Medium and
High Voltage Cables
www.nktcables.com
Table of contents
Single core
Aluminium (Al) 1.9/3.3kV ...................................................................................................................... 4-7
Copper (Cu) 1.9/3.3kV .........................................................................................................................8-11
Aluminium (Al) 3.8/6.6kV ................................................................................................................... 12-15
Copper (Cu) 3.8/6.6kV ...................................................................................................................... 16-19
Aluminium (Al) 6.35/11kV ................................................................................................................. 20-23
Copper (Cu) 6.35/11kV ..................................................................................................................... 24-27
Aluminium (Al) 12.7/22kV ................................................................................................................. 28-31
Copper (Cu) 12.7/22kV ..................................................................................................................... 32-35
Aluminium (Al) 19/33kV .................................................................................................................... 36-39
Copper (Cu) 19/33kV ........................................................................................................................ 40-43
Three core
Aluminium (Al) 1.9/3.3kV .................................................................................................................. 44-47
Copper (Cu) 1.9/3.3kV ...................................................................................................................... 48-51
Aluminium (Al) 3.8/6.6kV .................................................................................................................. 52-55
Copper (Cu) 3.8/6.6kV ...................................................................................................................... 56-59
Aluminium (Al) 6.35/11kV ................................................................................................................. 60-63
Copper (Cu) 6.35/11kV ..................................................................................................................... 64-67
Aluminium (Al) 12.7/22kV ................................................................................................................. 68-71
Copper (Cu) 12.7/22kV ..................................................................................................................... 72-75
Aluminium (Al) 19/33kV .................................................................................................................... 76-79
Copper (Cu) 19/33 kV ....................................................................................................................... 80-83
Single core
Aluminium (Al) 38/66kV .................................................................................................................... 84-87
Copper (Cu) 38/66kV ........................................................................................................................ 88-91
Aluminium (Al) 76/132kV .................................................................................................................. 92-95
Copper (Cu) 76/132kV ...................................................................................................................... 96-99
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
1
Profile
We think in solutions.
And deliver to meet your needs…
nkt cables Australia is a 100% subsidiary of nkt cables and a supplier of MV & HV power cable, overhead catenary
systems for Rail, MV & HV cable accessories and installation services to the Australian and New Zealand Markets.
nkt cables Australia has been in operation since 2010. We have seen significant growth each year and we are earning an
excellent reputation through our hard work, dedication and innovative solutions.
We also manufacture cable accessories from 3.3kV up to 550kV. Our accessories are a superior design due to the fact that
we utilise silicon compounds. This makes nkt accessories easier to install and a minimal number of parts in comparison to
other types on the market. All accessories are manufactured according to EN 50180/81, DIN 47636 and successfully passed
type testing to CENELEC HD 629.1/VDE 0278 629-1.
nkt cables Australia stock a comprehensive range of premium quality cable accessories at our Brisbane warehouse. The
products have been widely used in the Australian / New Zealand market and are approved and used by many utilities and
major clients globally.
nkt cables Australia also offer the knowledge, experience and expertise of a qualified team of jointers who are available to
travel throughout Australia & New Zealand. They are licensed to carry out jointing work up to 420kV as well as oil cable
joints / maintenance. All tooling required to successfully complete installation on joints and terminations is ready and
available for projects and breakdowns. We hold major breakdown contracts and have 24 hour service agreements in place
on our client’s networks.
33kV – Supply and Installation - Nyngan Solar Farm 220kV – Full Turn Key - NAaN Project – Auckland
nkt cables
nkt cables is a global front-line supplier to the energy sector. We develop, manufacture and market high quality cables and
solutions for the electrical construction, railway and automotive industries. We supply creative and sustainable products,
services and solutions for our customers.
Our manufacturing plants are amongst the most modern, flexible and cost-effective in the world and we invest heavily to
keep them at the highest technological level. Neutral CO2 emissions have a high priority and also waste prevention in our
brand new state-of-the-art factory in Cologne.
Our main focus is to be at the forefront of innovative products and solutions whilst caring for our environment.
In 2015 nkt cables had 3,208 employees and a turnover of around 1.2 Billion Euro. nkt cables is owned by NKT Holding
A/S (www.nkt.dk), which is listed on the Danish Stock Exchange. NKT Holding owns a group of companies, which spans a
number of industries and has production facilities on four continents. In 2015 NKT Holding had 9,078 employees.
Read more at www.nktcables.com
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
2
nkt cables Ltd., Changzhou (NCL)
nkt cables Ltd., Changzhou (“NCL”) is a wholly-owned subsidiary of nkt cables Group with a registered
capital of RMB ¥628,800,000. Drawing on the advanced German industrial technology and scientific
management of its parent company, NCL utilizes these factors to the benefit of its customers. Our product range
covers three areas: XLPE insulated power cables at rated voltages of 3.3kV-110kV, accessories and electrifying
wire rod for railway contact networks. We also provide our customers with complete railway system solutions.
nkt cables Ltd., Changzhou Hejian Branch (“NCC”) is a branch company of nkt cables Ltd., Changzhou.
NCL acquired NCC in 2008 with the factory becoming fully operational in 2010. NCC possesses the most
advanced production lines and testing equipment for high voltage cables sourced from Finland, Germany,
Switzerland, France and Italy amongst others. This state of the art equipment is the foundation for high
quality manufacturing of cables.
NCC
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
3
Al 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
4
Al 1.9/3.3kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x500 26.0 2.2 32.4 70.2 1.5/1.6 44.7 3111 1119 671
1x630 29.7 2.4 36.5 70.2 1.5/1.6 48.8 3605 1221 733
1x800 34.0 2.6 41.2 70.2 1.5/1.6 53.6 4296 1340 804
1x1000 39.5 2.8 48.7 70.2 1.5/1.8 61.6 5442 1539 923
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
5
Al 1.9/3.3kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x25 110 130 100 105 75 110 110 105 95 100 95 85 2.37 6.9
1x35 135 160 120 130 90 135 135 130 115 115 115 100 3.31 6.9
1x50 160 190 150 160 110 160 160 155 135 140 135 125 4.73 6.9
1x70 205 240 185 200 135 195 195 190 165 165 165 150 6.62 6.9
1x95 245 290 230 245 165 230 230 225 195 195 195 185 8.99 6.9
1x120 285 330 265 280 190 260 255 255 220 215 220 210 11.4 10
1x150 320 370 300 320 220 290 285 285 245 240 250 235 14.2 10
1x185 365 420 340 365 250 325 315 325 275 265 280 270 17.5 10
1x240 430 490 405 435 290 370 360 375 315 300 325 310 22.7 10
1x300 490 550 465 495 330 415 395 420 350 335 365 350 28.4 10
1x400 570 625 540 580 390 465 440 480 395 370 415 410 37.8 10
1x500 655 715 635 680 450 525 485 545 445 410 470 470 47.3 10
1x630 745 800 730 780 510 580 535 615 490 445 525 530 59.6 10
1x800 845 890 835 895 605 640 580 685 540 485 585 615 75.7 10
1x1000 985 1005 995 1065 705 725 635 795 590 525 655 705 94.6 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
6
Al 1.9/3.3kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x25 1.20 1.54 1.54 0.141 0.158 0.201 9400 0.296 0.301 4.61 1.93 0.392 2.3 0.0676
1x35 0.868 1.11 1.11 0.136 0.154 0.197 8600 0.326 0.325 5.00 1.89 0.392 1.66 0.0623
1x50 0.641 0.821 0.821 0.131 0.149 0.194 7700 0.365 0.368 5.52 1.84 0.392 1.19 0.0591
1x70 0.443 0.568 0.568 0.124 0.141 0.183 6600 0.413 0.419 6.39 1.76 0.392 0.837 0.0572
1x95 0.320 0.410 0.410 0.116 0.132 0.179 5900 0.468 0.475 7.23 1.72 0.392 0.613 0.0525
1x120 0.253 0.325 0.325 0.110 0.125 0.173 5300 0.516 0.524 7.92 1.70 0.269 0.516 0.0505
1x150 0.206 0.265 0.264 0.108 0.121 0.170 5000 0.561 0.568 8.62 1.68 0.269 0.469 0.0480
1x185 0.164 0.211 0.211 0.104 0.119 0.164 4500 0.616 0.613 9.32 1.59 0.269 0.427 0.0445
1x240 0.125 0.161 0.161 0.101 0.118 0.161 4200 0.687 0.665 10.0 1.38 0.269 0.395 0.0420
1x300 0.100 0.130 0.129 0.0985 0.115 0.159 4000 0.757 0.690 10.3 1.28 0.269 0.370 0.0410
1x400 0.0778 0.102 0.101 0.0976 0.113 0.153 3700 0.844 0.726 11.0 1.26 0.269 0.348 0.0393
1x500 0.0605 0.0803 0.0791 0.0961 0.109 0.151 3200 0.884 0.778 11.6 1.22 0.269 0.331 0.0384
1x630 0.0469 0.0637 0.0620 0.0941 0.107 0.149 2800 0.911 0.853 13.1 1.21 0.269 0.318 0.0363
1x800 0.0367 0.0517 0.0495 0.0899 0.104 0.147 2300 0.954 0.947 14.3 1.20 0.269 0.307 0.0333
1x1000 0.0291 0.0392 0.0388 0.0865 0.103 0.141 2000 1.062 1.06 16.9 1.17 0.269 0.300 0.0332
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
7
Cu 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
8
Cu 1.9/3.3kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x500 26.0 2.2 32.4 70.2 1.5/1.6 44.7 6058 1119 671
1x630 29.7 2.4 36.5 70.2 1.5/1.6 48.8 7500 1221 733
1x800 34.0 2.6 41.2 70.2 1.5/1.6 53.6 9389 1340 804
1x1000 39.5 2.8 48.7 70.2 1.5/1.8 61.6 11650 1539 923
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
9
Cu 1.9/3.3kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x25 140 170 130 140 95 145 145 140 125 125 125 110 3.57 6.9
1x35 175 205 160 170 120 175 175 170 150 150 150 135 5.00 6.9
1x50 210 245 195 205 140 205 205 200 175 175 175 160 7.15 6.9
1x70 260 305 245 260 180 245 245 245 210 205 210 200 10.0 6.9
1x95 315 365 295 315 215 290 285 290 245 240 250 235 13.6 6.9
1x120 360 415 340 360 240 330 320 330 275 265 280 270 17.1 10
1x150 405 460 385 410 280 365 350 370 305 290 315 305 21.4 10
1x185 460 520 440 470 315 405 385 415 340 320 350 345 26.4 10
1x240 535 600 520 555 370 460 435 475 385 360 405 395 34.3 10
1x300 605 665 590 635 430 510 475 535 425 390 450 455 42.9 10
1x400 690 745 680 730 490 565 520 600 470 425 505 515 57.2 10
1x500 785 830 780 835 555 625 565 670 515 465 565 575 71.5 10
1x630 875 915 880 945 620 680 605 745 555 490 615 640 90.0 10
1x800 985 1015 1005 1075 725 740 650 820 615 535 690 730 114 10
1x1000 1145 1125 1205 1285 850 835 700 955 655 565 750 850 143 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
10
Cu 1.9/3.3kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x25 0.727 0.927 0.927 0.141 0.159 0.203 9200 0.296 0.301 4.61 1.93 0.392 1.47 0.0701
1x35 0.524 0.668 0.668 0.135 0.153 0.198 8500 0.326 0.325 5.00 1.89 0.392 1.05 0.0673
1x50 0.387 0.494 0.494 0.129 0.142 0.190 7600 0.365 0.368 5.52 1.84 0.392 0.758 0.0615
1x70 0.268 0.342 0.342 0.121 0.136 0.185 6500 0.413 0.419 6.39 1.76 0.392 0.533 0.0586
1x95 0.193 0.247 0.247 0.114 0.129 0.176 5900 0.468 0.475 7.23 1.72 0.392 0.459 0.0511
1x120 0.153 0.196 0.195 0.109 0.121 0.171 5300 0.516 0.524 7.92 1.70 0.269 0.416 0.0485
1x150 0.124 0.160 0.159 0.106 0.118 0.167 4800 0.561 0.568 8.62 1.68 0.269 0.388 0.0441
1x185 0.0991 0.128 0.127 0.103 0.115 0.163 4400 0.616 0.613 9.32 1.59 0.269 0.363 0.0401
1x240 0.0754 0.0982 0.0973 0.101 0.113 0.162 4000 0.687 0.665 10.0 1.38 0.269 0.341 0.0398
1x300 0.0601 0.0792 0.0781 0.0991 0.110 0.160 3900 0.757 0.690 10.3 1.28 0.269 0.330 0.0368
1x400 0.0470 0.0632 0.0618 0.0981 0.105 0.159 3600 0.844 0.726 11.0 1.26 0.269 0.318 0.0375
1x500 0.0366 0.0508 0.0489 0.0972 0.104 0.156 3500 0.884 0.778 11.6 1.22 0.269 0.307 0.0353
1x630 0.0283 0.0413 0.0390 0.0953 0.103 0.151 3200 0.911 0.853 13.1 1.21 0.269 0.299 0.0331
1x800 0.0221 0.0349 0.0318 0.0926 0.102 0.149 2700 0.954 0.947 14.3 1.20 0.269 0.294 0.0318
1x1000 0.0176 0.0248 0.0241 0.0897 0.100 0.142 2300 1.062 1.06 16.9 1.17 0.269 0.288 0.0306
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
11
Al 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
12
Al 3.8/6.6kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x25 6.0 2.5 12.4 47.2 1.5/1.6 25.5 1012 639 383
1x35 6.9 2.5 13.3 47.2 1.5/1.6 26.4 1063 661 397
1x50 8.1 2.5 14.5 47.2 1.5/1.6 27.6 1132 691 415
1x70 9.6 2.5 16.0 47.2 1.5/1.6 29.1 1232 729 437
1x95 11.3 2.5 17.7 47.2 1.5/1.6 30.8 1352 771 463
1x120 12.8 2.5 19.2 70.3 1.5/1.6 32.3 1677 809 485
1x150 14.2 2.5 20.6 70.3 1.5/1.6 33.7 1804 844 506
1x185 15.9 2.5 22.3 70.3 1.5/1.6 35.4 1960 886 532
1x240 18.1 2.6 24.7 70.3 1.5/1.6 37.8 2173 946 568
1x300 20.3 2.8 27.3 70.3 1.5/1.6 40.4 2427 1011 607
1x400 23.0 3.0 30.4 70.2 1.5/1.6 42.7 2756 1069 641
1x500 26.0 3.2 34.4 70.2 1.5/1.6 46.7 3218 1169 701
1x630 29.7 3.2 38.1 70.2 1.5/1.6 50.4 3696 1261 757
1x800 34.0 3.2 42.4 70.2 1.5/1.7 54.9 4373 1373 824
1x1000 39.5 3.2 49.5 70.2 1.5/1.8 62.4 5488 1559 935
1x1200 43.5 3.2 53.5 70.2 1.5/1.8 66.4 5642 1659 995
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
13
Al 3.8/6.6kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x25 115 135 105 110 79 115 115 110 100 105 100 90 2.37 6.9
1x35 140 165 125 135 95 140 140 135 120 120 120 105 3.31 6.9
1x50 165 195 155 165 115 165 165 160 140 145 140 130 4.73 6.9
1x70 210 245 190 205 140 200 200 195 170 170 170 155 6.62 6.9
1x95 250 295 235 250 170 235 235 230 200 200 200 190 8.99 6.9
1x120 290 335 270 285 195 265 260 260 225 220 225 215 11.4 10
1x150 325 375 305 325 225 295 290 290 250 245 255 240 14.2 10
1x185 370 425 345 370 255 330 320 330 280 270 285 275 17.5 10
1x240 435 495 410 440 295 375 365 380 320 305 330 315 22.7 10
1x300 495 555 470 500 335 420 400 425 355 340 370 355 28.4 10
1x400 575 630 545 585 395 470 445 485 400 375 420 415 37.8 10
1x500 660 720 640 685 455 530 490 550 450 415 475 475 47.3 10
1x630 750 805 735 785 515 585 540 620 495 450 530 535 59.6 10
1x800 850 895 840 900 610 645 585 690 545 490 590 620 75.7 10
1x1000 990 1010 1000 1070 710 730 640 800 595 530 660 710 94.6 10
1x1200 1080 1080 1100 1180 780 780 675 870 635 555 715 775 114 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
14
Al 3.8/6.6kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x25 1.20 1.54 1.54 0.147 0.162 0.208 9500 0.255 0.304 4.63 1.97 0.392 2.3 0.0785
1x35 0.868 1.11 1.11 0.138 0.153 0.199 8700 0.278 0.332 5.04 1.92 0.392 1.66 0.0709
1x50 0.641 0.821 0.821 0.135 0.150 0.196 7800 0.309 0.369 5.61 1.87 0.392 1.19 0.0676
1x70 0.443 0.568 0.568 0.124 0.140 0.185 6800 0.353 0.422 6.41 1.82 0.392 0.837 0.0591
1x95 0.320 0.410 0.410 0.118 0.133 0.179 6000 0.400 0.478 7.26 1.77 0.392 0.613 0.0543
1x120 0.253 0.325 0.325 0.114 0.129 0.175 5500 0.439 0.524 7.96 1.74 0.269 0.516 0.0512
1x150 0.206 0.265 0.264 0.110 0.126 0.171 5100 0.477 0.569 8.66 1.72 0.269 0.469 0.0485
1x185 0.164 0.211 0.211 0.108 0.123 0.168 4700 0.518 0.618 9.40 1.70 0.269 0.427 0.0461
1x240 0.125 0.161 0.161 0.104 0.119 0.165 4300 0.561 0.670 10.2 1.62 0.269 0.395 0.0437
1x300 0.100 0.130 0.129 0.102 0.118 0.163 4100 0.582 0.695 10.6 1.50 0.269 0.370 0.0427
1x400 0.0778 0.102 0.101 0.0989 0.114 0.160 3900 0.613 0.731 11.1 1.39 0.269 0.348 0.0395
1x500 0.0605 0.0803 0.0791 0.0963 0.112 0.157 3700 0.654 0.781 11.9 1.29 0.269 0.331 0.0379
1x630 0.0469 0.0637 0.0620 0.0938 0.109 0.155 3300 0.725 0.866 13.2 1.28 0.269 0.318 0.0358
1x800 0.0367 0.0517 0.0495 0.0909 0.106 0.152 2900 0.818 0.976 14.8 1.26 0.269 0.307 0.0343
1x1000 0.0291 0.0392 0.0388 0.089 0.104 0.150 2500 0.979 1.17 17.8 1.25 0.269 0.300 0.0332
1x1200 0.0247 0.0329 0.0323 0.0882 0.103 0.149 2300 1.06 1.26 19.2 1.24 0.269 0.295 0.0326
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
15
Cu 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
16
Cu 3.8/6.6kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x25 6.0 2.5 12.4 47.2 1.5/1.6 25.5 1166 639 383
1x35 6.9 2.5 13.3 47.2 1.5/1.6 26.4 1274 661 397
1x50 8.1 2.5 14.5 47.2 1.5/1.6 27.6 1419 691 415
1x70 9.6 2.5 16.0 47.2 1.5/1.6 29.1 1636 729 437
1x95 11.3 2.5 17.7 47.2 1.5/1.6 30.8 1912 771 463
1x120 12.8 2.5 19.2 70.3 1.5/1.6 32.3 2404 809 485
1x150 14.2 2.5 20.6 70.3 1.5/1.6 33.7 2682 844 506
1x185 15.9 2.5 22.3 70.3 1.5/1.6 35.4 3066 886 532
1x240 18.1 2.6 24.7 70.3 1.5/1.6 37.8 3617 946 568
1x300 20.3 2.8 27.3 70.3 1.5/1.6 40.4 4243 1011 607
1x400 23.0 3.0 30.4 70.2 1.5/1.6 42.7 5081 1069 641
1x500 26.0 3.2 34.4 70.2 1.5/1.6 46.7 6166 1169 701
1x630 29.7 3.2 38.1 70.2 1.5/1.6 50.4 7591 1261 757
1x800 34.0 3.2 42.4 70.2 1.5/1.7 54.9 9466 1373 824
1x1000 39.5 3.2 49.5 70.2 1.5/1.8 62.4 11697 1559 935
1x1200 43.5 3.2 53.5 70.2 1.5/1.8 66.4 11851 1659 995
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
17
Cu 3.8/6.6kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x25 145 175 135 145 100 150 150 145 130 130 130 115 3.57 6.9
1x35 180 210 165 175 125 180 180 175 155 155 155 140 5.00 6.9
1x50 215 250 200 210 145 210 210 205 180 180 180 165 7.15 6.9
1x70 265 310 250 265 185 250 250 250 215 210 215 205 10.0 6.9
1x95 320 370 300 320 220 295 290 295 250 245 255 240 13.6 6.9
1x120 365 420 345 365 245 335 325 335 280 270 285 275 17.1 10
1x150 410 465 390 415 285 370 355 375 310 295 320 310 21.4 10
1x185 470 525 445 475 320 410 390 420 345 325 355 350 26.4 10
1x240 545 605 525 560 375 465 440 480 390 365 410 400 34.3 10
1x300 615 670 595 640 435 515 480 540 430 395 455 460 42.9 10
1x400 700 750 685 735 495 570 525 605 475 430 510 520 57.2 10
1x500 790 835 785 840 560 630 570 675 520 470 570 580 71.5 10
1x630 880 920 885 950 625 685 610 750 560 495 620 645 90.0 10
1x800 990 1020 1010 1080 730 745 655 825 620 540 695 735 114 10
1x1000 1150 1130 1210 1290 855 840 705 960 660 570 755 855 143 10
1x1200 1230 1200 1320 1410 925 885 735 1030 700 595 810 920 171 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
18
Cu 3.8/6.6kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x25 0.727 0.927 0.927 0.147 0.162 0.207 9400 0.256 0.305 4.64 1.97 0.392 1.47 0.0771
1x35 0.524 0.668 0.668 0.141 0.156 0.202 8600 0.279 0.333 5.06 1.92 0.392 1.05 0.0733
1x50 0.387 0.494 0.494 0.134 0.150 0.195 7800 0.311 0.371 5.64 1.87 0.392 0.758 0.0678
1x70 0.268 0.342 0.342 0.129 0.144 0.190 6700 0.359 0.428 6.51 1.81 0.392 0.533 0.0632
1x95 0.193 0.247 0.247 0.120 0.135 0.181 6000 0.404 0.482 7.33 1.77 0.392 0.459 0.0550
1x120 0.153 0.196 0.195 0.113 0.128 0.174 5400 0.447 0.534 8.11 1.74 0.269 0.416 0.0505
1x150 0.124 0.160 0.159 0.110 0.125 0.171 5000 0.486 0.580 8.81 1.72 0.269 0.388 0.0480
1x185 0.0991 0.128 0.127 0.106 0.122 0.167 4500 0.533 0.636 9.67 1.69 0.269 0.363 0.0455
1x240 0.0754 0.0982 0.0973 0.103 0.118 0.164 4200 0.578 0.690 10.5 1.61 0.269 0.341 0.0420
1x300 0.0601 0.0792 0.0781 0.101 0.117 0.162 4000 0.601 0.718 10.9 1.49 0.269 0.330 0.0410
1x400 0.0470 0.0632 0.0618 0.0987 0.114 0.160 3800 0.636 0.759 11.5 1.38 0.269 0.318 0.0396
1x500 0.0366 0.0508 0.0489 0.0968 0.112 0.158 3600 0.662 0.790 12.0 1.29 0.269 0.307 0.0384
1x630 0.0283 0.0413 0.0390 0.0943 0.110 0.155 3300 0.733 0.875 13.3 1.28 0.269 0.299 0.0363
1x800 0.0221 0.0349 0.0318 0.0896 0.105 0.151 2800 0.862 1.03 15.6 1.26 0.269 0.294 0.0333
1x1000 0.0176 0.0248 0.0241 0.0890 0.104 0.150 2500 0.979 1.17 17.8 1.25 0.269 0.288 0.0332
1x1200 0.0151 0.0210 0.0202 0.0882 0.103 0.149 2300 1.06 1.26 19.2 1.24 0.269 0.285 0.0326
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
19
Al 6.35/11kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
20
Al 6.35/11kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x25 6.0 3.4 14.2 47.2 1.5/1.6 27.3 1082 684 410
1x35 6.9 3.4 15.1 47.2 1.5/1.6 28.2 1136 706 424
1x50 8.1 3.4 16.3 47.2 1.5/1.6 29.4 1207 736 442
1x70 9.6 3.4 17.8 47.2 1.5/1.6 30.9 1311 774 464
1x95 11.3 3.4 19.5 70.3 1.5/1.6 32.6 1653 816 490
1x120 12.8 3.4 21.0 70.3 1.5/1.6 34.1 1764 854 512
1x150 14.2 3.4 22.4 70.3 1.5/1.6 35.5 1896 889 533
1x185 15.9 3.4 24.1 70.3 1.5/1.6 37.2 2056 931 559
1x240 18.1 3.4 26.3 70.3 1.5/1.6 39.4 2264 986 592
1x300 20.3 3.4 28.5 70.2 1.5/1.6 40.8 2487 1021 613
1x400 23.0 3.4 31.2 70.2 1.5/1.6 43.5 2807 1089 653
1x500 26.0 3.4 34.8 70.2 1.5/1.6 47.1 3246 1179 707
1x630 29.7 3.4 38.5 70.2 1.5/1.6 50.8 3726 1271 763
1x800 34.0 3.4 42.8 70.2 1.5/1.7 55.3 4406 1383 830
1x1000 39.5 3.4 49.9 70.2 1.5/1.8 62.8 5526 1569 941
1x1200 43.5 3.4 53.9 70.2 1.5/1.8 66.9 6237 1672 1003
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
21
Al 6.35/11kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x25 115 135 105 115 80 115 115 115 100 105 100 91 2.37 6.9
1x35 140 165 130 135 96 140 140 135 120 120 120 110 3.31 6.9
1x50 170 200 155 165 115 165 165 160 145 145 140 130 4.73 6.9
1x70 210 245 195 205 145 200 200 195 175 170 170 160 6.62 6.9
1x95 255 295 235 250 170 235 235 230 205 200 200 190 8.99 10
1x120 290 335 270 290 200 265 260 260 225 225 230 220 11.4 10
1x150 330 375 305 325 225 295 290 295 255 250 255 245 14.2 10
1x185 375 425 350 375 255 330 320 330 285 275 290 275 17.5 10
1x240 440 495 415 440 295 375 365 380 325 310 330 320 22.7 10
1x300 500 555 470 505 345 420 400 425 360 340 370 365 28.4 10
1x400 575 630 550 585 400 470 445 485 405 375 420 415 37.8 10
1x500 660 720 640 685 455 530 495 550 450 415 475 475 47.3 10
1x630 750 805 735 785 520 590 540 620 495 450 530 535 59.6 10
1x800 850 900 840 900 610 645 585 695 545 490 590 620 75.7 10
1x1000 990 1010 1000 1070 715 730 640 800 600 530 660 710 94.6 10
1x1200 1080 1080 1100 1180 780 780 675 870 640 560 715 775 114 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
22
Al 6.35/11kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x25 1.20 1.54 1.54 0.153 0.168 0.213 12000 0.203 0.405 10.3 2.62 0.392 2.30 0.0858
1x35 0.868 1.11 1.11 0.144 0.159 0.205 11000 0.220 0.439 11.1 2.54 0.392 1.66 0.0779
1x50 0.641 0.821 0.821 0.140 0.155 0.201 9900 0.243 0.486 12.3 2.46 0.392 1.19 0.074
1x70 0.443 0.568 0.568 0.129 0.144 0.190 8700 0.276 0.551 14.0 2.37 0.392 0.838 0.0649
1x95 0.320 0.410 0.410 0.123 0.138 0.184 7800 0.311 0.620 15.8 2.30 0.269 0.614 0.0597
1x120 0.253 0.325 0.325 0.118 0.133 0.179 7100 0.339 0.677 17.2 2.25 0.269 0.516 0.0562
1x150 0.206 0.265 0.264 0.115 0.13 0.176 6600 0.368 0.734 18.6 2.22 0.269 0.469 0.0533
1x185 0.164 0.211 0.211 0.111 0.127 0.172 6100 0.398 0.794 20.2 2.18 0.269 0.434 0.0498
1x240 0.125 0.161 0.161 0.107 0.123 0.168 5400 0.445 0.887 22.5 2.14 0.269 0.395 0.0464
1x300 0.100 0.130 0.129 0.105 0.12 0.165 4900 0.491 0.980 24.9 2.11 0.269 0.370 0.0443
1x400 0.0778 0.102 0.101 0.101 0.116 0.161 4400 0.548 1.09 27.8 2.08 0.269 0.348 0.0414
1x500 0.0605 0.0803 0.0790 0.0969 0.112 0.158 3900 0.620 1.24 31.4 2.05 0.269 0.331 0.0385
1x630 0.0469 0.0636 0.0620 0.0944 0.110 0.155 3500 0.687 1.37 34.8 2.02 0.269 0.317 0.0364
1x800 0.0367 0.0516 0.0495 0.0914 0.107 0.152 3100 0.774 1.54 39.2 2.00 0.269 0.308 0.0342
1x1000 0.0291 0.0392 0.0387 0.0897 0.105 0.151 2600 0.926 1.85 46.9 1.97 0.269 0.300 0.0337
1x1200 0.0247 0.0328 0.0323 0.0887 0.104 0.150 2400 0.998 1.99 50.6 1.96 0.269 0.295 0.0330
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
23
Cu 6.35/11kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
24
Cu 6.35/11kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x25 6.0 3.4 14.2 47.2 1.5/1.6 27.3 1236 684 410
1x35 6.9 3.4 15.1 47.2 1.5/1.6 28.2 1346 706 424
1x50 8.1 3.4 16.3 47.2 1.5/1.6 29.4 1494 736 442
1x70 9.6 3.4 17.8 47.2 1.5/1.6 30.9 1716 774 464
1x95 11.3 3.4 19.5 70.3 1.5/1.6 32.6 2214 816 490
1x120 12.8 3.4 21.0 70.3 1.5/1.6 34.1 2491 854 512
1x150 14.2 3.4 22.4 70.3 1.5/1.6 35.5 2773 889 533
1x185 15.9 3.4 24.1 70.3 1.5/1.6 37.2 3162 931 559
1x240 18.1 3.4 26.3 70.3 1.5/1.6 39.4 3708 986 592
1x300 20.3 3.4 28.5 70.2 1.5/1.6 40.8 4303 1021 613
1x400 23.0 3.4 31.2 70.2 1.5/1.6 43.5 5133 1089 653
1x500 26.0 3.4 34.8 70.2 1.5/1.6 47.1 6194 1179 707
1x630 29.7 3.4 38.5 70.2 1.5/1.6 50.8 7621 1271 763
1x800 34.0 3.4 42.8 70.2 1.5/1.7 55.3 9499 1383 830
1x1000 39.5 3.4 49.9 70.2 1.5/1.8 62.8 11735 1569 941
1x1200 43.5 3.4 53.9 70.2 1.5/1.8 66.9 13683 1672 1003
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
25
Cu 6.35/11kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x25 150 175 140 145 105 150 150 145 130 130 130 115 3.57 6.9
1x35 180 210 170 180 125 180 180 175 155 155 155 140 5.00 6.9
1x50 215 250 200 215 150 210 210 205 180 180 180 165 7.15 6.9
1x70 270 310 250 270 185 250 250 250 215 215 215 205 10.0 6.9
1x95 325 370 300 320 220 295 290 295 255 245 255 240 13.6 10
1x120 370 420 350 370 255 335 325 335 285 275 290 280 17.1 10
1x150 415 470 395 420 290 370 355 375 315 300 320 310 21.4 10
1x185 475 530 450 480 325 415 395 420 350 330 360 350 26.4 10
1x240 550 605 525 565 375 470 440 485 395 365 410 405 34.3 10
1x300 620 675 600 640 440 520 480 540 435 400 460 465 42.9 10
1x400 705 755 690 735 500 575 525 605 475 435 510 520 57.2 10
1x500 790 835 785 840 560 630 570 675 525 470 570 580 71.5 10
1x630 880 920 890 950 625 685 610 750 565 500 625 645 90.0 10
1x800 990 1020 1010 1090 730 745 655 825 620 540 695 735 114 10
1x1000 1150 1130 1210 1290 855 840 705 960 660 570 755 855 143 10
1x1200 1230 1200 1320 1420 925 885 735 1030 700 595 815 920 171 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
26
Cu 6.35/11kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x25 0.727 0.927 0.927 0.152 0.168 0.213 12000 0.203 0.406 10.3 2.62 0.392 1.47 0.0654
1x35 0.524 0.668 0.668 0.146 0.162 0.207 11000 0.221 0.441 11.2 2.54 0.392 1.05 0.0593
1x50 0.387 0.494 0.494 0.140 0.155 0.200 9900 0.244 0.488 12.4 2.46 0.392 0.758 0.0536
1x70 0.268 0.342 0.342 0.133 0.149 0.194 8600 0.280 0.559 14.2 2.36 0.392 0.533 0.0479
1x95 0.193 0.247 0.247 0.122 0.137 0.183 7700 0.314 0.626 15.9 2.30 0.269 0.456 0.0594
1x120 0.153 0.196 0.195 0.118 0.133 0.179 6900 0.350 0.697 17.7 2.24 0.269 0.416 0.0566
1x150 0.124 0.160 0.159 0.114 0.129 0.175 6400 0.374 0.747 19.0 2.21 0.269 0.388 0.0527
1x185 0.0991 0.128 0.127 0.110 0.125 0.171 5900 0.409 0.817 20.7 2.17 0.269 0.369 0.0489
1x240 0.0754 0.0981 0.0973 0.106 0.121 0.167 5300 0.458 0.913 23.2 2.13 0.269 0.346 0.0456
1x300 0.0601 0.0791 0.0781 0.103 0.119 0.164 4800 0.507 1.01 25.7 2.10 0.269 0.331 0.0434
1x400 0.0470 0.0631 0.0617 0.100 0.116 0.161 4200 0.569 1.13 28.8 2.07 0.269 0.318 0.0414
1x500 0.0366 0.0507 0.0489 0.0974 0.113 0.158 3800 0.627 1.25 31.8 2.04 0.269 0.308 0.0391
1x630 0.0283 0.0413 0.0390 0.0948 0.110 0.156 3500 0.694 1.38 35.2 2.02 0.269 0.299 0.0369
1x800 0.0221 0.0348 0.0318 0.0901 0.105 0.151 3000 0.816 1.63 41.3 1.99 0.269 0.293 0.0339
1x1000 0.0176 0.0247 0.0241 0.0897 0.105 0.151 2600 0.926 1.85 46.9 1.97 0.269 0.289 0.0337
1x1200 0.0151 0.0210 0.0202 0.0887 0.104 0.150 2400 0.998 1.99 50.6 1.96 0.269 0.286 0.0330
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
27
Al 12.7/22kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
28
Al 12.7/22kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x35 6.9 5.5 19.3 70.3 1.5/1.6 32.4 1540 811 487
1x50 8.1 5.5 20.5 70.3 1.5/1.6 33.6 1619 841 505
1x70 9.6 5.5 22.0 70.3 1.5/1.6 35.1 1733 879 527
1x95 11.3 5.5 23.7 70.3 1.5/1.6 36.8 1867 921 553
1x120 12.8 5.5 25.2 70.3 1.5/1.6 38.3 1987 959 575
1x150 14.2 5.5 26.6 70.3 1.5/1.6 39.7 2128 994 596
1x185 15.9 5.5 28.3 70.2 1.5/1.6 40.6 2286 1016 610
1x240 18.1 5.5 30.5 70.2 1.5/1.6 42.8 2508 1071 643
1x300 20.3 5.5 32.7 70.2 1.5/1.6 45.0 2756 1126 676
1x400 23.0 5.5 35.4 70.2 1.5/1.6 47.7 3093 1194 716
1x500 26.0 5.5 39.0 70.2 1.5/1.6 51.4 3559 1285 771
1x630 29.7 5.5 42.7 70.2 1.5/1.7 55.2 4074 1381 828
1x800 34.0 5.5 47.0 70.2 1.5/1.8 59.7 4777 1491 895
1x1000 39.5 5.5 54.1 70.2 1.5/1.9 67.2 5966 1680 1008
1x1200 43.5 5.5 58.1 70.2 1.5/2.0 71.3 6704 1784 1070
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
29
Al 12.7/22kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x35 145 165 135 140 100 140 140 135 120 125 120 110 3.31 10
1x50 175 200 160 170 120 165 165 160 145 145 140 135 4.73 10
1x70 215 245 200 210 150 200 200 195 175 175 175 165 6.62 10
1x95 260 295 240 255 180 235 235 230 205 205 205 195 8.99 10
1x120 295 335 275 295 205 265 260 260 230 230 235 220 11.4 10
1x150 335 375 310 330 230 295 290 295 260 250 260 245 14.2 10
1x185 380 425 355 380 270 330 320 330 285 280 290 285 17.5 10
1x240 445 495 420 445 310 380 365 380 330 315 335 330 22.7 10
1x300 505 555 480 510 350 420 405 430 365 345 375 370 28.4 10
1x400 580 630 555 590 405 475 450 485 410 385 425 420 37.8 10
1x500 670 720 645 690 460 530 495 555 455 420 480 475 47.3 10
1x630 760 805 740 790 545 590 540 625 505 460 540 555 59.6 10
1x800 855 900 850 905 615 650 590 695 545 495 590 620 75.7 10
1x1000 995 1010 1000 1070 715 730 645 800 610 540 670 715 94.6 10
1x1200 1090 1090 1110 1190 785 785 680 870 650 565 725 775 114 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
30
Al 12.7/22kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x35 0.868 1.11 1.11 0.156 0.171 0.216 15000 0.157 0.626 31.8 3.62 0.269 1.67 0.0919
1x50 0.641 0.821 0.821 0.151 0.166 0.211 14000 0.172 0.685 34.8 3.47 0.269 1.19 0.0869
1x70 0.443 0.568 0.568 0.140 0.155 0.201 13000 0.192 0.768 39.0 3.30 0.269 0.838 0.0769
1x95 0.320 0.410 0.410 0.133 0.148 0.194 11000 0.214 0.855 43.4 3.17 0.269 0.620 0.0708
1x120 0.253 0.325 0.325 0.128 0.143 0.189 10000 0.232 0.926 47.0 3.08 0.269 0.522 0.0667
1x150 0.206 0.264 0.264 0.124 0.139 0.185 9700 0.250 0.997 50.7 3.01 0.269 0.476 0.0633
1x185 0.164 0.211 0.211 0.120 0.136 0.181 9000 0.269 1.07 54.5 2.95 0.269 0.434 0.0593
1x240 0.125 0.161 0.161 0.116 0.131 0.177 8100 0.298 1.19 60.4 2.87 0.269 0.395 0.0551
1x300 0.100 0.129 0.129 0.112 0.128 0.173 7400 0.327 1.30 66.3 2.81 0.269 0.370 0.0527
1x400 0.0778 0.102 0.101 0.108 0.123 0.169 6700 0.363 1.45 73.5 2.75 0.269 0.348 0.0488
1x500 0.0605 0.0800 0.0790 0.104 0.119 0.164 5900 0.407 1.62 82.4 2.69 0.269 0.331 0.0453
1x630 0.0469 0.0633 0.0619 0.101 0.116 0.161 5400 0.448 1.79 90.9 2.64 0.269 0.318 0.0427
1x800 0.0367 0.0512 0.0493 0.0971 0.112 0.158 4800 0.502 2.00 102 2.60 0.269 0.308 0.0398
1x1000 0.0291 0.0391 0.0387 0.0944 0.110 0.155 4000 0.597 2.38 121 2.54 0.269 0.300 0.0386
1x1200 0.0247 0.0328 0.0323 0.0931 0.108 0.154 3800 0.641 2.56 130 2.52 0.269 0.295 0.0376
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
31
Cu 12.7/22kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
32
Cu 12.7/22kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x35 6.9 5.5 19.3 70.3 1.5/1.6 32.4 1751 811 487
1x50 8.1 5.5 20.5 70.3 1.5/1.6 33.6 1906 841 505
1x70 9.6 5.5 22.0 70.3 1.5/1.6 35.1 2137 879 527
1x95 11.3 5.5 23.7 70.3 1.5/1.6 36.8 2427 921 553
1x120 12.8 5.5 25.2 70.3 1.5/1.6 38.3 2714 959 575
1x150 14.2 5.5 26.6 70.3 1.5/1.6 39.7 3005 994 596
1x185 15.9 5.5 28.3 70.2 1.5/1.6 40.6 3392 1016 610
1x240 18.1 5.5 30.5 70.2 1.5/1.6 42.8 3952 1071 643
1x300 20.3 5.5 32.7 70.2 1.5/1.6 45.0 4573 1126 676
1x400 23.0 5.5 35.4 70.2 1.5/1.6 47.7 5419 1194 716
1x500 26.0 5.5 39.0 70.2 1.5/1.6 51.4 6506 1285 771
1x630 29.7 5.5 42.7 70.2 1.5/1.7 55.2 7969 1381 828
1x800 34.0 5.5 47.0 70.2 1.5/1.8 59.7 9870 1491 895
1x1000 39.5 5.5 54.1 70.2 1.5/1.9 67.2 12174 1680 1008
1x1200 43.5 5.5 58.1 70.2 1.5/2.0 71.3 14150 1784 1070
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
33
Cu 12.7/22kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x35 185 210 175 185 130 180 180 175 155 155 155 145 5.00 10
1x50 220 250 205 220 155 210 210 205 185 180 180 170 7.15 10
1x70 275 310 255 270 195 250 250 250 220 215 220 210 10.0 10
1x95 330 370 310 325 230 295 290 295 260 250 260 250 13.6 10
1x120 375 420 355 375 260 335 325 335 290 280 295 280 17.1 10
1x150 425 470 400 425 295 370 360 375 320 305 325 315 21.4 10
1x185 480 530 455 485 345 415 395 420 355 335 365 365 26.4 10
1x240 560 605 535 570 395 470 445 485 400 375 420 415 34.3 10
1x300 630 675 610 650 445 520 485 540 440 405 465 465 42.9 10
1x400 715 755 700 745 505 575 530 610 490 445 520 525 57.2 10
1x500 800 840 795 850 570 635 575 680 530 475 575 585 71.5 10
1x630 895 925 900 960 665 695 615 755 575 510 635 675 90.0 10
1x800 1010 1030 1030 1110 740 750 660 835 615 540 690 745 114 10
1x1000 1160 1140 1220 1300 865 845 710 965 680 580 775 860 143 10
1x1200 1250 1210 1330 1420 935 895 745 1040 720 610 835 925 171 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
34
Cu 12.7/22kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x35 0.524 0.668 0.668 0.158 0.173 0.219 15000 0.157 0.628 31.9 3.62 0.269 1.05 0.0935
1x50 0.387 0.494 0.494 0.150 0.166 0.211 14000 0.172 0.688 34.9 3.46 0.269 0.758 0.0869
1x70 0.268 0.342 0.342 0.142 0.157 0.203 12000 0.195 0.778 39.5 3.29 0.269 0.531 0.0799
1x95 0.193 0.247 0.247 0.132 0.147 0.193 11000 0.216 0.862 43.8 3.16 0.269 0.463 0.0704
1x120 0.153 0.196 0.195 0.127 0.142 0.188 10000 0.236 0.942 47.8 3.07 0.269 0.423 0.0659
1x150 0.124 0.159 0.159 0.123 0.138 0.184 9500 0.254 1.01 51.5 3.00 0.269 0.394 0.0625
1x185 0.0991 0.128 0.127 0.119 0.134 0.180 8700 0.276 1.10 55.9 2.93 0.269 0.369 0.0582
1x240 0.0754 0.0978 0.0972 0.114 0.130 0.175 7900 0.306 1.22 62.0 2.85 0.269 0.346 0.0541
1x300 0.0601 0.0788 0.0780 0.111 0.126 0.172 7200 0.337 1.34 68.2 2.79 0.269 0.33 0.0517
1x400 0.0470 0.0627 0.0617 0.108 0.123 0.169 6400 0.375 1.50 76.0 2.73 0.269 0.318 0.0487
1x500 0.0366 0.0503 0.0488 0.104 0.119 0.165 5900 0.411 1.64 83.3 2.68 0.269 0.307 0.0459
1x630 0.0283 0.0407 0.0388 0.101 0.116 0.162 5300 0.453 1.81 91.8 2.64 0.269 0.300 0.0431
1x800 0.0221 0.0342 0.0317 0.0956 0.111 0.157 4600 0.528 2.11 107 2.58 0.269 0.294 0.0393
1x1000 0.0176 0.0246 0.0240 0.0944 0.110 0.155 4000 0.597 2.38 121 2.54 0.269 0.288 0.0386
1x1200 0.0151 0.0208 0.0201 0.0931 0.108 0.154 3800 0.641 2.56 130 2.52 0.269 0.285 0.0376
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
35
Al 19/33kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
36
Al 19/33kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x50 8.1 8.0 25.5 70.3 1.5/1.6 38.6 1884 966 580
1x70 9.6 8.0 27.0 70.3 1.5/1.6 40.1 2008 1004 602
1x95 11.3 8.0 28.7 70.2 1.5/1.6 41.0 2142 1026 616
1x120 12.8 8.0 30.2 70.2 1.5/1.6 42.5 2274 1064 638
1x150 14.2 8.0 31.6 70.2 1.5/1.6 43.9 2425 1099 659
1x185 15.9 8.0 33.3 70.2 1.5/1.6 45.6 2608 1141 685
1x240 18.1 8.0 35.5 70.2 1.5/1.6 47.8 2846 1196 718
1x300 20.3 8.0 37.7 70.2 1.5/1.6 50.1 3115 1252 751
1x400 23.0 8.0 40.4 70.2 1.5/1.7 52.9 3483 1323 794
1x500 26.0 8.0 44.0 70.2 1.5/1.8 56.7 3984 1416 850
1x630 29.7 8.0 47.7 70.2 1.5/1.8 60.5 4528 1512 907
1x800 34.0 8.0 52.0 70.2 1.5/1.9 64.9 5266 1623 974
1x1000 39.5 8.0 59.1 70.2 1.5/2.0 72.3 6506 1809 1085
1x1200 43.5 8.0 63.1 70.2 1.5/2.0 76.5 7275 1912 1147
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
37
Al 19/33kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x50 175 195 165 170 125 160 165 160 145 150 145 135 4.73 10
1x70 215 245 200 215 160 200 200 195 180 180 175 170 6.62 10
1x95 260 290 245 260 190 235 235 230 210 205 210 200 8.99 10
1x120 300 335 280 295 215 265 260 260 240 235 235 230 11.4 10
1x150 335 375 315 335 240 295 290 295 265 260 265 255 14.2 10
1x185 385 425 360 380 270 330 325 330 295 285 295 285 17.5 10
1x240 450 490 425 450 315 380 365 380 335 320 340 330 22.7 10
1x300 510 555 485 515 355 420 405 430 370 355 380 370 28.4 10
1x400 585 630 560 595 425 475 450 490 415 390 430 440 37.8 10
1x500 675 715 650 690 485 535 500 555 465 430 485 495 47.3 10
1x630 765 805 750 795 555 595 545 625 510 465 540 560 59.6 10
1x800 865 900 855 910 625 655 595 700 560 505 605 625 75.7 10
1x1000 1000 1010 1010 1070 735 735 650 800 620 550 685 730 94.6 10
1x1200 1090 1090 1110 1190 805 790 685 875 640 565 710 795 114 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
38
Al 19/33kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x50 0.641 0.821 0.821 0.162 0.178 0.223 18000 0.134 0.798 60.7 4.04 0.269 1.20 0.0997
1x70 0.443 0.568 0.568 0.151 0.166 0.212 16000 0.148 0.885 67.3 3.81 0.269 0.848 0.0889
1x95 0.320 0.410 0.410 0.143 0.158 0.204 15000 0.164 0.977 74.3 3.62 0.269 0.621 0.0821
1x120 0.253 0.325 0.325 0.138 0.154 0.199 14000 0.176 1.05 79.9 3.50 0.269 0.523 0.0775
1x150 0.206 0.264 0.264 0.134 0.149 0.195 13000 0.189 1.13 85.5 3.40 0.269 0.476 0.0739
1x185 0.164 0.211 0.211 0.130 0.145 0.191 12000 0.202 1.20 91.5 3.31 0.269 0.434 0.0695
1x240 0.125 0.161 0.161 0.125 0.140 0.185 11000 0.222 1.32 101 3.20 0.269 0.395 0.0647
1x300 0.100 0.129 0.129 0.121 0.136 0.182 10000 0.242 1.44 110 3.11 0.269 0.371 0.0613
1x400 0.0778 0.101 0.101 0.115 0.131 0.176 9100 0.267 1.59 121 3.02 0.269 0.348 0.0568
1x500 0.0605 0.0797 0.0789 0.111 0.126 0.172 8100 0.297 1.77 135 2.93 0.269 0.331 0.0527
1x630 0.0469 0.0629 0.0618 0.107 0.122 0.168 7400 0.326 1.94 148 2.87 0.269 0.317 0.0495
1x800 0.0367 0.0507 0.0492 0.103 0.118 0.164 6700 0.363 2.17 165 2.80 0.269 0.307 0.0461
1x1000 0.0291 0.0390 0.0387 0.0999 0.115 0.161 5600 0.427 2.55 194 2.72 0.269 0.300 0.0441
1x1200 0.0247 0.0327 0.0323 0.0983 0.114 0.159 5300 0.458 2.73 208 2.69 0.269 0.294 0.0428
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
39
Cu 19/33kV
MV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
40
Cu 19/33kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
1x50 8.1 8.0 25.5 70.3 1.5/1.6 38.6 2171 966 580
1x70 9.6 8.0 27.0 70.3 1.5/1.6 40.1 2412 1004 602
1x95 11.3 8.0 28.7 70.2 1.5/1.6 41.0 2703 1026 616
1x120 12.8 8.0 30.2 70.2 1.5/1.6 42.5 3001 1064 638
1x150 14.2 8.0 31.6 70.2 1.5/1.6 43.9 3303 1099 659
1x185 15.9 8.0 33.3 70.2 1.5/1.6 45.6 3714 1141 685
1x240 18.1 8.0 35.5 70.2 1.5/1.6 47.8 4290 1196 718
1x300 20.3 8.0 37.7 70.2 1.5/1.6 50.1 4931 1252 751
1xx400 23.0 8.0 40.4 70.2 1.5/1.7 52.9 5809 1323 794
1x500 26.0 8.0 44.0 70.2 1.5/1.8 56.7 6931 1416 850
1x630 29.7 8.0 47.7 70.2 1.5/1.8 60.5 8423 1512 907
1x800 34.0 8.0 52.0 70.2 1.5/1.9 64.9 10359 1623 974
1x1000 39.5 8.0 59.1 70.2 1.5/2.0 72.3 12714 1809 1085
1x1200 43.5 8.0 63.1 70.2 1.5/2.0 76.5 14721 1912 1147
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
41
Cu 19/33kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
1x50 225 250 210 220 160 210 210 205 185 185 185 175 7.15 10
1x70 275 310 260 275 205 250 250 250 225 220 225 215 10.0 10
1x95 335 370 315 330 240 300 295 295 265 255 265 260 13.6 10
1x120 380 420 360 380 275 335 330 335 295 285 300 290 17.1 10
1x150 430 470 405 430 310 370 360 375 325 315 335 325 21.4 10
1x185 485 530 465 490 350 415 400 420 365 345 375 365 26.4 10
1x240 565 605 545 575 405 470 445 485 410 385 425 420 34.3 10
1x300 635 680 620 655 455 525 485 545 450 415 470 470 42.9 10
1x400 720 760 710 750 535 580 535 610 495 450 530 550 57.2 10
1x500 810 845 805 855 600 640 580 685 545 485 590 615 71.5 10
1x630 905 930 915 970 675 700 625 760 580 515 635 680 90.0 10
1x800 1020 1030 1040 1110 750 760 670 840 635 555 710 750 114 10
1x1000 1170 1140 1220 1310 890 850 720 970 665 580 750 885 143 10
1x1200 1260 1210 1340 1430 965 900 750 1050 700 605 805 950 171 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
42
Cu 19/33kV
Electrical parameters
(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
1x50 0.387 0.494 0.494 0.162 0.177 0.223 18000 0.134 0.801 60.9 4.03 0.269 0.768 0.0998
1x70 0.268 0.342 0.342 0.153 0.168 0.214 16000 0.150 0.896 68.1 3.79 0.269 0.538 0.0921
1x95 0.193 0.247 0.247 0.143 0.158 0.204 15000 0.165 0.984 74.8 3.61 0.269 0.463 0.0819
1x120 0.153 0.195 0.195 0.137 0.153 0.198 14000 0.179 1.07 81.1 3.48 0.269 0.422 0.0766
1x150 0.124 0.159 0.159 0.133 0.148 0.194 13000 0.191 1.14 86.8 3.38 0.269 0.395 0.0731
1x185 0.0991 0.127 0.127 0.129 0.144 0.190 12000 0.207 1.23 93.7 3.28 0.269 0.369 0.0682
1x240 0.0754 0.0976 0.0972 0.123 0.139 0.184 11000 0.228 1.36 103 3.17 0.269 0.346 0.0635
1x300 0.0601 0.0786 0.0779 0.120 0.135 0.180 9700 0.249 1.48 113 3.08 0.269 0.331 0.0612
1x400 0.0470 0.0624 0.0616 0.115 0.130 0.176 8800 0.275 1.64 125 2.99 0.269 0.317 0.0565
1x500 0.0366 0.0499 0.0487 0.111 0.126 0.172 8000 0.300 1.79 136 2.93 0.269 0.307 0.0532
1x630 0.0283 0.0403 0.0387 0.107 0.123 0.168 7300 0.329 1.96 149 2.86 0.269 0.300 0.0505
1x800 0.0221 0.0336 0.0315 0.102 0.117 0.162 6300 0.381 2.27 173 2.78 0.269 0.294 0.0454
1x1000 0.0176 0.0245 0.0240 0.0999 0.115 0.161 5600 0.427 2.55 194 2.72 0.269 0.288 0.0441
1x1200 0.0151 0.0207 0.0201 0.0983 0.114 0.159 5300 0.458 2.73 208 2.69 0.269 0.285 0.0428
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
43
Al 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
44
Al 1.9/3.3kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x500 26.0 2.2 32.0 67.9 1.7/2.4 87.7 8597 2193 1316
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
45
Al 1.9/3.3kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
3x25 90 95 60 95 72 2.37 10
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
46
Al 1.9/3.3kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x25 1.20 1.54 0.103 9200 0.296 0.206 2.1 1.27 0.273 4.26 0.0658
3x35 0.868 1.11 0.0983 8500 0.326 0.237 2.5 1.22 0.273 3.12 0.0572
3x50 0.641 0.822 0.0921 8000 0.365 0.272 3.4 1.17 0.273 2.31 0.0521
3x70 0.443 0.569 0.0896 6800 0.413 0.313 4.3 1.11 0.273 1.60 0.0492
3x95 0.320 0.410 0.0869 6100 0.468 0.357 5.0 1.07 0.273 1.15 0.0470
3x120 0.253 0.325 0.0857 5500 0.516 0.382 5.7 1.04 0.273 1.05 0.0441
3x150 0.206 0.265 0.0842 5000 0.561 0.424 6.7 1.02 0.273 1.00 0.0413
3x185 0.164 0.211 0.0824 4500 0.616 0.464 8.4 0.98 0.273 0.961 0.0402
3x240 0.125 0.162 0.0814 3900 0.687 0.508 7.8 0.92 0.273 0.940 0.0384
3x300 0.100 0.130 0.0807 3600 0.757 0.556 8.5 0.86 0.273 0.917 0.0368
3x400 0.0778 0.102 0.0793 3200 0.844 0.595 8.9 0.83 0.273 0.895 0.0324
3x500 0.0617 0.0824 0.0784 3000 0.884 0.637 9.4 0.79 0.273 0.868 0.0303
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
47
Cu 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
48
Cu 1.9/3.3kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x500 26.0 2.2 32.0 67.9 1.7/2.4 87.7 17454 2193 1316
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
49
Cu 1.9/3.3kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
50
Cu 1.9/3.3kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x25 0.727 0.932 0.103 9100 0.296 0.207 2.1 1.27 0.273 2.85 0.0524
3x35 0.524 0.672 0.0984 8500 0.326 0.238 2.6 1.22 0.273 2.11 0.0493
3x50 0.387 0.496 0.0921 7900 0.365 0.275 3.5 1.17 0.273 1.47 0.0475
3x70 0.268 0.344 0.0895 6800 0.413 0.314 4.3 1.11 0.273 1.06 0.0466
3x95 0.193 0.248 0.0869 6000 0.468 0.359 5.1 1.08 0.273 0.987 0.0434
3x120 0.153 0.197 0.0857 5500 0.516 0.384 5.8 1.04 0.273 0.950 0.0412
3x150 0.124 0.161 0.0836 5000 0.561 0.426 6.7 1.02 0.273 0.921 0.0401
3x185 0.0991 0.129 0.0824 4400 0.616 0.465 8.5 0.98 0.273 0.896 0.0394
3x240 0.0754 0.0992 0.0817 3900 0.687 0.509 7.9 0.92 0.273 0.892 0.0387
3x300 0.0601 0.0802 0.0809 3600 0.757 0.558 8.5 0.87 0.273 0.878 0.0374
3x400 0.0470 0.0642 0.0796 3100 0.844 0.597 9.0 0.83 0.273 0.865 0.0351
3x500 0.0373 0.0527 0.0768 2900 0.884 0.621 10.5 0.76 0.273 0.842 0.0338
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
51
Al 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
52
Al 3.8/6.6kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x25 6.0 2.5 12.4 67.9 1.5/1.6 42.3 2179 1056 634
3x35 6.9 2.5 13.3 67.9 1.5/1.6 44.2 2345 1105 663
3x50 8.1 2.5 14.5 67.9 1.5/1.6 46.8 2570 1169 702
3x70 9.6 2.5 16.0 67.9 1.5/1.6 50.1 2871 1251 751
3x95 11.3 2.5 17.7 67.9 1.5/1.7 53.9 3277 1346 808
3x120 12.8 2.5 19.2 67.9 1.5/1.8 57.2 3646 1430 858
3x150 14.15 2.5 20.6 67.9 1.5/1.8 60.4 4036 1509 905
3x185 15.9 2.5 22.3 67.9 1.5/2.0 64.3 4582 1607 964
3x240 18.1 2.6 24.7 67.9 1.5/2.0 69.6 5272 1739 1044
3x300 20.3 2.8 27.3 67.9 1.5/2.1 75.4 6162 1886 1132
3x400 23.0 3.0 30.4 67.9 1.6/2.3 82.7 7418 2069 1241
3x500 26.0 3.2 34.0 67.9 1.7/2.5 92.2 9110 2306 1384
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
53
Al 3.8/6.6kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
54
Al 3.8/6.6kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x25 1.20 1.54 0.115 9500 0.255 0.304 4.6 1.97 0.273 4.39 0.0785
3x35 0.868 1.11 0.109 8700 0.278 0.332 5.0 1.92 0.273 3.14 0.0709
3x50 0.641 0.822 0.104 7800 0.309 0.369 5.6 1.87 0.273 2.32 0.0658
3x70 0.443 0.569 0.0964 6800 0.353 0.422 6.4 1.82 0.273 1.62 0.0574
3x95 0.320 0.410 0.0924 6000 0.400 0.478 7.3 1.77 0.273 1.20 0.0527
3x120 0.253 0.325 0.0898 5500 0.439 0.524 8.0 1.74 0.273 1.05 0.0497
3x150 0.206 0.265 0.0877 5100 0.477 0.569 8.7 1.72 0.273 1.00 0.0471
3x185 0.164 0.211 0.0857 4700 0.518 0.618 9.4 1.70 0.273 0.961 0.0440
3x240 0.125 0.162 0.0839 4300 0.561 0.670 10.2 1.62 0.273 0.941 0.0416
3x300 0.100 0.130 0.0835 4100 0.582 0.695 10.6 1.50 0.273 0.918 0.0407
3x400 0.0778 0.102 0.0814 3900 0.613 0.731 11.1 1.39 0.273 0.894 0.0385
3x500 0.0617 0.0824 0.0800 3700 0.654 0.781 11.8 1.29 0.273 0.878 0.0370
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
55
Cu 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
56
Cu 3.8/6.6kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x25 6.0 2.5 12.4 67.9 1.5/1.6 42.3 2642 1056 634
3x35 6.9 2.5 13.3 67.9 1.5/1.6 44.2 2979 1105 663
3x50 8.1 2.5 14.5 67.9 1.5/1.6 46.8 3433 1169 702
3x70 9.6 2.5 16.0 67.9 1.5/1.6 50.1 4086 1251 751
3x95 11.3 2.5 17.7 67.9 1.5/1.7 53.9 4961 1346 808
3x120 12.8 2.5 19.2 67.9 1.5/1.8 57.2 5832 1430 858
3x150 14.2 2.5 20.6 67.9 1.5/1.8 60.4 6674 1509 905
3x185 15.9 2.5 22.3 67.9 1.5/2.0 64.3 7907 1607 964
3x240 18.1 2.6 24.7 67.9 1.5/2.0 69.6 9612 1739 1044
3x300 20.3 2.8 27.3 67.9 1.5/2.1 75.4 11623 1886 1132
3x400 23.0 3.0 30.4 67.9 1.6/2.3 82.7 14408 2069 1241
3x500 26.0 3.2 34.0 67.9 1.7/2.5 92.2 17968 2306 1384
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
57
Cu 3.8/6.6kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
58
Cu 3.8/6.6kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x25 0.727 0.932 0.115 9400 0.256 0.305 4.6 1.97 0.273 2.85 0.0763
3x35 0.524 0.672 0.109 8600 0.279 0.333 5.1 1.92 0.273 2.12 0.0708
3x50 0.387 0.496 0.104 7800 0.311 0.371 5.6 1.87 0.273 1.48 0.0660
3x70 0.268 0.344 0.0987 6700 0.359 0.428 6.5 1.81 0.273 1.06 0.0601
3x95 0.193 0.248 0.0922 6000 0.404 0.482 7.3 1.77 0.273 0.989 0.0524
3x120 0.153 0.197 0.0893 5400 0.447 0.534 8.1 1.74 0.273 0.950 0.0491
3x150 0.124 0.161 0.0872 5000 0.486 0.580 8.8 1.72 0.273 0.920 0.0466
3x185 0.0991 0.129 0.0851 4500 0.533 0.636 9.7 1.69 0.273 0.896 0.0433
3x240 0.0754 0.0992 0.0833 4200 0.578 0.690 10.5 1.61 0.273 0.892 0.0409
3x300 0.0601 0.0802 0.0829 4000 0.601 0.718 10.9 1.49 0.273 0.878 0.0399
3x400 0.0470 0.0642 0.0817 3800 0.636 0.759 11.5 1.38 0.273 0.864 0.0387
3x500 0.0373 0.0527 0.0806 3600 0.662 0.790 12.0 1.29 0.273 0.855 0.0376
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
59
Al 6.35/11kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
60
Al 6.35/11kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x25 6.0 3.4 14.2 67.9 1.5/1.6 46.1 2414 1153 692
3x35 6.9 3.4 15.1 67.9 1.5/1.6 48.1 2589 1202 721
3x50 8.1 3.4 16.3 67.9 1.5/1.6 50.7 2801 1268 761
3x70 9.6 3.4 17.8 67.9 1.5/1.7 54.1 3156 1352 811
3x95 11.3 3.4 19.5 67.9 1.5/1.8 58.0 3593 1450 870
3x120 12.8 3.4 21.0 67.9 1.5/1.9 61.3 3940 1534 920
3x150 14.15 3.4 22.4 67.9 1.5/2.0 64.5 4389 1612 967
3x185 15.9 3.4 24.1 67.9 1.5/2.0 68.3 4895 1707 1024
3x240 18.1 3.4 26.3 67.9 1.5/2.1 73.3 5631 1832 1099
3x300 20.3 3.4 28.5 67.9 1.5/2.2 78.2 6453 1955 1173
3x400 23.0 3.4 31.2 67.9 1.6/2.3 84.5 7610 2112 1267
3x500 26.0 3.4 34.4 67.9 1.7/2.5 93.1 9216 2327 1396
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
61
Al 6.35/11kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
62
Al 6.35/11kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x25 1.20 1.54 0.124 12000 0.203 0.405 10.3 2.62 0.273 4.10 0.0858
3x35 0.868 1.11 0.117 11000 0.220 0.439 11.1 2.54 0.273 3.14 0.0779
3x50 0.641 0.821 0.112 9900 0.243 0.486 12.3 2.46 0.273 2.32 0.0724
3x70 0.443 0.569 0.104 8700 0.276 0.551 14.0 2.37 0.273 1.62 0.0634
3x95 0.320 0.410 0.0990 7800 0.311 0.620 15.8 2.30 0.273 1.20 0.0583
3x120 0.253 0.325 0.0959 7100 0.339 0.677 17.2 2.25 0.273 1.05 0.0549
3x150 0.206 0.265 0.0934 6600 0.368 0.734 18.6 2.22 0.273 1.00 0.0520
3x185 0.164 0.211 0.0911 6100 0.398 0.794 20.2 2.18 0.273 0.981 0.0486
3x240 0.125 0.161 0.0881 5400 0.445 0.887 22.5 2.14 0.273 0.941 0.0453
3x300 0.100 0.130 0.0864 4900 0.491 0.980 24.9 2.11 0.273 0.916 0.0432
3x400 0.0778 0.102 0.0832 4400 0.548 1.09 27.8 2.08 0.273 0.894 0.0405
3x500 0.0617 0.0823 0.0808 3900 0.620 1.24 31.4 2.05 0.273 0.880 0.0377
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
63
Cu 6.35/11kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
64
Cu 6.35/11kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x25 6.0 3.4 14.2 67.9 1.5/1.6 46.1 2877 1153 692
3x35 6.9 3.4 15.1 67.9 1.5/1.6 48.1 3223 1202 721
3x50 8.1 3.4 16.3 67.9 1.5/1.6 50.7 3664 1268 761
3x70 9.6 3.4 17.8 67.9 1.5/1.7 54.1 4371 1352 811
3x95 11.3 3.4 19.5 67.9 1.5/1.8 58.0 5278 1450 870
3x120 12.8 3.4 21.0 67.9 1.5/1.9 61.3 6125 1534 920
3x150 14.15 3.4 22.4 67.9 1.5/2.0 64.5 7027 1612 967
3x185 15.9 3.4 24.1 67.9 1.5/2.0 68.3 8220 1707 1024
3x240 18.1 3.4 26.3 67.9 1.5/2.1 73.3 9972 1832 1099
3x300 20.3 3.4 28.5 67.9 1.5/2.2 78.2 11913 1955 1173
3x400 23.0 3.4 31.2 67.9 1.6/2.3 84.5 14599 2112 1267
3x500 26.0 3.4 34.4 67.9 1.7/2.5 93.1 18073 2327 1396
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
65
Cu 6.35/11kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
66
Cu 6.35/11kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x25 0.727 0.932 0.124 12000 0.203 0.406 10.3 2.62 0.273 2.85 0.0823
3x35 0.524 0.672 0.117 11000 0.221 0.441 11.2 2.54 0.273 2.12 0.0775
3x50 0.387 0.496 0.112 9900 0.244 0.488 12.4 2.46 0.273 1.49 0.0724
3x70 0.268 0.344 0.106 8600 0.280 0.559 14.2 2.36 0.273 1.06 0.0663
3x95 0.193 0.248 0.0987 7700 0.314 0.626 15.9 2.30 0.273 0.989 0.0579
3x120 0.153 0.197 0.0953 7000 0.346 0.689 17.5 2.25 0.273 0.950 0.0542
3x150 0.124 0.161 0.0928 6400 0.374 0.747 19.0 2.21 0.273 0.921 0.0514
3x185 0.0991 0.129 0.0903 5900 0.409 0.817 20.7 2.17 0.273 0.915 0.0477
3x240 0.0754 0.0990 0.0874 5300 0.458 0.913 23.2 2.13 0.273 0.892 0.0445
3x300 0.0601 0.0800 0.0857 4800 0.507 1.01 25.7 2.10 0.273 0.876 0.0424
3x400 0.0470 0.0641 0.0834 4200 0.569 1.13 28.8 2.07 0.273 0.864 0.0405
3x500 0.0373 0.0527 0.0815 3800 0.627 1.25 31.8 2.04 0.273 0.853 0.0383
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
67
Al 12.7/22kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
68
Al 12.7/22kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x35 6.9 5.5 19.3 6.9 1.5/1.8 57.6 3244 1439 863
3x50 8.1 5.5 20.5 8.1 1.5/1.9 60.3 3486 1507 904
3x70 9.6 5.5 22.0 9.6 1.5/2.0 63.6 3882 1591 954
3x95 11.3 5.5 23.7 11.3 1.5/2.0 67.4 4354 1686 1011
3x120 12.8 5.5 25.2 12.8 1.5/2.1 70.8 4737 1770 1062
3x150 14.15 5.5 26.6 14.15 1.5/2.1 73.9 5226 1848 1109
3x185 15.9 5.5 28.3 15.9 1.5/2.2 77.8 5833 1945 1167
3x240 18.1 5.5 30.5 18.1 1.6/2.3 83.0 6665 2074 1244
3x300 20.3 5.5 32.7 20.3 1.7/2.4 87.9 7551 2198 1319
3x400 23.0 5.5 35.4 23.0 1.8/2.6 94.4 8829 2360 1416
3x500 26.0 5.5 38.6 26.0 1.9/2.7 103.0 10570 2576 1545
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
69
Al 12.7/22kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
70
Al 12.7/22kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x35 0.868 1.11 0.134 15000 0.157 0.626 31.8 3.62 0.273 3.15 0.0919
3x50 0.641 0.821 0.128 14000 0.172 0.685 34.8 3.47 0.273 2.32 0.0855
3x70 0.443 0.568 0.118 13000 0.192 0.768 39.0 3.30 0.273 1.62 0.0756
3x95 0.320 0.410 0.112 11000 0.214 0.855 43.4 3.17 0.273 1.23 0.0696
3x120 0.253 0.325 0.108 10000 0.232 0.926 47.0 3.08 0.273 1.07 0.0656
3x150 0.206 0.265 0.105 9700 0.250 0.997 50.7 3.01 0.273 1.02 0.0622
3x185 0.164 0.211 0.102 9000 0.269 1.07 54.5 2.95 0.273 0.982 0.0582
3x240 0.125 0.161 0.0983 8100 0.298 1.19 60.4 2.87 0.273 0.941 0.0542
3x300 0.100 0.130 0.0958 7400 0.327 1.30 66.3 2.81 0.273 0.918 0.0519
3x400 0.0778 0.102 0.0917 6700 0.363 1.45 73.5 2.75 0.273 0.894 0.0480
3x500 0.0617 0.0819 0.0885 5900 0.407 1.62 82.4 2.69 0.273 0.879 0.4460
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
71
Cu 12.7/22kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
72
Cu 12.7/22kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
3x35 6.9 5.5 19.3 67.9 1.5/1.8 57.6 3878 1439 863
3x50 8.1 5.5 20.5 67.9 1.5/1.9 60.3 4349 1507 904
3x70 9.6 5.5 22.0 67.9 1.5/2.0 63.6 5097 1591 954
3x95 11.3 5.5 23.7 67.9 1.5/2.0 67.4 6039 1686 1011
3x120 12.8 5.5 25.2 67.9 1.5/2.1 70.8 6922 1770 1062
3x150 14.15 5.5 26.6 67.9 1.5/2.1 73.9 7864 1848 1109
3x185 15.9 5.5 28.3 67.9 1.5/2.2 77.8 9158 1945 1167
3x240 18.1 5.5 30.5 67.9 1.6/2.3 83.0 11006 2074 1244
3x300 20.3 5.5 32.7 67.9 1.7/2.4 87.9 13011 2198 1319
3x400 23.0 5.5 35.4 67.9 1.8/2.6 94.4 15819 2360 1416
3x500 26.0 5.5 38.6 67.9 1.9/2.7 103.0 19428 2576 1545
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
73
Cu 12.7/22kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
74
Cu 12.7/22kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x35 0.524 0.672 0.134 15000 0.157 0.628 31.9 3.62 0.273 2.12 0.0915
3x50 0.387 0.496 0.128 14000 0.172 0.688 34.9 3.46 0.273 1.49 0.0843
3x70 0.268 0.344 0.120 12000 0.195 0.778 39.5 3.29 0.273 1.06 0.0778
3x95 0.193 0.248 0.112 11000 0.216 0.862 43.8 3.16 0.273 1.01 0.0692
3x120 0.153 0.197 0.108 10000 0.236 0.942 47.8 3.07 0.273 0.970 0.0648
3x150 0.124 0.160 0.104 9500 0.254 1.010 51.5 3.00 0.273 0.941 0.0615
3x185 0.0991 0.128 0.101 8700 0.276 1.10 55.9 2.93 0.273 0.916 0.0572
3x240 0.0754 0.0986 0.0973 7900 0.306 1.22 62.0 2.85 0.273 0.894 0.0532
3x300 0.0601 0.0796 0.0949 7200 0.337 1.34 68.2 2.79 0.273 0.877 0.0508
3x400 0.0470 0.0636 0.0917 6400 0.375 1.50 76.0 2.73 0.273 0.864 0.0479
3x500 0.0373 0.0520 0.0891 5900 0.411 1.64 83.3 2.68 0.273 0.856 0.0451
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
75
Al 19/33kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
76
Al 19/33kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
77
Al 19/33kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
78
Al 19/33kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x50 0.641 0.822 0.143 18000 0.134 0.798 60.7 4.04 0.273 2.36 0.0986
3x70 0.443 0.569 0.132 16000 0.148 0.885 67.3 3.81 0.273 1.65 0.0879
3x95 0.320 0.410 0.125 15000 0.164 0.977 74.3 3.62 0.273 1.23 0.0811
3x120 0.253 0.325 0.121 14000 0.176 1.05 79.9 3.50 0.273 1.07 0.0766
3x150 0.206 0.264 0.117 13000 0.189 1.13 85.5 3.40 0.273 1.02 0.0730
3x185 0.164 0.211 0.113 12000 0.202 1.20 91.5 3.31 0.273 0.980 0.0686
3x240 0.125 0.161 0.109 11000 0.222 1.32 101 3.20 0.273 0.941 0.0639
3x300 0.100 0.130 0.106 10000 0.242 1.44 110 3.11 0.273 0.917 0.0606
3x400 0.0778 0.102 0.101 9100 0.267 1.59 121 3.02 0.273 0.896 0.0561
3x500 0.0617 0.0815 0.0969 8100 0.297 1.77 135 2.93 0.273 0.879 0.0520
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
79
Cu 19/33kV
MV cables with Longitudinal Water-Blocking System
10 9 8 7 6 5 4 3 2 1
Construction:
Application:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0
Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement
Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
80
Cu 19/33kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
81
Cu 19/33kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
82
Cu 19/33kV
Electrical parameters
No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz
(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)
3x50 0.387 0.496 0.143 18000 0.134 0.801 60.9 4.03 0.273 1.51 0.0977
3x70 0.268 0.344 0.134 16000 0.150 0.896 68.1 3.79 0.273 1.08 0.0902
3x95 0.193 0.248 0.125 15000 0.165 0.984 74.8 3.61 0.273 1.01 0.0801
3x120 0.153 0.197 0.120 14000 0.179 1.07 81.1 3.48 0.273 0.970 0.0757
3x150 0.124 0.160 0.116 13000 0.191 1.14 86.8 3.38 0.273 0.940 0.0722
3x185 0.0991 0.128 0.112 12000 0.207 1.32 97.3 3.28 0.273 0.917 0.0647
3x240 0.0754 0.0986 0.108 11000 0.228 1.36 103 3.17 0.273 0.891 0.0627
3x300 0.0601 0.0796 0.104 9700 0.249 1.48 113 3.08 0.273 0.876 0.0594
3x400 0.0470 0.0636 0.101 8800 0.275 1.64 125 2.99 0.273 0.865 0.0558
3x500 0.0373 0.0515 0.0974 8000 0.300 1.79 136 2.93 0.273 0.855 0.0525
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
83
Al 38/66kV
HV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 38/66 Min. temperature for laying (°C) 0
Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
84
Al 38/66kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]
1x120 12.8 13.0 41.6 116.3 0.25/2.6 57.9 3554 1150 900 3.6
1x150 14.2 12.0 41.0 116.3 0.25/2.6 57.3 3560 1150 850 4.5
1x185 15.9 12.0 42.7 116.3 0.25/2.6 59.1 3776 1200 900 5.6
1x240 18.1 12.0 44.9 116.3 0.25/2.7 61.4 4059 1250 950 7.2
1x300 20.3 11.0 45.1 116.3 0.25/2.7 61.6 4186 1250 950 9.0
1x400 23.0 11.0 47.8 116.3 0.25/2.8 64.6 4597 1300 1000 12.0
1x500 26.0 11.0 50.8 116.3 0.25/2.9 67.7 5094 1350 1050 15.0
1x630 29.7 11.0 54.5 116.3 0.25/3.0 71.7 5689 1450 1100 18.9
1x800 34.0 10.0 57.0 116.3 0.25/3.1 74.1 6255 1500 1150 24.0
1x1000 39.5 10.0 64.5 116.3 0.25/3.2 81.6 7476 1650 1250 30.0
1x1200 43.5 10.0 68.5 116.3 0.25/3.3 85.9 8289 1750 1300 36.0
1x1600 49.2 10.0 74.2 116.3 0.25/3.5 92.0 9773 1850 1400 48.0
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
85
Al 38/66kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
86
Al 38/66kV
Electrical parameters
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
87
Cu 38/66kV
HV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 38/66 Min. temperature for laying (°C) 0
Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
88
Cu 38/66kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]
1x120 12.8 13.0 41.6 116.3 0.25/2.6 57.9 4281 1158 900 8.4
1x150 14.2 12.0 41.0 116.3 0.25/2.6 57.3 4437 1146 850 10.5
1x185 15.9 12.0 42.7 116.3 0.25/2.6 59.1 4883 1182 900 13.0
1x240 18.1 12.0 44.9 116.3 0.25/2.7 61.4 5503 1228 950 16.8
1x300 20.3 11.0 45.1 116.3 0.25/2.7 61.6 6002 1232 950 21.0
1x400 23.0 11.0 47.8 116.3 0.25/2.8 64.6 6923 1292 1000 28.0
1x500 26.0 11.0 50.8 116.3 0.25/2.9 67.7 8041 1354 1050 35.0
1x630 29.7 11.0 54.5 116.3 0.25/3.0 71.7 9584 1434 1100 44.1
1x800 34.0 10.0 57.0 116.3 0.25/3.1 74.1 11348 1482 1150 56.0
1x1000 39.5 10.0 64.5 116.3 0.25/3.2 81.6 13688 1632 1250 70.0
1x1200 43.5 10.0 68.5 116.3 0.25/3.3 85.9 15738 1718 1300 84.0
1x1600 49.2 10.0 74.2 116.3 0.25/3.5 92.0 19698 1840 1400 112.0
1x2000 55.2 10.0 80.2 116.3 0.25/3.7 98.4 23680 1968 1500 140.0
1x2500 61.5 10.0 86.5 116.3 0.25/3.9 105.1 28579 2102 1600 175.0
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
89
Cu 38/66kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
90
Cu 38/66kV
Electrical parameters
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
91
Al 76/132kV
HV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 76/132 Min. temperature for laying (°C) 0
Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
92
Al 76/132kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]
1x150 14.2 18.0 53.0 116.3 0.25/3.0 70.1 4701 1400 1050 4.5
1x185 15.9 18.0 54.7 116.3 0.25/3.1 71.9 4952 1450 1100 5.6
1x240 18.1 18.0 56.9 116.3 0.25/3.1 74.3 5282 1500 1150 7.2
1x300 20.3 18.0 59.1 116.3 0.25/3.2 76.6 5639 1550 1150 9.0
1x400 23.0 18.0 61.8 116.3 0.25/3.3 79.5 6115 1600 1200 12.0
1x500 26.0 18.0 64.8 116.3 0.25/3.4 82.7 6681 1650 1250 15.0
1x630 29.7 18.0 68.5 116.3 0.25/3.5 86.6 7362 1750 1300 18.9
1x800 34.0 18.0 72.8 116.3 0.25/3.6 91.2 8256 1850 1400 24.0
1x1000 39.5 18.0 80.5 116.3 0.25/3.8 98.8 9667 2000 1500 30.0
1x1200 43.5 18.0 84.5 116.3 0.25/3.9 103.0 10585 2050 1550 36.0
1x1600 49.2 18.0 90.2 116.3 0.25/4.1 109.1 12222 2200 1650 48.0
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
93
Al 76/132kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
94
Al 76/132kV
Electrical parameters
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
95
Cu 76/132kV
HV cables with Longitudinal Water-Blocking System
9 8 7 6 5 4 3 2 1
Construction:
Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.
Properties:
Rated voltage U0/U (kV) 76/132 Min. temperature for laying (°C) 0
Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement
In air,shaded,no wind
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
96
Cu 76/132kV
Technical details
No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]
1x150 14.2 18.0 53.0 116.3 0.25/3.0 70.1 5579 1400 1050 10.5
1x185 15.9 18.0 54.7 116.3 0.25/3.1 71.9 6058 1450 1100 13.0
1x240 18.1 18.0 56.9 116.3 0.25/3.1 74.3 6726 1500 1150 16.8
1x300 20.3 18.0 59.1 116.3 0.25/3.2 76.6 7456 1550 1150 21.0
1x400 23.0 18.0 61.8 116.3 0.25/3.3 79.5 8440 1600 1200 28.0
1x500 26.0 18.0 64.8 116.3 0.25/3.4 82.7 9628 1650 1250 35.0
1x630 29.7 18.0 68.5 116.3 0.25/3.5 86.6 11257 1750 1300 44.1
1x800 34.0 18.0 72.8 116.3 0.25/3.6 91.2 13349 1850 1400 56.0
1x1000 39.5 18.0 80.5 116.3 0.25/3.8 98.8 15878 2000 1500 70.0
1x1200 43.5 18.0 84.5 116.3 0.25/3.9 103.0 18035 2050 1550 84.0
1x1600 49.2 18.0 90.2 116.3 0.25/4.1 109.1 22148 2200 1650 112.0
1x2000 55.2 18.0 96.2 116.3 0.25/4.3 115.5 26287 2300 1750 140.0
1x2500 61.5 18.0 102.5 116.3 0.25/4.5 122.2 31357 2450 1850 175.0
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
97
Cu 76/132kV
Current ratings
(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
98
Cu 76/132kV
Electrical parameters
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.
99
2016
06.2016/Product Catalogue MV and HV Cables Australia/Copyright
sales.au@nktcables.com
www.nktcables.com