You are on page 1of 1

MIDAS/Civil RC Column Checking Result

Company Project Title


Author ACER File Name E:\...\PILAR EKSISTING.mcb

1. Design Condition
Design Code ACI318-02
Unit System kN, m
Member Number 9 (PM), 19 (Shear)
Material Data fc' = 30000, fy = 420000, fys = 420000 KPa

0.6
Column Height 1m
Section Property BP D0.6m (1) (No : 10)
Rebar Pattern Pos 1 Pos 2 Pos 3
Layer 1 12-D25 -- --
Total Rebar Area Ast = 0.0060804 m² (Rhost = 0.0215) 0.096

2. Applied Loads
Load Combination 18 AT (I) Point
Pu = -1626.4 kN, Mcy = 98.8615, Mcz = 76.6183, Mc = 125.076 kN-m

3. Axial Forces and Moments Capacity Check


Concentric Max. Axial Load phiPn-max = 4996.51 kN
Axial Load Ratio Pu/phiPn = -1626.4 / -1740.9 = 0.934 < 1.000 ....... O.K
Moment Ratio Mcy/phiMny = 98.8615 / 104.443 = 0.947 < 1.000 ....... O.K
Mcz/phiMnz = 76.6183 / 83.6895 = 0.916 < 1.000 ....... O.K
Mc/phiMn = 125.076 / 133.837 = 0.935 < 1.000 ....... O.K

4. P-M Interaction Diagram


P(kN)
10009

Theta=38.70Deg. phiPn(kN) phiMn(kN-m)


8674
N.A=37.78Deg.
6245.64 0.00
7340
4843.30 264.79
6005
3994.56 362.03
4997
4671
3256.96 412.10
3336 2649.36 435.96

2002
2145.97 446.50
1733.43 456.97
667
0 1434.41 474.19
-667 M(kN-m)
1083.59 484.03
-2002 (-1626,125)
(-1741,134) 565.97 484.42
-3336 -313.12 391.80
147

220

294

367

441

514

588

661

734
73

0 -1551.51 172.46
-2298.39 0.00

5. Shear Force Capacity Check


Applied Shear Strength Vu = 154.224 kN (Load Combination 17)
Shear Strength by Conc phiVc = 2.19114 kN
Shear Strength by Rebar phiVs = 255.427 kN (2.0-D13 @150)
Shear Ratio Vu/phiVn = 154.224 / 257.618 = 0.599 < 1.000 ....... O.K

Modeling, Integrated Design & Analysis Software Print Date/Time : 06/16/2021 11:32
http://www.MidasUser.com
MIDAS/Civil V 8.1.0

You might also like