10 15 20 [us] 25
Lightning_V_Amp_40.pl4: v:GR1
lightning_v_amp_30.pl4: v:GR1
lightning_v_amp_20.pl4: v:GR1
lightning_v_amp_10.pl4: v:GR1
47
50 3.0
[kA] [MV]
2.5
40
2.0
1.5
30
1.0
20
0.5
0.0
10
-0.5
0 -1.0
0 5 10 15 20 [us] 25 0 5 10 15 20 [us] 25
Lightning_V_Front_6.pl4: c:XX0227-GR1 Lightning_V_Tail_20.pl4: v:GR2
lightning_v_front_4.pl4: c:XX0227-GR1 lightning_v_tail_30.pl4: v:GR2
lightning_v_front_1.2.pl4: c:XX0227-GR1 lightning_v_tail_40.pl4: v:GR2
Fig. 12 Lightning source wave shape with various front time Fig. 16 Induced voltage at top of tower 1 with various front time of lightning
3.5 current
[MV] 2.0
2.5 *10 6
1.6
1.5
0.5 1.2
-0.5 0.8
-1.5
0.4
-2.5
0 5 10 15 20 [us] 25
0.0
Lightning_V_Front_6.pl4: v:GR1 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 [us] 4.0
lightning_v_front_4.pl4: v:GR1 Lightning_V_Tail_20.pl4: m:U
lightning_v_front_1.2.pl4: v:GR1 lightning_v_tail_30.pl4: m:U
Fig. 13 Induced voltage at top of tower 1 with various front time of lightning lightning_v_tail_40.pl4: m:U
current Fig. 17Backflash over clearance at insulator of phase A with various front
time of lightning current
3.0
*10 6
2.5 E. Parameters of the Ground System
Vertical and horizontal electrodes which are used at each
2.0
leg of the transmission line tower as footing ground system
1.5 during lightning transient, have many parameters such as:
1.0
0.5
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 [us] 4.0
lightning_v_front_1.2.pl4: m:U
resistivity of the earth in ohm. meter, ; permittivity of the
lightning_v_front_4.pl4: m:U
lightning_v_front_6.pl4: m:U soil in farad per meter, ; permeability of the soil in henries
Fig. 14 Backflash over clearance at insulator of phase A with various front
time of lightning current per meter, ; electrode length in meter, ; electrode radius in
meter, ; depth of burial of horizontal electrode in meter, .
40
[kA] Among these parameters, the length of the electrode has the
35
major effect. Figures 18 and 19 show the induced voltage
30 wave forms on the top of tower 1 with a various lengths of
25 vertical and horizontal electrodes respectively. It is noticed
20 that the magnitude of the induced voltage increases with
15
increasing the length of vertical or horizontal electrode.
10
0
0 5 10 15 20 [us] 25
Lightning_V_Tail_20.pl4: c:XX0227-GR1
lightning_v_tail_30.pl4: c:XX0227-GR1
lightning_v_tail_40.pl4: c:XX0227-GR1
48
1.6 [3] Leonid Grcev, “Modeling of Grounding Electrodes under Lightning
[MV] Currents” IEEE Transaction on Electromagnetic Compatibility, Vol. 51,
1.2 No. 3, Aug. 2009, pp. 559-571.
[4] R. Rudenberg, Electrical Shock Waves in Power System. Cambridge,
0.8 MA: Harvard Univ. Press, 1968.
[5] H. B. Dwight, "Calculation of the resistances to ground", Electr. Eng.,
0.4
vol. 55, pp. 1319-1328, Dec. 1936.
[6] E. D. Sunde, “Earth Conduction Effects in Transmission Systems”, 2nd
0.0
ed. New York: Dover, 1968.
-0.4
[7] Ametani, A.; Kawamura, T., “A Method of a Lightning Surge Analysis
Recommended in Japan Using EMTP”, IEEE Trans. on Power Delivery,
-0.8 Vol. 20, No. 2, pp. 867-875, April 2005.
0 5 10 15 20 [us] 25 [8] P. Yadee and S. Premrudeepreechacharn, “Analysis of Tower Footing
lightning_v_l_30.pl4: v:GR1
Resistance Effected Back Flashover Across Insulator in a Transmission
lightning_v_l_5.pl4: v:GR1
lightning_v_l_3.pl4: v:GR1 System” the International Conference on Power Systems Transients
lightning_v_l_1.pl4: v:GR1 (IPST’07) in Lyon, France on June 4-7, 2007.
Fig.18 Induced voltage at top of tower 1 with various lengths vertical
electrode
1.6
[MV]
1.2
0.8
0.4
0.0
-0.4
-0.8
0 5 10 15 20 [us] 25
lightning_h_l_30.pl4: v:GR1
lightning_h_l_5.pl4: v:GR1
lightning_h_l_3.pl4: v:GR1
lightning_h_l_1.pl4: v:GR1
IV. CONCLUSION
REFERENCES
[1] P. Chowdhuri, “Parameters of lightning strokes and their effects on
power systems,” IEEE Transmission and Distribution Conference and
Exposition, Nov. 2001, pp. 1047-1051.
[2] J. A. Gutierrez R., P. Moreno, L. Guardado, L Naredo, “Comparison of
Transmission line models for Evaluating Lightning Performance” IEEE
Bologna Power Tech. Conference, June 23-26, Bologna, Italy 2003.
49
View publication stats