Professional Documents
Culture Documents
JunoNet - ModBus Interface
JunoNet - ModBus Interface
Version 2.0
Table of Contents
Index 0
I
ModBus Transmission Protocol for JunoNet
Only the Serial Port communication is supported, in both ASCII and RTU modes. Use the
Installation Menu on the Panel to select the mode and serial port settings required.
Using this function the user can get up to 6 variables from the Panel current status.
Below are represented all the available variables and its address.
The variables can be obtained from the panel one by one (requesting one coil at a time), or the six
variables at once.
Below is one example on how to get all the variables at once. In the example we used the Simply
Modbus because it shows what its traveling in the communication line.
Request Description:
Response Description:
In this example we got 0x11 for the Panel status. So coil 0 (fire status) and coil 4 (silence status)
are active.
That means that the panel is in alarm and the sounders have been silenced.
Using this function the user can get the type, condition and analogue value from any device
connected to the system.
Bellow are described the possible types and conditions.
Condition Meaning
000 No Alarm
001 Fault
010 Pre Alarm
011 Fire
100 Sensor Changed
101 Sensor Removed
110 Double Address
111 ---
Table.3 - Device Conditions.
In order to get the data from the correct device you need to follow the addressing rule:
Example:
If we want to read from Device 9 on Loop 7 the address is:
Loop calc.: (0x0100) + ((7 - 1) x (0x80)) = 0x400
Dev. calc.: 0x400 + (9 - 1) = 0x408
In the above example we are requesting the data from 10 devices starting on the 1st device of Loop
1.
Request Description:
Response Description:
Using this function the user can operate the panel using 3 different buttons.
Bellow are described available buttons.
Notes:
1. Accepts coil states 0xFF00 and 0x0000 for SET and RESET the Evacuation.
2. Accepts coil state 0xFF00 as OPERATE.
Request Description:
Response Description:
Using this function the user can operate on the Output (I/O units) of any address on the system.
To determine the Coil address you have to follow the same rule used in Device Information:
Example:
If we want to read from Device 9 on Loop 7 the address is:
Loop calc.: (0x0100) + ((7 - 1) x (0x80)) = 0x400
Dev. calc.: 0x400 + (9 - 1) = 0x408
Request Description:
Response Description:
Request Description:
Response Description:
II
ModBus Transmission Protocol for JunoNet
2 JunoNet Configuration
In order to enable the Modbus communication in the panel you have to go to Diagnostics mode:
1. De-energize the panel;
2. Press SYSTEM RESET button;
3. Apply power to the panel;
4. When “Diagnostics mode” shows in the display release the SYSTEM RESET button;
5. Press ESC and Enter your Installer password;
6. Go to Installation Menu;
7. Change the autom.: to MODBUS RTU(1);
8. Change the com speed: to 115200(1);
9. Change the mode: to 8N2(1);
10.Press ENTER 5 Times to Save the configuration;
11.Restart the panel;
12.Configure panel address (can be configured @ function (8-5-1)).
Note 1: You can choose the settings that best fit your needs.
III
ModBus Transmission Protocol for JunoNet
3 Hardware Interfaces
Four different interfacing technologies are available, namely:
· RS-232
· RS-485
· Fibre Optics
· TCP/IP
3.1.2 J-NET-ADV-COMS-FO
3.1.3 J-NET-ADV-COMS-TCP/IP
Configure the Network setting according to the local network, then press OK.