Appendix B Communication|ScrEdit Software User Manual

LG Glofa GM6 CNET DELTA

A. HMI factory settings

Baud rate: 19200, 8, None, 1. (RS-232)

Controller station number: 0.

Control area/state area: %MW0 / %MW10.

NOTE

1) HMI default setting is predefined for CPU Port. If the user want to connect to CNET communication
module, the baud rate should be changed to 38400, 8, None, 1. (RS-422 / RS-485).

B. Definition of controller Read/Write address

Registers

Register Type Format Word No. Bit No. Data Size

w(word):0 ~ 3
Input Image IWb.s.w b(base): 0 ~ 1 Word
s(slot): 0 ~ 7
w(word):0 ~ 1
Input Image IDb.s.w b(base): 0 ~ 1 DWord
s(slot): 0 ~ 7
w(word):0 ~ 3
Output Image QWb.s.w b(base): 0 ~ 1 Word
s(slot): 0 ~ 7
w(word):0 ~ 1
Output Image QDb.s.w b(base): 0 ~ 1 DWord
s(slot): 0 ~ 7
Internal Memory MWn n: 0 ~ 4095 N/A Word
Internal Memory MDn n: 0 ~ 2047 N/A DWord

Contacts

Contact type Format Word No. Bit No.


n(bit): 0 ~ 63
Input Image IXb.s.n s(slot): 0 ~ 7
b(base): 0 ~ 1
n(bit): 0 ~ 63
Output Image QXb.s.n s(slot): 0 ~ 7
b(base): 0 ~ 1
Internal Memory MXn N/A n: 0 ~ 65535

B-48 Revision 05/30/2006, EH00


Appendix B Communication|ScrEdit Software User Manual

C. Connections (Connector Pinouts)

RS-232

via CPU Port

DOP Controller Controller


9 pin D-SUB male 9 pin D-SUB male 9 pin D-SUB male
(RS-232) (RS-232) (RS-232)

RXD (2) (7) TXD


TXD (3) (4) RXD
GND (5) (5) GND

Top View

RS-422

via G6L-CUEC CNET communication module

DOP Controller
9 pin D-SUB male (RS-422) Cable Connector (RS-422)

RXD+ (2) SDA


RXD- (1) SDB
TXD- (4) RDA
TXD+ (3) RDB
GND (5) SG

Revision 05/30/2006, EH00 B-49