Appendix B Communication|ScrEdit Software User Manual

Matsushita FP PLC DELTA

A. HMI factory settings

Baud rate: 9600, 8, ODD, 1.

Controller station number: 238.

Control area/state area: DT0 / DT10.

B. Definition of controller Read/Write address

Registers

Read/Write Range
Register Type Format Data length
Word No. Bit No.
Internal Relay WRn n: 0 ~ 886, N/A Word
Special Internal Relay 900 ~ 910
Link Relay WLn n: 0 ~ 639 N/A Word
External Input Relay WXn n: 0 ~ 511 N/A Word
External Output Relay WYn n: 0 ~ 511 N/A Word
Timer/Counter P.V. EVn n: 0 ~ 3071 N/A Word
Timer/Counter S.V. SVn n: 0 ~ 3071 N/A Word
Data Register DTn n: 0 ~ 32764 N/A Word
Link Data Register LDn n: 0 ~ 8447 N/A Word
File Register FLn n: 0 ~ 32764 N/A Word
Special Data Register DT9_n n: 0 ~ 511 N/A Word

¾ DT9_0 ~ DT9_511 are applicable for FP0 T32C, FP2, FP2SH, FP10SH controllers. (Special data
registers are all within the range of DT90000 ~ DT9XXXX).

¾ The actual transmitted address of DT9_n is 90000 + n (for DT). For example, the actual transmitted
address of DT9_1 is 90001 (for DT), the actual transmitted address of DT9_2 is 90002 (for DT) and vise
versa.

Contacts

Read/Write Range
Contact type Format
Word No. Bit No.
Internal Relay Rnb n: 0 ~ 886 b: 0 ~ f
Special Internal Relay n: 900 ~ 910 b: 0 ~ f
Link Relay Lnb n: 0 ~ 639 b: 0 ~ f
External Input Relay Xnb n: 0 ~ 511 b: 0 ~ f
External Output Relay Ynb n: 0 ~ 511 b: 0 ~ f
Timer Flag Contact Tn N/A n: 0 ~ 3071
Counter Flag Contact Cn N/A n: 0 ~ 3071

B-56 Revision 05/30/2006, EH00


Appendix B Communication|ScrEdit Software User Manual

¾ Increase the range of read / write address (for FP2SH / FP10SH controllers).

C. Connections (Connector Pinouts)

RS-232

DOP Series Controller Controller


9 pin D-SUB male 5 pin Mini DIN male 5 pin Mini DIN male
(RS-232) (RS-232 for FP0) (RS-232 for FP0)

RXD (2) (2) TXD

TXD (3) (3) RXD


GND (5) (1) SG

Top View

RS-232

DOP Series Controller Controller


9 pin D-SUB male 9 pin D-SUB male 9 pin D-SUB male
(RS-232) (RS-232 for FP1) (RS-232 for FP1)

RXD (2) (2) TXD

TXD (3) (3) RXD


GND (5) (7) GND
(4) RTS Top View

(5) CTS

Revision 05/30/2006, EH00 B-57