Product Catalogue Australia

Medium and
High Voltage Cables

Member of the NKT Group / Story Bridge, Brisbane

www.nktcables.com
Table of contents

About nkt cables Australia

Profile ................................................................................................................................................... 2-3

MV cables with Longitudinal Water-Blocking System

Single core
Aluminium (Al) 1.9/3.3kV ...................................................................................................................... 4-7
Copper (Cu) 1.9/3.3kV .........................................................................................................................8-11
Aluminium (Al) 3.8/6.6kV ................................................................................................................... 12-15
Copper (Cu) 3.8/6.6kV ...................................................................................................................... 16-19
Aluminium (Al) 6.35/11kV ................................................................................................................. 20-23
Copper (Cu) 6.35/11kV ..................................................................................................................... 24-27
Aluminium (Al) 12.7/22kV ................................................................................................................. 28-31
Copper (Cu) 12.7/22kV ..................................................................................................................... 32-35
Aluminium (Al) 19/33kV .................................................................................................................... 36-39
Copper (Cu) 19/33kV ........................................................................................................................ 40-43

Three core
Aluminium (Al) 1.9/3.3kV .................................................................................................................. 44-47
Copper (Cu) 1.9/3.3kV ...................................................................................................................... 48-51
Aluminium (Al) 3.8/6.6kV .................................................................................................................. 52-55
Copper (Cu) 3.8/6.6kV ...................................................................................................................... 56-59
Aluminium (Al) 6.35/11kV ................................................................................................................. 60-63
Copper (Cu) 6.35/11kV ..................................................................................................................... 64-67
Aluminium (Al) 12.7/22kV ................................................................................................................. 68-71
Copper (Cu) 12.7/22kV ..................................................................................................................... 72-75
Aluminium (Al) 19/33kV .................................................................................................................... 76-79
Copper (Cu) 19/33 kV ....................................................................................................................... 80-83

HV cables with Longitudinal Water-Blocking System

Single core
Aluminium (Al) 38/66kV .................................................................................................................... 84-87
Copper (Cu) 38/66kV ........................................................................................................................ 88-91
Aluminium (Al) 76/132kV .................................................................................................................. 92-95
Copper (Cu) 76/132kV ...................................................................................................................... 96-99

All cables can be customised to the clients specific requirements.

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

1
Profile

nkt cables Australia

We think in solutions.
And deliver to meet your needs…

nkt cables Australia is a 100% subsidiary of nkt cables and a supplier of MV & HV power cable, overhead catenary
systems for Rail, MV & HV cable accessories and installation services to the Australian and New Zealand Markets.
nkt cables Australia has been in operation since 2010. We have seen significant growth each year and we are earning an
excellent reputation through our hard work, dedication and innovative solutions.

We also manufacture cable accessories from 3.3kV up to 550kV. Our accessories are a superior design due to the fact that
we utilise silicon compounds. This makes nkt accessories easier to install and a minimal number of parts in comparison to
other types on the market. All accessories are manufactured according to EN 50180/81, DIN 47636 and successfully passed
type testing to CENELEC HD 629.1/VDE 0278 629-1.

nkt cables Australia stock a comprehensive range of premium quality cable accessories at our Brisbane warehouse. The
products have been widely used in the Australian / New Zealand market and are approved and used by many utilities and
major clients globally.

nkt cables Australia also offer the knowledge, experience and expertise of a qualified team of jointers who are available to
travel throughout Australia & New Zealand. They are licensed to carry out jointing work up to 420kV as well as oil cable
joints / maintenance. All tooling required to successfully complete installation on joints and terminations is ready and
available for projects and breakdowns. We hold major breakdown contracts and have 24 hour service agreements in place
on our client’s networks.

33kV – Supply and Installation - Nyngan Solar Farm 220kV – Full Turn Key - NAaN Project – Auckland

nkt cables

nkt cables is a global front-line supplier to the energy sector. We develop, manufacture and market high quality cables and
solutions for the electrical construction, railway and automotive industries. We supply creative and sustainable products,
services and solutions for our customers.

Our manufacturing plants are amongst the most modern, flexible and cost-effective in the world and we invest heavily to
keep them at the highest technological level. Neutral CO2 emissions have a high priority and also waste prevention in our
brand new state-of-the-art factory in Cologne.

Our main focus is to be at the forefront of innovative products and solutions whilst caring for our environment.

In 2015 nkt cables had 3,208 employees and a turnover of around 1.2 Billion Euro. nkt cables is owned by NKT Holding
A/S (www.nkt.dk), which is listed on the Danish Stock Exchange. NKT Holding owns a group of companies, which spans a
number of industries and has production facilities on four continents. In 2015 NKT Holding had 9,078 employees.
Read more at www.nktcables.com
All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

2
nkt cables Ltd., Changzhou (NCL)

nkt cables Ltd., Changzhou (“NCL”) is a wholly-owned subsidiary of nkt cables Group with a registered
capital of RMB ¥628,800,000. Drawing on the advanced German industrial technology and scientific
management of its parent company, NCL utilizes these factors to the benefit of its customers. Our product range
covers three areas: XLPE insulated power cables at rated voltages of 3.3kV-110kV, accessories and electrifying
wire rod for railway contact networks. We also provide our customers with complete railway system solutions.

Location: Changzhou, Jiangsu


Province, PRC
Area: 120,000m²
Employees: 360
Product range: MV/HV cables 3.3-110kV, railway OCS products, cable accessories

nkt cables Ltd., Changzhou Hejian Branch (NCC)

nkt cables Ltd., Changzhou Hejian Branch (“NCC”) is a branch company of nkt cables Ltd., Changzhou.
NCL acquired NCC in 2008 with the factory becoming fully operational in 2010. NCC possesses the most
advanced production lines and testing equipment for high voltage cables sourced from Finland, Germany,
Switzerland, France and Italy amongst others. This state of the art equipment is the foundation for high
quality manufacturing of cables.

Location: Hejian, Hebei


Province, PRC
Area: 90,000m²
Employees: 180
Product range: MV/HV cables 11-220kV

NCC

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

3
Al 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semi conductive 7 Non conductive


water-blocking tape water-blocking tape

Insulation screen Cu wire screen


2 Conductor screen 4 6 8 PVC inner sheath
and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0

Test voltage (kV) 7.6 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25 ℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

4
Al 1.9/3.3kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x25 6.0 2 11.4 47.2 1.5/1.6 24.5 992 614 368

1x35 6.9 2 12.3 47.2 1.5/1.6 25.4 1042 636 382

1x50 8.1 2 13.5 47.2 1.5/1.6 26.6 1110 666 400

1x70 9.6 2 15.0 47.2 1.5/1.6 28.1 1208 704 422

1x95 11.3 2 16.7 47.2 1.5/1.6 29.8 1325 746 448

1x120 12.8 2 18.2 70.3 1.5/1.6 31.3 1649 784 470

1x150 14.2 2 19.6 70.3 1.5/1.6 32.7 1774 819 491

1x185 15.9 2 21.3 70.3 1.5/1.6 34.4 1928 861 517

1x240 18.1 2 23.5 70.3 1.5/1.6 36.6 2128 916 550

1x300 20.3 2 25.7 70.3 1.5/1.6 38.8 2355 971 583

1x400 23.0 2 28.4 70.2 1.5/1.6 40.7 2653 1019 611

1x500 26.0 2.2 32.4 70.2 1.5/1.6 44.7 3111 1119 671

1x630 29.7 2.4 36.5 70.2 1.5/1.6 48.8 3605 1221 733

1x800 34.0 2.6 41.2 70.2 1.5/1.6 53.6 4296 1340 804

1x1000 39.5 2.8 48.7 70.2 1.5/1.8 61.6 5442 1539 923

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

5
Al 1.9/3.3kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x25 110 130 100 105 75 110 110 105 95 100 95 85 2.37 6.9

1x35 135 160 120 130 90 135 135 130 115 115 115 100 3.31 6.9

1x50 160 190 150 160 110 160 160 155 135 140 135 125 4.73 6.9

1x70 205 240 185 200 135 195 195 190 165 165 165 150 6.62 6.9

1x95 245 290 230 245 165 230 230 225 195 195 195 185 8.99 6.9

1x120 285 330 265 280 190 260 255 255 220 215 220 210 11.4 10

1x150 320 370 300 320 220 290 285 285 245 240 250 235 14.2 10

1x185 365 420 340 365 250 325 315 325 275 265 280 270 17.5 10

1x240 430 490 405 435 290 370 360 375 315 300 325 310 22.7 10

1x300 490 550 465 495 330 415 395 420 350 335 365 350 28.4 10

1x400 570 625 540 580 390 465 440 480 395 370 415 410 37.8 10

1x500 655 715 635 680 450 525 485 545 445 410 470 470 47.3 10

1x630 745 800 730 780 510 580 535 615 490 445 525 530 59.6 10

1x800 845 890 835 895 605 640 580 685 540 485 585 615 75.7 10

1x1000 985 1005 995 1065 705 725 635 795 590 525 655 705 94.6 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

6
Al 1.9/3.3kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x25 1.20 1.54 1.54 0.141 0.158 0.201 9400 0.296 0.301 4.61 1.93 0.392 2.3 0.0676

1x35 0.868 1.11 1.11 0.136 0.154 0.197 8600 0.326 0.325 5.00 1.89 0.392 1.66 0.0623

1x50 0.641 0.821 0.821 0.131 0.149 0.194 7700 0.365 0.368 5.52 1.84 0.392 1.19 0.0591

1x70 0.443 0.568 0.568 0.124 0.141 0.183 6600 0.413 0.419 6.39 1.76 0.392 0.837 0.0572

1x95 0.320 0.410 0.410 0.116 0.132 0.179 5900 0.468 0.475 7.23 1.72 0.392 0.613 0.0525

1x120 0.253 0.325 0.325 0.110 0.125 0.173 5300 0.516 0.524 7.92 1.70 0.269 0.516 0.0505

1x150 0.206 0.265 0.264 0.108 0.121 0.170 5000 0.561 0.568 8.62 1.68 0.269 0.469 0.0480

1x185 0.164 0.211 0.211 0.104 0.119 0.164 4500 0.616 0.613 9.32 1.59 0.269 0.427 0.0445

1x240 0.125 0.161 0.161 0.101 0.118 0.161 4200 0.687 0.665 10.0 1.38 0.269 0.395 0.0420

1x300 0.100 0.130 0.129 0.0985 0.115 0.159 4000 0.757 0.690 10.3 1.28 0.269 0.370 0.0410

1x400 0.0778 0.102 0.101 0.0976 0.113 0.153 3700 0.844 0.726 11.0 1.26 0.269 0.348 0.0393

1x500 0.0605 0.0803 0.0791 0.0961 0.109 0.151 3200 0.884 0.778 11.6 1.22 0.269 0.331 0.0384

1x630 0.0469 0.0637 0.0620 0.0941 0.107 0.149 2800 0.911 0.853 13.1 1.21 0.269 0.318 0.0363

1x800 0.0367 0.0517 0.0495 0.0899 0.104 0.147 2300 0.954 0.947 14.3 1.20 0.269 0.307 0.0333

1x1000 0.0291 0.0392 0.0388 0.0865 0.103 0.141 2000 1.062 1.06 16.9 1.17 0.269 0.300 0.0332

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

7
Cu 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0

Test voltage (kV) 7.6 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

8
Cu 1.9/3.3kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x25 6.0 2 11.4 47.2 1.5/1.6 24.5 1146 614 368

1x35 6.9 2 12.3 47.2 1.5/1.6 25.4 1253 636 382

1x50 8.1 2 13.5 47.2 1.5/1.6 26.6 1397 666 400

1x70 9.6 2 15.0 47.2 1.5/1.6 28.1 1612 704 422

1x95 11.3 2 16.7 47.2 1.5/1.6 29.8 1886 746 448

1x120 12.8 2 18.2 70.3 1.5/1.6 31.3 2376 784 470

1x150 14.2 2 19.6 70.3 1.5/1.6 32.7 2652 819 491

1x185 15.9 2 21.3 70.3 1.5/1.6 34.4 3034 861 517

1x240 18.1 2 23.5 70.3 1.5/1.6 36.6 3572 916 550

1x300 20.3 2 25.7 70.3 1.5/1.6 38.8 4171 971 583

1x400 23.0 2 28.4 70.2 1.5/1.6 40.7 4978 1019 611

1x500 26.0 2.2 32.4 70.2 1.5/1.6 44.7 6058 1119 671

1x630 29.7 2.4 36.5 70.2 1.5/1.6 48.8 7500 1221 733

1x800 34.0 2.6 41.2 70.2 1.5/1.6 53.6 9389 1340 804

1x1000 39.5 2.8 48.7 70.2 1.5/1.8 61.6 11650 1539 923

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

9
Cu 1.9/3.3kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x25 140 170 130 140 95 145 145 140 125 125 125 110 3.57 6.9

1x35 175 205 160 170 120 175 175 170 150 150 150 135 5.00 6.9

1x50 210 245 195 205 140 205 205 200 175 175 175 160 7.15 6.9

1x70 260 305 245 260 180 245 245 245 210 205 210 200 10.0 6.9

1x95 315 365 295 315 215 290 285 290 245 240 250 235 13.6 6.9

1x120 360 415 340 360 240 330 320 330 275 265 280 270 17.1 10

1x150 405 460 385 410 280 365 350 370 305 290 315 305 21.4 10

1x185 460 520 440 470 315 405 385 415 340 320 350 345 26.4 10

1x240 535 600 520 555 370 460 435 475 385 360 405 395 34.3 10

1x300 605 665 590 635 430 510 475 535 425 390 450 455 42.9 10

1x400 690 745 680 730 490 565 520 600 470 425 505 515 57.2 10

1x500 785 830 780 835 555 625 565 670 515 465 565 575 71.5 10

1x630 875 915 880 945 620 680 605 745 555 490 615 640 90.0 10

1x800 985 1015 1005 1075 725 740 650 820 615 535 690 730 114 10

1x1000 1145 1125 1205 1285 850 835 700 955 655 565 750 850 143 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

10
Cu 1.9/3.3kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x25 0.727 0.927 0.927 0.141 0.159 0.203 9200 0.296 0.301 4.61 1.93 0.392 1.47 0.0701

1x35 0.524 0.668 0.668 0.135 0.153 0.198 8500 0.326 0.325 5.00 1.89 0.392 1.05 0.0673

1x50 0.387 0.494 0.494 0.129 0.142 0.190 7600 0.365 0.368 5.52 1.84 0.392 0.758 0.0615

1x70 0.268 0.342 0.342 0.121 0.136 0.185 6500 0.413 0.419 6.39 1.76 0.392 0.533 0.0586

1x95 0.193 0.247 0.247 0.114 0.129 0.176 5900 0.468 0.475 7.23 1.72 0.392 0.459 0.0511

1x120 0.153 0.196 0.195 0.109 0.121 0.171 5300 0.516 0.524 7.92 1.70 0.269 0.416 0.0485

1x150 0.124 0.160 0.159 0.106 0.118 0.167 4800 0.561 0.568 8.62 1.68 0.269 0.388 0.0441

1x185 0.0991 0.128 0.127 0.103 0.115 0.163 4400 0.616 0.613 9.32 1.59 0.269 0.363 0.0401

1x240 0.0754 0.0982 0.0973 0.101 0.113 0.162 4000 0.687 0.665 10.0 1.38 0.269 0.341 0.0398

1x300 0.0601 0.0792 0.0781 0.0991 0.110 0.160 3900 0.757 0.690 10.3 1.28 0.269 0.330 0.0368

1x400 0.0470 0.0632 0.0618 0.0981 0.105 0.159 3600 0.844 0.726 11.0 1.26 0.269 0.318 0.0375

1x500 0.0366 0.0508 0.0489 0.0972 0.104 0.156 3500 0.884 0.778 11.6 1.22 0.269 0.307 0.0353

1x630 0.0283 0.0413 0.0390 0.0953 0.103 0.151 3200 0.911 0.853 13.1 1.21 0.269 0.299 0.0331

1x800 0.0221 0.0349 0.0318 0.0926 0.102 0.149 2700 0.954 0.947 14.3 1.20 0.269 0.294 0.0318

1x1000 0.0176 0.0248 0.0241 0.0897 0.100 0.142 2300 1.062 1.06 16.9 1.17 0.269 0.288 0.0306

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

11
Al 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semiconducting 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0

Test voltage (kV) 15.2 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

12
Al 3.8/6.6kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x25 6.0 2.5 12.4 47.2 1.5/1.6 25.5 1012 639 383

1x35 6.9 2.5 13.3 47.2 1.5/1.6 26.4 1063 661 397

1x50 8.1 2.5 14.5 47.2 1.5/1.6 27.6 1132 691 415

1x70 9.6 2.5 16.0 47.2 1.5/1.6 29.1 1232 729 437

1x95 11.3 2.5 17.7 47.2 1.5/1.6 30.8 1352 771 463

1x120 12.8 2.5 19.2 70.3 1.5/1.6 32.3 1677 809 485

1x150 14.2 2.5 20.6 70.3 1.5/1.6 33.7 1804 844 506

1x185 15.9 2.5 22.3 70.3 1.5/1.6 35.4 1960 886 532

1x240 18.1 2.6 24.7 70.3 1.5/1.6 37.8 2173 946 568

1x300 20.3 2.8 27.3 70.3 1.5/1.6 40.4 2427 1011 607

1x400 23.0 3.0 30.4 70.2 1.5/1.6 42.7 2756 1069 641

1x500 26.0 3.2 34.4 70.2 1.5/1.6 46.7 3218 1169 701

1x630 29.7 3.2 38.1 70.2 1.5/1.6 50.4 3696 1261 757

1x800 34.0 3.2 42.4 70.2 1.5/1.7 54.9 4373 1373 824

1x1000 39.5 3.2 49.5 70.2 1.5/1.8 62.4 5488 1559 935

1x1200 43.5 3.2 53.5 70.2 1.5/1.8 66.4 5642 1659 995

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

13
Al 3.8/6.6kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x25 115 135 105 110 79 115 115 110 100 105 100 90 2.37 6.9

1x35 140 165 125 135 95 140 140 135 120 120 120 105 3.31 6.9

1x50 165 195 155 165 115 165 165 160 140 145 140 130 4.73 6.9

1x70 210 245 190 205 140 200 200 195 170 170 170 155 6.62 6.9

1x95 250 295 235 250 170 235 235 230 200 200 200 190 8.99 6.9

1x120 290 335 270 285 195 265 260 260 225 220 225 215 11.4 10

1x150 325 375 305 325 225 295 290 290 250 245 255 240 14.2 10

1x185 370 425 345 370 255 330 320 330 280 270 285 275 17.5 10

1x240 435 495 410 440 295 375 365 380 320 305 330 315 22.7 10

1x300 495 555 470 500 335 420 400 425 355 340 370 355 28.4 10

1x400 575 630 545 585 395 470 445 485 400 375 420 415 37.8 10

1x500 660 720 640 685 455 530 490 550 450 415 475 475 47.3 10

1x630 750 805 735 785 515 585 540 620 495 450 530 535 59.6 10

1x800 850 895 840 900 610 645 585 690 545 490 590 620 75.7 10

1x1000 990 1010 1000 1070 710 730 640 800 595 530 660 710 94.6 10

1x1200 1080 1080 1100 1180 780 780 675 870 635 555 715 775 114 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

14
Al 3.8/6.6kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x25 1.20 1.54 1.54 0.147 0.162 0.208 9500 0.255 0.304 4.63 1.97 0.392 2.3 0.0785

1x35 0.868 1.11 1.11 0.138 0.153 0.199 8700 0.278 0.332 5.04 1.92 0.392 1.66 0.0709

1x50 0.641 0.821 0.821 0.135 0.150 0.196 7800 0.309 0.369 5.61 1.87 0.392 1.19 0.0676

1x70 0.443 0.568 0.568 0.124 0.140 0.185 6800 0.353 0.422 6.41 1.82 0.392 0.837 0.0591

1x95 0.320 0.410 0.410 0.118 0.133 0.179 6000 0.400 0.478 7.26 1.77 0.392 0.613 0.0543

1x120 0.253 0.325 0.325 0.114 0.129 0.175 5500 0.439 0.524 7.96 1.74 0.269 0.516 0.0512

1x150 0.206 0.265 0.264 0.110 0.126 0.171 5100 0.477 0.569 8.66 1.72 0.269 0.469 0.0485

1x185 0.164 0.211 0.211 0.108 0.123 0.168 4700 0.518 0.618 9.40 1.70 0.269 0.427 0.0461

1x240 0.125 0.161 0.161 0.104 0.119 0.165 4300 0.561 0.670 10.2 1.62 0.269 0.395 0.0437

1x300 0.100 0.130 0.129 0.102 0.118 0.163 4100 0.582 0.695 10.6 1.50 0.269 0.370 0.0427

1x400 0.0778 0.102 0.101 0.0989 0.114 0.160 3900 0.613 0.731 11.1 1.39 0.269 0.348 0.0395

1x500 0.0605 0.0803 0.0791 0.0963 0.112 0.157 3700 0.654 0.781 11.9 1.29 0.269 0.331 0.0379

1x630 0.0469 0.0637 0.0620 0.0938 0.109 0.155 3300 0.725 0.866 13.2 1.28 0.269 0.318 0.0358

1x800 0.0367 0.0517 0.0495 0.0909 0.106 0.152 2900 0.818 0.976 14.8 1.26 0.269 0.307 0.0343

1x1000 0.0291 0.0392 0.0388 0.089 0.104 0.150 2500 0.979 1.17 17.8 1.25 0.269 0.300 0.0332

1x1200 0.0247 0.0329 0.0323 0.0882 0.103 0.149 2300 1.06 1.26 19.2 1.24 0.269 0.295 0.0326

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

15
Cu 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0

Test voltage (kV) 15.2 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

16
Cu 3.8/6.6kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x25 6.0 2.5 12.4 47.2 1.5/1.6 25.5 1166 639 383

1x35 6.9 2.5 13.3 47.2 1.5/1.6 26.4 1274 661 397

1x50 8.1 2.5 14.5 47.2 1.5/1.6 27.6 1419 691 415

1x70 9.6 2.5 16.0 47.2 1.5/1.6 29.1 1636 729 437

1x95 11.3 2.5 17.7 47.2 1.5/1.6 30.8 1912 771 463

1x120 12.8 2.5 19.2 70.3 1.5/1.6 32.3 2404 809 485

1x150 14.2 2.5 20.6 70.3 1.5/1.6 33.7 2682 844 506

1x185 15.9 2.5 22.3 70.3 1.5/1.6 35.4 3066 886 532

1x240 18.1 2.6 24.7 70.3 1.5/1.6 37.8 3617 946 568

1x300 20.3 2.8 27.3 70.3 1.5/1.6 40.4 4243 1011 607

1x400 23.0 3.0 30.4 70.2 1.5/1.6 42.7 5081 1069 641

1x500 26.0 3.2 34.4 70.2 1.5/1.6 46.7 6166 1169 701

1x630 29.7 3.2 38.1 70.2 1.5/1.6 50.4 7591 1261 757

1x800 34.0 3.2 42.4 70.2 1.5/1.7 54.9 9466 1373 824

1x1000 39.5 3.2 49.5 70.2 1.5/1.8 62.4 11697 1559 935

1x1200 43.5 3.2 53.5 70.2 1.5/1.8 66.4 11851 1659 995

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

17
Cu 3.8/6.6kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x25 145 175 135 145 100 150 150 145 130 130 130 115 3.57 6.9

1x35 180 210 165 175 125 180 180 175 155 155 155 140 5.00 6.9

1x50 215 250 200 210 145 210 210 205 180 180 180 165 7.15 6.9

1x70 265 310 250 265 185 250 250 250 215 210 215 205 10.0 6.9

1x95 320 370 300 320 220 295 290 295 250 245 255 240 13.6 6.9

1x120 365 420 345 365 245 335 325 335 280 270 285 275 17.1 10

1x150 410 465 390 415 285 370 355 375 310 295 320 310 21.4 10

1x185 470 525 445 475 320 410 390 420 345 325 355 350 26.4 10

1x240 545 605 525 560 375 465 440 480 390 365 410 400 34.3 10

1x300 615 670 595 640 435 515 480 540 430 395 455 460 42.9 10

1x400 700 750 685 735 495 570 525 605 475 430 510 520 57.2 10

1x500 790 835 785 840 560 630 570 675 520 470 570 580 71.5 10

1x630 880 920 885 950 625 685 610 750 560 495 620 645 90.0 10

1x800 990 1020 1010 1080 730 745 655 825 620 540 695 735 114 10

1x1000 1150 1130 1210 1290 855 840 705 960 660 570 755 855 143 10

1x1200 1230 1200 1320 1410 925 885 735 1030 700 595 810 920 171 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

18
Cu 3.8/6.6kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x25 0.727 0.927 0.927 0.147 0.162 0.207 9400 0.256 0.305 4.64 1.97 0.392 1.47 0.0771

1x35 0.524 0.668 0.668 0.141 0.156 0.202 8600 0.279 0.333 5.06 1.92 0.392 1.05 0.0733

1x50 0.387 0.494 0.494 0.134 0.150 0.195 7800 0.311 0.371 5.64 1.87 0.392 0.758 0.0678

1x70 0.268 0.342 0.342 0.129 0.144 0.190 6700 0.359 0.428 6.51 1.81 0.392 0.533 0.0632

1x95 0.193 0.247 0.247 0.120 0.135 0.181 6000 0.404 0.482 7.33 1.77 0.392 0.459 0.0550

1x120 0.153 0.196 0.195 0.113 0.128 0.174 5400 0.447 0.534 8.11 1.74 0.269 0.416 0.0505

1x150 0.124 0.160 0.159 0.110 0.125 0.171 5000 0.486 0.580 8.81 1.72 0.269 0.388 0.0480

1x185 0.0991 0.128 0.127 0.106 0.122 0.167 4500 0.533 0.636 9.67 1.69 0.269 0.363 0.0455

1x240 0.0754 0.0982 0.0973 0.103 0.118 0.164 4200 0.578 0.690 10.5 1.61 0.269 0.341 0.0420

1x300 0.0601 0.0792 0.0781 0.101 0.117 0.162 4000 0.601 0.718 10.9 1.49 0.269 0.330 0.0410

1x400 0.0470 0.0632 0.0618 0.0987 0.114 0.160 3800 0.636 0.759 11.5 1.38 0.269 0.318 0.0396

1x500 0.0366 0.0508 0.0489 0.0968 0.112 0.158 3600 0.662 0.790 12.0 1.29 0.269 0.307 0.0384

1x630 0.0283 0.0413 0.0390 0.0943 0.110 0.155 3300 0.733 0.875 13.3 1.28 0.269 0.299 0.0363

1x800 0.0221 0.0349 0.0318 0.0896 0.105 0.151 2800 0.862 1.03 15.6 1.26 0.269 0.294 0.0333

1x1000 0.0176 0.0248 0.0241 0.0890 0.104 0.150 2500 0.979 1.17 17.8 1.25 0.269 0.288 0.0332

1x1200 0.0151 0.0210 0.0202 0.0882 0.103 0.149 2300 1.06 1.26 19.2 1.24 0.269 0.285 0.0326

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

19
Al 6.35/11kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0

Test voltage (kV) 25.5 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

20
Al 6.35/11kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x25 6.0 3.4 14.2 47.2 1.5/1.6 27.3 1082 684 410

1x35 6.9 3.4 15.1 47.2 1.5/1.6 28.2 1136 706 424

1x50 8.1 3.4 16.3 47.2 1.5/1.6 29.4 1207 736 442

1x70 9.6 3.4 17.8 47.2 1.5/1.6 30.9 1311 774 464

1x95 11.3 3.4 19.5 70.3 1.5/1.6 32.6 1653 816 490

1x120 12.8 3.4 21.0 70.3 1.5/1.6 34.1 1764 854 512

1x150 14.2 3.4 22.4 70.3 1.5/1.6 35.5 1896 889 533

1x185 15.9 3.4 24.1 70.3 1.5/1.6 37.2 2056 931 559

1x240 18.1 3.4 26.3 70.3 1.5/1.6 39.4 2264 986 592

1x300 20.3 3.4 28.5 70.2 1.5/1.6 40.8 2487 1021 613

1x400 23.0 3.4 31.2 70.2 1.5/1.6 43.5 2807 1089 653

1x500 26.0 3.4 34.8 70.2 1.5/1.6 47.1 3246 1179 707

1x630 29.7 3.4 38.5 70.2 1.5/1.6 50.8 3726 1271 763

1x800 34.0 3.4 42.8 70.2 1.5/1.7 55.3 4406 1383 830

1x1000 39.5 3.4 49.9 70.2 1.5/1.8 62.8 5526 1569 941

1x1200 43.5 3.4 53.9 70.2 1.5/1.8 66.9 6237 1672 1003

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

21
Al 6.35/11kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x25 115 135 105 115 80 115 115 115 100 105 100 91 2.37 6.9

1x35 140 165 130 135 96 140 140 135 120 120 120 110 3.31 6.9

1x50 170 200 155 165 115 165 165 160 145 145 140 130 4.73 6.9

1x70 210 245 195 205 145 200 200 195 175 170 170 160 6.62 6.9

1x95 255 295 235 250 170 235 235 230 205 200 200 190 8.99 10

1x120 290 335 270 290 200 265 260 260 225 225 230 220 11.4 10

1x150 330 375 305 325 225 295 290 295 255 250 255 245 14.2 10

1x185 375 425 350 375 255 330 320 330 285 275 290 275 17.5 10

1x240 440 495 415 440 295 375 365 380 325 310 330 320 22.7 10

1x300 500 555 470 505 345 420 400 425 360 340 370 365 28.4 10

1x400 575 630 550 585 400 470 445 485 405 375 420 415 37.8 10

1x500 660 720 640 685 455 530 495 550 450 415 475 475 47.3 10

1x630 750 805 735 785 520 590 540 620 495 450 530 535 59.6 10

1x800 850 900 840 900 610 645 585 695 545 490 590 620 75.7 10

1x1000 990 1010 1000 1070 715 730 640 800 600 530 660 710 94.6 10

1x1200 1080 1080 1100 1180 780 780 675 870 640 560 715 775 114 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

22
Al 6.35/11kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x25 1.20 1.54 1.54 0.153 0.168 0.213 12000 0.203 0.405 10.3 2.62 0.392 2.30 0.0858

1x35 0.868 1.11 1.11 0.144 0.159 0.205 11000 0.220 0.439 11.1 2.54 0.392 1.66 0.0779

1x50 0.641 0.821 0.821 0.140 0.155 0.201 9900 0.243 0.486 12.3 2.46 0.392 1.19 0.074

1x70 0.443 0.568 0.568 0.129 0.144 0.190 8700 0.276 0.551 14.0 2.37 0.392 0.838 0.0649

1x95 0.320 0.410 0.410 0.123 0.138 0.184 7800 0.311 0.620 15.8 2.30 0.269 0.614 0.0597

1x120 0.253 0.325 0.325 0.118 0.133 0.179 7100 0.339 0.677 17.2 2.25 0.269 0.516 0.0562

1x150 0.206 0.265 0.264 0.115 0.13 0.176 6600 0.368 0.734 18.6 2.22 0.269 0.469 0.0533

1x185 0.164 0.211 0.211 0.111 0.127 0.172 6100 0.398 0.794 20.2 2.18 0.269 0.434 0.0498

1x240 0.125 0.161 0.161 0.107 0.123 0.168 5400 0.445 0.887 22.5 2.14 0.269 0.395 0.0464

1x300 0.100 0.130 0.129 0.105 0.12 0.165 4900 0.491 0.980 24.9 2.11 0.269 0.370 0.0443

1x400 0.0778 0.102 0.101 0.101 0.116 0.161 4400 0.548 1.09 27.8 2.08 0.269 0.348 0.0414

1x500 0.0605 0.0803 0.0790 0.0969 0.112 0.158 3900 0.620 1.24 31.4 2.05 0.269 0.331 0.0385

1x630 0.0469 0.0636 0.0620 0.0944 0.110 0.155 3500 0.687 1.37 34.8 2.02 0.269 0.317 0.0364

1x800 0.0367 0.0516 0.0495 0.0914 0.107 0.152 3100 0.774 1.54 39.2 2.00 0.269 0.308 0.0342

1x1000 0.0291 0.0392 0.0387 0.0897 0.105 0.151 2600 0.926 1.85 46.9 1.97 0.269 0.300 0.0337

1x1200 0.0247 0.0328 0.0323 0.0887 0.104 0.150 2400 0.998 1.99 50.6 1.96 0.269 0.295 0.0330

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

23
Cu 6.35/11kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0

Test voltage (kV) 25.5 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

24
Cu 6.35/11kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x25 6.0 3.4 14.2 47.2 1.5/1.6 27.3 1236 684 410

1x35 6.9 3.4 15.1 47.2 1.5/1.6 28.2 1346 706 424

1x50 8.1 3.4 16.3 47.2 1.5/1.6 29.4 1494 736 442

1x70 9.6 3.4 17.8 47.2 1.5/1.6 30.9 1716 774 464

1x95 11.3 3.4 19.5 70.3 1.5/1.6 32.6 2214 816 490

1x120 12.8 3.4 21.0 70.3 1.5/1.6 34.1 2491 854 512

1x150 14.2 3.4 22.4 70.3 1.5/1.6 35.5 2773 889 533

1x185 15.9 3.4 24.1 70.3 1.5/1.6 37.2 3162 931 559

1x240 18.1 3.4 26.3 70.3 1.5/1.6 39.4 3708 986 592

1x300 20.3 3.4 28.5 70.2 1.5/1.6 40.8 4303 1021 613

1x400 23.0 3.4 31.2 70.2 1.5/1.6 43.5 5133 1089 653

1x500 26.0 3.4 34.8 70.2 1.5/1.6 47.1 6194 1179 707

1x630 29.7 3.4 38.5 70.2 1.5/1.6 50.8 7621 1271 763

1x800 34.0 3.4 42.8 70.2 1.5/1.7 55.3 9499 1383 830

1x1000 39.5 3.4 49.9 70.2 1.5/1.8 62.8 11735 1569 941

1x1200 43.5 3.4 53.9 70.2 1.5/1.8 66.9 13683 1672 1003

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

25
Cu 6.35/11kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x25 150 175 140 145 105 150 150 145 130 130 130 115 3.57 6.9

1x35 180 210 170 180 125 180 180 175 155 155 155 140 5.00 6.9

1x50 215 250 200 215 150 210 210 205 180 180 180 165 7.15 6.9

1x70 270 310 250 270 185 250 250 250 215 215 215 205 10.0 6.9

1x95 325 370 300 320 220 295 290 295 255 245 255 240 13.6 10

1x120 370 420 350 370 255 335 325 335 285 275 290 280 17.1 10

1x150 415 470 395 420 290 370 355 375 315 300 320 310 21.4 10

1x185 475 530 450 480 325 415 395 420 350 330 360 350 26.4 10

1x240 550 605 525 565 375 470 440 485 395 365 410 405 34.3 10

1x300 620 675 600 640 440 520 480 540 435 400 460 465 42.9 10

1x400 705 755 690 735 500 575 525 605 475 435 510 520 57.2 10

1x500 790 835 785 840 560 630 570 675 525 470 570 580 71.5 10

1x630 880 920 890 950 625 685 610 750 565 500 625 645 90.0 10

1x800 990 1020 1010 1090 730 745 655 825 620 540 695 735 114 10

1x1000 1150 1130 1210 1290 855 840 705 960 660 570 755 855 143 10

1x1200 1230 1200 1320 1420 925 885 735 1030 700 595 815 920 171 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

26
Cu 6.35/11kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x25 0.727 0.927 0.927 0.152 0.168 0.213 12000 0.203 0.406 10.3 2.62 0.392 1.47 0.0654

1x35 0.524 0.668 0.668 0.146 0.162 0.207 11000 0.221 0.441 11.2 2.54 0.392 1.05 0.0593

1x50 0.387 0.494 0.494 0.140 0.155 0.200 9900 0.244 0.488 12.4 2.46 0.392 0.758 0.0536

1x70 0.268 0.342 0.342 0.133 0.149 0.194 8600 0.280 0.559 14.2 2.36 0.392 0.533 0.0479

1x95 0.193 0.247 0.247 0.122 0.137 0.183 7700 0.314 0.626 15.9 2.30 0.269 0.456 0.0594

1x120 0.153 0.196 0.195 0.118 0.133 0.179 6900 0.350 0.697 17.7 2.24 0.269 0.416 0.0566

1x150 0.124 0.160 0.159 0.114 0.129 0.175 6400 0.374 0.747 19.0 2.21 0.269 0.388 0.0527

1x185 0.0991 0.128 0.127 0.110 0.125 0.171 5900 0.409 0.817 20.7 2.17 0.269 0.369 0.0489

1x240 0.0754 0.0981 0.0973 0.106 0.121 0.167 5300 0.458 0.913 23.2 2.13 0.269 0.346 0.0456

1x300 0.0601 0.0791 0.0781 0.103 0.119 0.164 4800 0.507 1.01 25.7 2.10 0.269 0.331 0.0434

1x400 0.0470 0.0631 0.0617 0.100 0.116 0.161 4200 0.569 1.13 28.8 2.07 0.269 0.318 0.0414

1x500 0.0366 0.0507 0.0489 0.0974 0.113 0.158 3800 0.627 1.25 31.8 2.04 0.269 0.308 0.0391

1x630 0.0283 0.0413 0.0390 0.0948 0.110 0.156 3500 0.694 1.38 35.2 2.02 0.269 0.299 0.0369

1x800 0.0221 0.0348 0.0318 0.0901 0.105 0.151 3000 0.816 1.63 41.3 1.99 0.269 0.293 0.0339

1x1000 0.0176 0.0247 0.0241 0.0897 0.105 0.151 2600 0.926 1.85 46.9 1.97 0.269 0.289 0.0337

1x1200 0.0151 0.0210 0.0202 0.0887 0.104 0.150 2400 0.998 1.99 50.6 1.96 0.269 0.286 0.0330

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

27
Al 12.7/22kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0

Test voltage (kV) 50 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

28
Al 12.7/22kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x35 6.9 5.5 19.3 70.3 1.5/1.6 32.4 1540 811 487

1x50 8.1 5.5 20.5 70.3 1.5/1.6 33.6 1619 841 505

1x70 9.6 5.5 22.0 70.3 1.5/1.6 35.1 1733 879 527

1x95 11.3 5.5 23.7 70.3 1.5/1.6 36.8 1867 921 553

1x120 12.8 5.5 25.2 70.3 1.5/1.6 38.3 1987 959 575

1x150 14.2 5.5 26.6 70.3 1.5/1.6 39.7 2128 994 596

1x185 15.9 5.5 28.3 70.2 1.5/1.6 40.6 2286 1016 610

1x240 18.1 5.5 30.5 70.2 1.5/1.6 42.8 2508 1071 643

1x300 20.3 5.5 32.7 70.2 1.5/1.6 45.0 2756 1126 676

1x400 23.0 5.5 35.4 70.2 1.5/1.6 47.7 3093 1194 716

1x500 26.0 5.5 39.0 70.2 1.5/1.6 51.4 3559 1285 771

1x630 29.7 5.5 42.7 70.2 1.5/1.7 55.2 4074 1381 828

1x800 34.0 5.5 47.0 70.2 1.5/1.8 59.7 4777 1491 895

1x1000 39.5 5.5 54.1 70.2 1.5/1.9 67.2 5966 1680 1008

1x1200 43.5 5.5 58.1 70.2 1.5/2.0 71.3 6704 1784 1070

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

29
Al 12.7/22kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x35 145 165 135 140 100 140 140 135 120 125 120 110 3.31 10

1x50 175 200 160 170 120 165 165 160 145 145 140 135 4.73 10

1x70 215 245 200 210 150 200 200 195 175 175 175 165 6.62 10

1x95 260 295 240 255 180 235 235 230 205 205 205 195 8.99 10

1x120 295 335 275 295 205 265 260 260 230 230 235 220 11.4 10

1x150 335 375 310 330 230 295 290 295 260 250 260 245 14.2 10

1x185 380 425 355 380 270 330 320 330 285 280 290 285 17.5 10

1x240 445 495 420 445 310 380 365 380 330 315 335 330 22.7 10

1x300 505 555 480 510 350 420 405 430 365 345 375 370 28.4 10

1x400 580 630 555 590 405 475 450 485 410 385 425 420 37.8 10

1x500 670 720 645 690 460 530 495 555 455 420 480 475 47.3 10

1x630 760 805 740 790 545 590 540 625 505 460 540 555 59.6 10

1x800 855 900 850 905 615 650 590 695 545 495 590 620 75.7 10

1x1000 995 1010 1000 1070 715 730 645 800 610 540 670 715 94.6 10

1x1200 1090 1090 1110 1190 785 785 680 870 650 565 725 775 114 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

30
Al 12.7/22kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x35 0.868 1.11 1.11 0.156 0.171 0.216 15000 0.157 0.626 31.8 3.62 0.269 1.67 0.0919

1x50 0.641 0.821 0.821 0.151 0.166 0.211 14000 0.172 0.685 34.8 3.47 0.269 1.19 0.0869

1x70 0.443 0.568 0.568 0.140 0.155 0.201 13000 0.192 0.768 39.0 3.30 0.269 0.838 0.0769

1x95 0.320 0.410 0.410 0.133 0.148 0.194 11000 0.214 0.855 43.4 3.17 0.269 0.620 0.0708

1x120 0.253 0.325 0.325 0.128 0.143 0.189 10000 0.232 0.926 47.0 3.08 0.269 0.522 0.0667

1x150 0.206 0.264 0.264 0.124 0.139 0.185 9700 0.250 0.997 50.7 3.01 0.269 0.476 0.0633

1x185 0.164 0.211 0.211 0.120 0.136 0.181 9000 0.269 1.07 54.5 2.95 0.269 0.434 0.0593

1x240 0.125 0.161 0.161 0.116 0.131 0.177 8100 0.298 1.19 60.4 2.87 0.269 0.395 0.0551

1x300 0.100 0.129 0.129 0.112 0.128 0.173 7400 0.327 1.30 66.3 2.81 0.269 0.370 0.0527

1x400 0.0778 0.102 0.101 0.108 0.123 0.169 6700 0.363 1.45 73.5 2.75 0.269 0.348 0.0488

1x500 0.0605 0.0800 0.0790 0.104 0.119 0.164 5900 0.407 1.62 82.4 2.69 0.269 0.331 0.0453

1x630 0.0469 0.0633 0.0619 0.101 0.116 0.161 5400 0.448 1.79 90.9 2.64 0.269 0.318 0.0427

1x800 0.0367 0.0512 0.0493 0.0971 0.112 0.158 4800 0.502 2.00 102 2.60 0.269 0.308 0.0398

1x1000 0.0291 0.0391 0.0387 0.0944 0.110 0.155 4000 0.597 2.38 121 2.54 0.269 0.300 0.0386

1x1200 0.0247 0.0328 0.0323 0.0931 0.108 0.154 3800 0.641 2.56 130 2.52 0.269 0.295 0.0376

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

31
Cu 12.7/22kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0

Test voltage (kV) 50 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

32
Cu 12.7/22kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x35 6.9 5.5 19.3 70.3 1.5/1.6 32.4 1751 811 487

1x50 8.1 5.5 20.5 70.3 1.5/1.6 33.6 1906 841 505

1x70 9.6 5.5 22.0 70.3 1.5/1.6 35.1 2137 879 527

1x95 11.3 5.5 23.7 70.3 1.5/1.6 36.8 2427 921 553

1x120 12.8 5.5 25.2 70.3 1.5/1.6 38.3 2714 959 575

1x150 14.2 5.5 26.6 70.3 1.5/1.6 39.7 3005 994 596

1x185 15.9 5.5 28.3 70.2 1.5/1.6 40.6 3392 1016 610

1x240 18.1 5.5 30.5 70.2 1.5/1.6 42.8 3952 1071 643

1x300 20.3 5.5 32.7 70.2 1.5/1.6 45.0 4573 1126 676

1x400 23.0 5.5 35.4 70.2 1.5/1.6 47.7 5419 1194 716

1x500 26.0 5.5 39.0 70.2 1.5/1.6 51.4 6506 1285 771

1x630 29.7 5.5 42.7 70.2 1.5/1.7 55.2 7969 1381 828

1x800 34.0 5.5 47.0 70.2 1.5/1.8 59.7 9870 1491 895

1x1000 39.5 5.5 54.1 70.2 1.5/1.9 67.2 12174 1680 1008

1x1200 43.5 5.5 58.1 70.2 1.5/2.0 71.3 14150 1784 1070

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

33
Cu 12.7/22kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x35 185 210 175 185 130 180 180 175 155 155 155 145 5.00 10

1x50 220 250 205 220 155 210 210 205 185 180 180 170 7.15 10

1x70 275 310 255 270 195 250 250 250 220 215 220 210 10.0 10

1x95 330 370 310 325 230 295 290 295 260 250 260 250 13.6 10

1x120 375 420 355 375 260 335 325 335 290 280 295 280 17.1 10

1x150 425 470 400 425 295 370 360 375 320 305 325 315 21.4 10

1x185 480 530 455 485 345 415 395 420 355 335 365 365 26.4 10

1x240 560 605 535 570 395 470 445 485 400 375 420 415 34.3 10

1x300 630 675 610 650 445 520 485 540 440 405 465 465 42.9 10

1x400 715 755 700 745 505 575 530 610 490 445 520 525 57.2 10

1x500 800 840 795 850 570 635 575 680 530 475 575 585 71.5 10

1x630 895 925 900 960 665 695 615 755 575 510 635 675 90.0 10

1x800 1010 1030 1030 1110 740 750 660 835 615 540 690 745 114 10

1x1000 1160 1140 1220 1300 865 845 710 965 680 580 775 860 143 10

1x1200 1250 1210 1330 1420 935 895 745 1040 720 610 835 925 171 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

34
Cu 12.7/22kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x35 0.524 0.668 0.668 0.158 0.173 0.219 15000 0.157 0.628 31.9 3.62 0.269 1.05 0.0935

1x50 0.387 0.494 0.494 0.150 0.166 0.211 14000 0.172 0.688 34.9 3.46 0.269 0.758 0.0869

1x70 0.268 0.342 0.342 0.142 0.157 0.203 12000 0.195 0.778 39.5 3.29 0.269 0.531 0.0799

1x95 0.193 0.247 0.247 0.132 0.147 0.193 11000 0.216 0.862 43.8 3.16 0.269 0.463 0.0704

1x120 0.153 0.196 0.195 0.127 0.142 0.188 10000 0.236 0.942 47.8 3.07 0.269 0.423 0.0659

1x150 0.124 0.159 0.159 0.123 0.138 0.184 9500 0.254 1.01 51.5 3.00 0.269 0.394 0.0625

1x185 0.0991 0.128 0.127 0.119 0.134 0.180 8700 0.276 1.10 55.9 2.93 0.269 0.369 0.0582

1x240 0.0754 0.0978 0.0972 0.114 0.130 0.175 7900 0.306 1.22 62.0 2.85 0.269 0.346 0.0541

1x300 0.0601 0.0788 0.0780 0.111 0.126 0.172 7200 0.337 1.34 68.2 2.79 0.269 0.33 0.0517

1x400 0.0470 0.0627 0.0617 0.108 0.123 0.169 6400 0.375 1.50 76.0 2.73 0.269 0.318 0.0487

1x500 0.0366 0.0503 0.0488 0.104 0.119 0.165 5900 0.411 1.64 83.3 2.68 0.269 0.307 0.0459

1x630 0.0283 0.0407 0.0388 0.101 0.116 0.162 5300 0.453 1.81 91.8 2.64 0.269 0.300 0.0431

1x800 0.0221 0.0342 0.0317 0.0956 0.111 0.157 4600 0.528 2.11 107 2.58 0.269 0.294 0.0393

1x1000 0.0176 0.0246 0.0240 0.0944 0.110 0.155 4000 0.597 2.38 121 2.54 0.269 0.288 0.0386

1x1200 0.0151 0.0208 0.0201 0.0931 0.108 0.154 3800 0.641 2.56 130 2.52 0.269 0.285 0.0376

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

35
Al 19/33kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0

Test voltage (kV) 76 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

36
Al 19/33kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x50 8.1 8.0 25.5 70.3 1.5/1.6 38.6 1884 966 580

1x70 9.6 8.0 27.0 70.3 1.5/1.6 40.1 2008 1004 602

1x95 11.3 8.0 28.7 70.2 1.5/1.6 41.0 2142 1026 616

1x120 12.8 8.0 30.2 70.2 1.5/1.6 42.5 2274 1064 638

1x150 14.2 8.0 31.6 70.2 1.5/1.6 43.9 2425 1099 659

1x185 15.9 8.0 33.3 70.2 1.5/1.6 45.6 2608 1141 685

1x240 18.1 8.0 35.5 70.2 1.5/1.6 47.8 2846 1196 718

1x300 20.3 8.0 37.7 70.2 1.5/1.6 50.1 3115 1252 751

1x400 23.0 8.0 40.4 70.2 1.5/1.7 52.9 3483 1323 794

1x500 26.0 8.0 44.0 70.2 1.5/1.8 56.7 3984 1416 850

1x630 29.7 8.0 47.7 70.2 1.5/1.8 60.5 4528 1512 907

1x800 34.0 8.0 52.0 70.2 1.5/1.9 64.9 5266 1623 974

1x1000 39.5 8.0 59.1 70.2 1.5/2.0 72.3 6506 1809 1085

1x1200 43.5 8.0 63.1 70.2 1.5/2.0 76.5 7275 1912 1147

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

37
Al 19/33kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x50 175 195 165 170 125 160 165 160 145 150 145 135 4.73 10

1x70 215 245 200 215 160 200 200 195 180 180 175 170 6.62 10

1x95 260 290 245 260 190 235 235 230 210 205 210 200 8.99 10

1x120 300 335 280 295 215 265 260 260 240 235 235 230 11.4 10

1x150 335 375 315 335 240 295 290 295 265 260 265 255 14.2 10

1x185 385 425 360 380 270 330 325 330 295 285 295 285 17.5 10

1x240 450 490 425 450 315 380 365 380 335 320 340 330 22.7 10

1x300 510 555 485 515 355 420 405 430 370 355 380 370 28.4 10

1x400 585 630 560 595 425 475 450 490 415 390 430 440 37.8 10

1x500 675 715 650 690 485 535 500 555 465 430 485 495 47.3 10

1x630 765 805 750 795 555 595 545 625 510 465 540 560 59.6 10

1x800 865 900 855 910 625 655 595 700 560 505 605 625 75.7 10

1x1000 1000 1010 1010 1070 735 735 650 800 620 550 685 730 94.6 10

1x1200 1090 1090 1110 1190 805 790 685 875 640 565 710 795 114 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

38
Al 19/33kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x50 0.641 0.821 0.821 0.162 0.178 0.223 18000 0.134 0.798 60.7 4.04 0.269 1.20 0.0997

1x70 0.443 0.568 0.568 0.151 0.166 0.212 16000 0.148 0.885 67.3 3.81 0.269 0.848 0.0889

1x95 0.320 0.410 0.410 0.143 0.158 0.204 15000 0.164 0.977 74.3 3.62 0.269 0.621 0.0821

1x120 0.253 0.325 0.325 0.138 0.154 0.199 14000 0.176 1.05 79.9 3.50 0.269 0.523 0.0775

1x150 0.206 0.264 0.264 0.134 0.149 0.195 13000 0.189 1.13 85.5 3.40 0.269 0.476 0.0739

1x185 0.164 0.211 0.211 0.130 0.145 0.191 12000 0.202 1.20 91.5 3.31 0.269 0.434 0.0695

1x240 0.125 0.161 0.161 0.125 0.140 0.185 11000 0.222 1.32 101 3.20 0.269 0.395 0.0647

1x300 0.100 0.129 0.129 0.121 0.136 0.182 10000 0.242 1.44 110 3.11 0.269 0.371 0.0613

1x400 0.0778 0.101 0.101 0.115 0.131 0.176 9100 0.267 1.59 121 3.02 0.269 0.348 0.0568

1x500 0.0605 0.0797 0.0789 0.111 0.126 0.172 8100 0.297 1.77 135 2.93 0.269 0.331 0.0527

1x630 0.0469 0.0629 0.0618 0.107 0.122 0.168 7400 0.326 1.94 148 2.87 0.269 0.317 0.0495

1x800 0.0367 0.0507 0.0492 0.103 0.118 0.164 6700 0.363 2.17 165 2.80 0.269 0.307 0.0461

1x1000 0.0291 0.0390 0.0387 0.0999 0.115 0.161 5600 0.427 2.55 194 2.72 0.269 0.300 0.0441

1x1200 0.0247 0.0327 0.0323 0.0983 0.114 0.159 5300 0.458 2.73 208 2.69 0.269 0.294 0.0428

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

39
Cu 19/33kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semiconductive 7 Non conductive


water-blocking tape water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 8 PVC inner sheath


and Cu equalising tape

9 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0

Test voltage (kV) 76 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

40
Cu 19/33kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

1x50 8.1 8.0 25.5 70.3 1.5/1.6 38.6 2171 966 580

1x70 9.6 8.0 27.0 70.3 1.5/1.6 40.1 2412 1004 602

1x95 11.3 8.0 28.7 70.2 1.5/1.6 41.0 2703 1026 616

1x120 12.8 8.0 30.2 70.2 1.5/1.6 42.5 3001 1064 638

1x150 14.2 8.0 31.6 70.2 1.5/1.6 43.9 3303 1099 659

1x185 15.9 8.0 33.3 70.2 1.5/1.6 45.6 3714 1141 685

1x240 18.1 8.0 35.5 70.2 1.5/1.6 47.8 4290 1196 718

1x300 20.3 8.0 37.7 70.2 1.5/1.6 50.1 4931 1252 751

1xx400 23.0 8.0 40.4 70.2 1.5/1.7 52.9 5809 1323 794

1x500 26.0 8.0 44.0 70.2 1.5/1.8 56.7 6931 1416 850

1x630 29.7 8.0 47.7 70.2 1.5/1.8 60.5 8423 1512 907

1x800 34.0 8.0 52.0 70.2 1.5/1.9 64.9 10359 1623 974

1x1000 39.5 8.0 59.1 70.2 1.5/2.0 72.3 12714 1809 1085

1x1200 43.5 8.0 63.1 70.2 1.5/2.0 76.5 14721 1912 1147

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

41
Cu 19/33kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground In underground ducts
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x50 225 250 210 220 160 210 210 205 185 185 185 175 7.15 10

1x70 275 310 260 275 205 250 250 250 225 220 225 215 10.0 10

1x95 335 370 315 330 240 300 295 295 265 255 265 260 13.6 10

1x120 380 420 360 380 275 335 330 335 295 285 300 290 17.1 10

1x150 430 470 405 430 310 370 360 375 325 315 335 325 21.4 10

1x185 485 530 465 490 350 415 400 420 365 345 375 365 26.4 10

1x240 565 605 545 575 405 470 445 485 410 385 425 420 34.3 10

1x300 635 680 620 655 455 525 485 545 450 415 470 470 42.9 10

1x400 720 760 710 750 535 580 535 610 495 450 530 550 57.2 10

1x500 810 845 805 855 600 640 580 685 545 485 590 615 71.5 10

1x630 905 930 915 970 675 700 625 760 580 515 635 680 90.0 10

1x800 1020 1030 1040 1110 750 760 670 840 635 555 710 750 114 10

1x1000 1170 1140 1220 1310 890 850 720 970 665 580 750 885 143 10

1x1200 1260 1210 1340 1430 965 900 750 1050 700 605 805 950 171 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

42
Cu 19/33kV

Electrical parameters

Cond.AC resistance Inductive reactance


at 50Hz and 90 ℃ at 50Hz and 90 ℃
No. Conductor Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC Trefoil Flat Trefoil Flat Flat resistance to screen current per loss per dielectric resistance sequence sequence
resistance or flat spaced touching touching spaced at 20 ℃ capacitance phase phase stress at 20 ℃ resistance react at
at 20 ℃ touching at 20 ℃ 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

1x50 0.387 0.494 0.494 0.162 0.177 0.223 18000 0.134 0.801 60.9 4.03 0.269 0.768 0.0998

1x70 0.268 0.342 0.342 0.153 0.168 0.214 16000 0.150 0.896 68.1 3.79 0.269 0.538 0.0921

1x95 0.193 0.247 0.247 0.143 0.158 0.204 15000 0.165 0.984 74.8 3.61 0.269 0.463 0.0819

1x120 0.153 0.195 0.195 0.137 0.153 0.198 14000 0.179 1.07 81.1 3.48 0.269 0.422 0.0766

1x150 0.124 0.159 0.159 0.133 0.148 0.194 13000 0.191 1.14 86.8 3.38 0.269 0.395 0.0731

1x185 0.0991 0.127 0.127 0.129 0.144 0.190 12000 0.207 1.23 93.7 3.28 0.269 0.369 0.0682

1x240 0.0754 0.0976 0.0972 0.123 0.139 0.184 11000 0.228 1.36 103 3.17 0.269 0.346 0.0635

1x300 0.0601 0.0786 0.0779 0.120 0.135 0.180 9700 0.249 1.48 113 3.08 0.269 0.331 0.0612

1x400 0.0470 0.0624 0.0616 0.115 0.130 0.176 8800 0.275 1.64 125 2.99 0.269 0.317 0.0565

1x500 0.0366 0.0499 0.0487 0.111 0.126 0.172 8000 0.300 1.79 136 2.93 0.269 0.307 0.0532

1x630 0.0283 0.0403 0.0387 0.107 0.123 0.168 7300 0.329 1.96 149 2.86 0.269 0.300 0.0505

1x800 0.0221 0.0336 0.0315 0.102 0.117 0.162 6300 0.381 2.27 173 2.78 0.269 0.294 0.0454

1x1000 0.0176 0.0245 0.0240 0.0999 0.115 0.161 5600 0.427 2.55 194 2.72 0.269 0.288 0.0441

1x1200 0.0151 0.0207 0.0201 0.0983 0.114 0.159 5300 0.458 2.73 208 2.69 0.269 0.285 0.0428

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

43
Al 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0

Test voltage (kV) 7.6 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

44
Al 1.9/3.3kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x25 6.0 2 11.4 67.9 1.5/1.6 40.1 2076 1003 602

3x35 6.9 2 12.3 67.9 1.5/1.6 42.0 2238 1051 631

3x50 8.1 2 13.5 67.9 1.5/1.6 44.6 2457 1116 669

3x70 9.6 2 15.0 67.9 1.5/1.6 47.9 2777 1196 718

3x95 11.3 2 16.7 67.9 1.5/1.7 51.7 3147 1292 775

3x120 12.8 2 18.2 67.9 1.5/1.8 55.1 3509 1376 826

3x150 14.2 2 19.6 67.9 1.5/1.8 58.2 3932 1455 873

3x185 15.9 2 21.3 67.9 1.5/1.9 62.0 4414 1550 930

3x240 18.1 2 23.5 67.9 1.5/2.0 66.9 5097 1672 1003

3x300 20.3 2 25.7 67.9 1.5/2.1 71.9 5841 1797 1078

3x400 23.0 2 28.4 67.9 1.5/2.2 78.0 6924 1950 1170

3x500 26.0 2.2 32.0 67.9 1.7/2.4 87.7 8597 2193 1316

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

45
Al 1.9/3.3kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x25 90 95 60 95 72 2.37 10

3x35 110 120 75 120 90 3.31 10

3x50 135 145 95 145 110 4.73 10

3x70 170 185 120 180 135 6.62 10

3x95 210 230 150 215 170 8.99 10

3x120 245 265 175 250 195 11.4 10

3x150 275 300 200 275 220 14.2 10

3x185 320 345 225 315 250 17.5 10

3x240 380 415 270 365 295 22.7 10

3x300 440 480 320 415 345 28.4 10

3x400 515 565 375 480 400 37.8 10

3x500 590 635 410 530 460 47.3 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

46
Al 1.9/3.3kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x25 1.20 1.54 0.103 9200 0.296 0.206 2.1 1.27 0.273 4.26 0.0658

3x35 0.868 1.11 0.0983 8500 0.326 0.237 2.5 1.22 0.273 3.12 0.0572

3x50 0.641 0.822 0.0921 8000 0.365 0.272 3.4 1.17 0.273 2.31 0.0521

3x70 0.443 0.569 0.0896 6800 0.413 0.313 4.3 1.11 0.273 1.60 0.0492

3x95 0.320 0.410 0.0869 6100 0.468 0.357 5.0 1.07 0.273 1.15 0.0470

3x120 0.253 0.325 0.0857 5500 0.516 0.382 5.7 1.04 0.273 1.05 0.0441

3x150 0.206 0.265 0.0842 5000 0.561 0.424 6.7 1.02 0.273 1.00 0.0413

3x185 0.164 0.211 0.0824 4500 0.616 0.464 8.4 0.98 0.273 0.961 0.0402

3x240 0.125 0.162 0.0814 3900 0.687 0.508 7.8 0.92 0.273 0.940 0.0384

3x300 0.100 0.130 0.0807 3600 0.757 0.556 8.5 0.86 0.273 0.917 0.0368

3x400 0.0778 0.102 0.0793 3200 0.844 0.595 8.9 0.83 0.273 0.895 0.0324

3x500 0.0617 0.0824 0.0784 3000 0.884 0.637 9.4 0.79 0.273 0.868 0.0303

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

47
Cu 1.9/3.3kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 1.9/3.3 Min. temperature for laying (°C) 0

Test voltage (kV) 7.6 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

48
Cu 1.9/3.3kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x25 6.0 2 11.4 67.9 1.5/1.6 40.1 2540 1003 602

3x35 6.9 2 12.3 67.9 1.5/1.6 42.0 2871 1051 631

3x50 8.1 2 13.5 67.9 1.5/1.6 44.6 3320 1116 669

3x70 9.6 2 15.0 67.9 1.5/1.6 47.9 3992 1196 718

3x95 11.3 2 16.7 67.9 1.5/1.7 51.7 4832 1292 775

3x120 12.8 2 18.2 67.9 1.5/1.8 55.1 5694 1376 826

3x150 14.2 2 19.6 67.9 1.5/1.8 58.2 6570 1455 873

3x185 15.9 2 21.3 67.9 1.5/1.9 62.0 7739 1550 930

3x240 18.1 2 23.5 67.9 1.5/2.0 66.9 9438 1672 1003

3x300 20.3 2 25.7 67.9 1.5/2.1 71.9 11301 1797 1078

3x400 23.0 2 28.4 67.9 1.5/2.2 78.0 13914 1950 1170

3x500 26.0 2.2 32.0 67.9 1.7/2.4 87.7 17454 2193 1316

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

49
Cu 1.9/3.3kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x25 115 125 84 130 100 3.57 10

3x35 145 155 105 160 120 5.0 10

3x50 175 185 125 190 145 7.15 10

3x70 225 240 160 235 180 10.0 10

3x95 275 300 195 285 220 13.6 10

3x120 320 345 225 325 255 17.1 10

3x150 360 390 260 360 285 21.4 10

3x185 415 455 300 410 330 26.4 10

3x240 500 540 355 475 385 34.3 10

3x300 570 625 420 540 450 42.9 10

3x400 665 725 485 615 510 57.2 10

3x500 740 810 520 700 580 71.5 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

50
Cu 1.9/3.3kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x25 0.727 0.932 0.103 9100 0.296 0.207 2.1 1.27 0.273 2.85 0.0524

3x35 0.524 0.672 0.0984 8500 0.326 0.238 2.6 1.22 0.273 2.11 0.0493

3x50 0.387 0.496 0.0921 7900 0.365 0.275 3.5 1.17 0.273 1.47 0.0475

3x70 0.268 0.344 0.0895 6800 0.413 0.314 4.3 1.11 0.273 1.06 0.0466

3x95 0.193 0.248 0.0869 6000 0.468 0.359 5.1 1.08 0.273 0.987 0.0434

3x120 0.153 0.197 0.0857 5500 0.516 0.384 5.8 1.04 0.273 0.950 0.0412

3x150 0.124 0.161 0.0836 5000 0.561 0.426 6.7 1.02 0.273 0.921 0.0401

3x185 0.0991 0.129 0.0824 4400 0.616 0.465 8.5 0.98 0.273 0.896 0.0394

3x240 0.0754 0.0992 0.0817 3900 0.687 0.509 7.9 0.92 0.273 0.892 0.0387

3x300 0.0601 0.0802 0.0809 3600 0.757 0.558 8.5 0.87 0.273 0.878 0.0374

3x400 0.0470 0.0642 0.0796 3100 0.844 0.597 9.0 0.83 0.273 0.865 0.0351

3x500 0.0373 0.0527 0.0768 2900 0.884 0.621 10.5 0.76 0.273 0.842 0.0338

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

51
Al 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0

Test voltage (kV) 15.2 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

52
Al 3.8/6.6kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x25 6.0 2.5 12.4 67.9 1.5/1.6 42.3 2179 1056 634

3x35 6.9 2.5 13.3 67.9 1.5/1.6 44.2 2345 1105 663

3x50 8.1 2.5 14.5 67.9 1.5/1.6 46.8 2570 1169 702

3x70 9.6 2.5 16.0 67.9 1.5/1.6 50.1 2871 1251 751

3x95 11.3 2.5 17.7 67.9 1.5/1.7 53.9 3277 1346 808

3x120 12.8 2.5 19.2 67.9 1.5/1.8 57.2 3646 1430 858

3x150 14.15 2.5 20.6 67.9 1.5/1.8 60.4 4036 1509 905

3x185 15.9 2.5 22.3 67.9 1.5/2.0 64.3 4582 1607 964

3x240 18.1 2.6 24.7 67.9 1.5/2.0 69.6 5272 1739 1044

3x300 20.3 2.8 27.3 67.9 1.5/2.1 75.4 6162 1886 1132

3x400 23.0 3.0 30.4 67.9 1.6/2.3 82.7 7418 2069 1241

3x500 26.0 3.2 34.0 67.9 1.7/2.5 92.2 9110 2306 1384

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

53
Al 3.8/6.6kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x25 95 100 67 100 77 2.37 10

3x35 115 125 82 125 95 3.31 10

3x50 140 150 100 150 115 4.73 10

3x70 175 190 125 185 140 6.62 10

3x95 215 235 155 220 175 8.99 10

3x120 250 270 180 255 200 11.4 10

3x150 280 305 200 280 225 14.2 10

3x185 325 350 230 320 255 17.5 10

3x240 385 420 275 370 300 22.7 10

3x300 445 485 325 420 350 28.4 10

3x400 520 570 380 485 405 37.8 10

3x500 610 665 440 550 460 47.3 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

54
Al 3.8/6.6kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x25 1.20 1.54 0.115 9500 0.255 0.304 4.6 1.97 0.273 4.39 0.0785

3x35 0.868 1.11 0.109 8700 0.278 0.332 5.0 1.92 0.273 3.14 0.0709

3x50 0.641 0.822 0.104 7800 0.309 0.369 5.6 1.87 0.273 2.32 0.0658

3x70 0.443 0.569 0.0964 6800 0.353 0.422 6.4 1.82 0.273 1.62 0.0574

3x95 0.320 0.410 0.0924 6000 0.400 0.478 7.3 1.77 0.273 1.20 0.0527

3x120 0.253 0.325 0.0898 5500 0.439 0.524 8.0 1.74 0.273 1.05 0.0497

3x150 0.206 0.265 0.0877 5100 0.477 0.569 8.7 1.72 0.273 1.00 0.0471

3x185 0.164 0.211 0.0857 4700 0.518 0.618 9.4 1.70 0.273 0.961 0.0440

3x240 0.125 0.162 0.0839 4300 0.561 0.670 10.2 1.62 0.273 0.941 0.0416

3x300 0.100 0.130 0.0835 4100 0.582 0.695 10.6 1.50 0.273 0.918 0.0407

3x400 0.0778 0.102 0.0814 3900 0.613 0.731 11.1 1.39 0.273 0.894 0.0385

3x500 0.0617 0.0824 0.0800 3700 0.654 0.781 11.8 1.29 0.273 0.878 0.0370

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

55
Cu 3.8/6.6kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 3.8/6.6 Min. temperature for laying (°C) 0

Test voltage (kV) 15.2 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

56
Cu 3.8/6.6kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x25 6.0 2.5 12.4 67.9 1.5/1.6 42.3 2642 1056 634

3x35 6.9 2.5 13.3 67.9 1.5/1.6 44.2 2979 1105 663

3x50 8.1 2.5 14.5 67.9 1.5/1.6 46.8 3433 1169 702

3x70 9.6 2.5 16.0 67.9 1.5/1.6 50.1 4086 1251 751

3x95 11.3 2.5 17.7 67.9 1.5/1.7 53.9 4961 1346 808

3x120 12.8 2.5 19.2 67.9 1.5/1.8 57.2 5832 1430 858

3x150 14.2 2.5 20.6 67.9 1.5/1.8 60.4 6674 1509 905

3x185 15.9 2.5 22.3 67.9 1.5/2.0 64.3 7907 1607 964

3x240 18.1 2.6 24.7 67.9 1.5/2.0 69.6 9612 1739 1044

3x300 20.3 2.8 27.3 67.9 1.5/2.1 75.4 11623 1886 1132

3x400 23.0 3.0 30.4 67.9 1.6/2.3 82.7 14408 2069 1241

3x500 26.0 3.2 34.0 67.9 1.7/2.5 92.2 17968 2306 1384

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

57
Cu 3.8/6.6kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x25 120 130 89 135 105 3.57 10

3x35 150 160 110 165 125 5.00 10

3x50 180 195 130 195 150 7.15 10

3x70 230 245 165 240 185 10.0 10

3x95 280 305 200 290 225 13.6 10

3x120 325 350 230 330 260 17.1 10

3x150 365 395 265 365 290 21.4 10

3x185 420 460 305 415 335 26.4 10

3x240 500 545 360 480 390 34.3 10

3x300 575 630 425 545 455 42.9 10

3x400 670 730 490 620 515 57.2 10

3x500 765 830 555 700 580 71.5 10

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

58
Cu 3.8/6.6kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x25 0.727 0.932 0.115 9400 0.256 0.305 4.6 1.97 0.273 2.85 0.0763

3x35 0.524 0.672 0.109 8600 0.279 0.333 5.1 1.92 0.273 2.12 0.0708

3x50 0.387 0.496 0.104 7800 0.311 0.371 5.6 1.87 0.273 1.48 0.0660

3x70 0.268 0.344 0.0987 6700 0.359 0.428 6.5 1.81 0.273 1.06 0.0601

3x95 0.193 0.248 0.0922 6000 0.404 0.482 7.3 1.77 0.273 0.989 0.0524

3x120 0.153 0.197 0.0893 5400 0.447 0.534 8.1 1.74 0.273 0.950 0.0491

3x150 0.124 0.161 0.0872 5000 0.486 0.580 8.8 1.72 0.273 0.920 0.0466

3x185 0.0991 0.129 0.0851 4500 0.533 0.636 9.7 1.69 0.273 0.896 0.0433

3x240 0.0754 0.0992 0.0833 4200 0.578 0.690 10.5 1.61 0.273 0.892 0.0409

3x300 0.0601 0.0802 0.0829 4000 0.601 0.718 10.9 1.49 0.273 0.878 0.0399

3x400 0.0470 0.0642 0.0817 3800 0.636 0.759 11.5 1.38 0.273 0.864 0.0387

3x500 0.0373 0.0527 0.0806 3600 0.662 0.790 12.0 1.29 0.273 0.855 0.0376

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

59
Al 6.35/11kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0

Test voltage (kV) 25.5 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

60
Al 6.35/11kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x25 6.0 3.4 14.2 67.9 1.5/1.6 46.1 2414 1153 692

3x35 6.9 3.4 15.1 67.9 1.5/1.6 48.1 2589 1202 721

3x50 8.1 3.4 16.3 67.9 1.5/1.6 50.7 2801 1268 761

3x70 9.6 3.4 17.8 67.9 1.5/1.7 54.1 3156 1352 811

3x95 11.3 3.4 19.5 67.9 1.5/1.8 58.0 3593 1450 870

3x120 12.8 3.4 21.0 67.9 1.5/1.9 61.3 3940 1534 920

3x150 14.15 3.4 22.4 67.9 1.5/2.0 64.5 4389 1612 967

3x185 15.9 3.4 24.1 67.9 1.5/2.0 68.3 4895 1707 1024

3x240 18.1 3.4 26.3 67.9 1.5/2.1 73.3 5631 1832 1099

3x300 20.3 3.4 28.5 67.9 1.5/2.2 78.2 6453 1955 1173

3x400 23.0 3.4 31.2 67.9 1.6/2.3 84.5 7610 2112 1267

3x500 26.0 3.4 34.4 67.9 1.7/2.5 93.1 9216 2327 1396

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

61
Al 6.35/11kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x25 95 100 68 105 79 2.37 2.78

3x35 115 125 83 125 95 3.31 3.53

3x50 140 150 100 150 115 4.73 4.80

3x70 175 190 130 185 145 6.62 6.82

3x95 220 235 155 220 175 8.99 9.09

3x120 255 275 185 255 205 11.4 10.1

3x150 285 305 205 280 225 14.2 10.1

3x185 325 355 235 320 255 17.5 10.1

3x240 390 420 275 375 300 22.7 10.1

3x300 445 485 330 420 350 28.4 10.1

3x400 525 570 380 485 405 37.8 10.1

3x500 610 665 440 550 460 47.3 10.1

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

62
Al 6.35/11kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x25 1.20 1.54 0.124 12000 0.203 0.405 10.3 2.62 0.273 4.10 0.0858

3x35 0.868 1.11 0.117 11000 0.220 0.439 11.1 2.54 0.273 3.14 0.0779

3x50 0.641 0.821 0.112 9900 0.243 0.486 12.3 2.46 0.273 2.32 0.0724

3x70 0.443 0.569 0.104 8700 0.276 0.551 14.0 2.37 0.273 1.62 0.0634

3x95 0.320 0.410 0.0990 7800 0.311 0.620 15.8 2.30 0.273 1.20 0.0583

3x120 0.253 0.325 0.0959 7100 0.339 0.677 17.2 2.25 0.273 1.05 0.0549

3x150 0.206 0.265 0.0934 6600 0.368 0.734 18.6 2.22 0.273 1.00 0.0520

3x185 0.164 0.211 0.0911 6100 0.398 0.794 20.2 2.18 0.273 0.981 0.0486

3x240 0.125 0.161 0.0881 5400 0.445 0.887 22.5 2.14 0.273 0.941 0.0453

3x300 0.100 0.130 0.0864 4900 0.491 0.980 24.9 2.11 0.273 0.916 0.0432

3x400 0.0778 0.102 0.0832 4400 0.548 1.09 27.8 2.08 0.273 0.894 0.0405

3x500 0.0617 0.0823 0.0808 3900 0.620 1.24 31.4 2.05 0.273 0.880 0.0377

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

63
Cu 6.35/11kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 6.35/11 Min. temperature for laying (°C) 0

Test voltage (kV) 25.5 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

64
Cu 6.35/11kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x25 6.0 3.4 14.2 67.9 1.5/1.6 46.1 2877 1153 692

3x35 6.9 3.4 15.1 67.9 1.5/1.6 48.1 3223 1202 721

3x50 8.1 3.4 16.3 67.9 1.5/1.6 50.7 3664 1268 761

3x70 9.6 3.4 17.8 67.9 1.5/1.7 54.1 4371 1352 811

3x95 11.3 3.4 19.5 67.9 1.5/1.8 58.0 5278 1450 870

3x120 12.8 3.4 21.0 67.9 1.5/1.9 61.3 6125 1534 920

3x150 14.15 3.4 22.4 67.9 1.5/2.0 64.5 7027 1612 967

3x185 15.9 3.4 24.1 67.9 1.5/2.0 68.3 8220 1707 1024

3x240 18.1 3.4 26.3 67.9 1.5/2.1 73.3 9972 1832 1099

3x300 20.3 3.4 28.5 67.9 1.5/2.2 78.2 11913 1955 1173

3x400 23.0 3.4 31.2 67.9 1.6/2.3 84.5 14599 2112 1267

3x500 26.0 3.4 34.4 67.9 1.7/2.5 93.1 18073 2327 1396

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

65
Cu 6.35/11kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x25 125 135 90 135 105 3.57 3.79

3x35 150 165 110 165 125 5.00 5.05

3x50 185 200 135 195 150 7.15 7.32

3x70 230 250 170 240 190 10.0 10.1

3x95 285 305 210 290 230 13.6 10.1

3x120 330 355 240 330 265 17.1 10.1

3x150 370 400 270 365 295 21.4 10.1

3x185 425 460 305 415 335 26.4 10.1

3x240 505 550 375 480 400 34.3 10.1

3x300 580 630 425 545 455 42.9 10.1

3x400 670 730 490 620 520 57.2 10.1

3x500 765 835 555 695 580 71.5 10.1

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

66
Cu 6.35/11kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x25 0.727 0.932 0.124 12000 0.203 0.406 10.3 2.62 0.273 2.85 0.0823

3x35 0.524 0.672 0.117 11000 0.221 0.441 11.2 2.54 0.273 2.12 0.0775

3x50 0.387 0.496 0.112 9900 0.244 0.488 12.4 2.46 0.273 1.49 0.0724

3x70 0.268 0.344 0.106 8600 0.280 0.559 14.2 2.36 0.273 1.06 0.0663

3x95 0.193 0.248 0.0987 7700 0.314 0.626 15.9 2.30 0.273 0.989 0.0579

3x120 0.153 0.197 0.0953 7000 0.346 0.689 17.5 2.25 0.273 0.950 0.0542

3x150 0.124 0.161 0.0928 6400 0.374 0.747 19.0 2.21 0.273 0.921 0.0514

3x185 0.0991 0.129 0.0903 5900 0.409 0.817 20.7 2.17 0.273 0.915 0.0477

3x240 0.0754 0.0990 0.0874 5300 0.458 0.913 23.2 2.13 0.273 0.892 0.0445

3x300 0.0601 0.0800 0.0857 4800 0.507 1.01 25.7 2.10 0.273 0.876 0.0424

3x400 0.0470 0.0641 0.0834 4200 0.569 1.13 28.8 2.07 0.273 0.864 0.0405

3x500 0.0373 0.0527 0.0815 3800 0.627 1.25 31.8 2.04 0.273 0.853 0.0383

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

67
Al 12.7/22kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0

Test voltage (kV) 50 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

68
Al 12.7/22kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x35 6.9 5.5 19.3 6.9 1.5/1.8 57.6 3244 1439 863

3x50 8.1 5.5 20.5 8.1 1.5/1.9 60.3 3486 1507 904

3x70 9.6 5.5 22.0 9.6 1.5/2.0 63.6 3882 1591 954

3x95 11.3 5.5 23.7 11.3 1.5/2.0 67.4 4354 1686 1011

3x120 12.8 5.5 25.2 12.8 1.5/2.1 70.8 4737 1770 1062

3x150 14.15 5.5 26.6 14.15 1.5/2.1 73.9 5226 1848 1109

3x185 15.9 5.5 28.3 15.9 1.5/2.2 77.8 5833 1945 1167

3x240 18.1 5.5 30.5 18.1 1.6/2.3 83.0 6665 2074 1244

3x300 20.3 5.5 32.7 20.3 1.7/2.4 87.9 7551 2198 1319

3x400 23.0 5.5 35.4 23.0 1.8/2.6 94.4 8829 2360 1416

3x500 26.0 5.5 38.6 26.0 1.9/2.7 103.0 10570 2576 1545

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

69
Al 12.7/22kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x35 120 130 87 125 100 3.31 10.0

3x50 145 155 110 150 120 4.73 10.0

3x70 180 195 135 185 150 6.62 10.0

3x95 225 240 165 220 180 8.99 10.0

3x120 260 280 190 255 205 11.4 10.0

3x150 290 310 215 280 235 14.2 10.0

3x185 330 360 250 320 265 17.5 10.0

3x240 395 425 290 375 310 22.7 10.0

3x300 450 490 335 425 355 28.4 10.0

3x400 530 575 390 485 410 37.8 10.0

3x500 615 670 465 550 480 47.3 10.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

70
Al 12.7/22kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x35 0.868 1.11 0.134 15000 0.157 0.626 31.8 3.62 0.273 3.15 0.0919

3x50 0.641 0.821 0.128 14000 0.172 0.685 34.8 3.47 0.273 2.32 0.0855

3x70 0.443 0.568 0.118 13000 0.192 0.768 39.0 3.30 0.273 1.62 0.0756

3x95 0.320 0.410 0.112 11000 0.214 0.855 43.4 3.17 0.273 1.23 0.0696

3x120 0.253 0.325 0.108 10000 0.232 0.926 47.0 3.08 0.273 1.07 0.0656

3x150 0.206 0.265 0.105 9700 0.250 0.997 50.7 3.01 0.273 1.02 0.0622

3x185 0.164 0.211 0.102 9000 0.269 1.07 54.5 2.95 0.273 0.982 0.0582

3x240 0.125 0.161 0.0983 8100 0.298 1.19 60.4 2.87 0.273 0.941 0.0542

3x300 0.100 0.130 0.0958 7400 0.327 1.30 66.3 2.81 0.273 0.918 0.0519

3x400 0.0778 0.102 0.0917 6700 0.363 1.45 73.5 2.75 0.273 0.894 0.0480

3x500 0.0617 0.0819 0.0885 5900 0.407 1.62 82.4 2.69 0.273 0.879 0.4460

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

71
Cu 12.7/22kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 12.7/22 Min. temperature for laying (°C) 0

Test voltage (kV) 50 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

72
Cu 12.7/22kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x35 6.9 5.5 19.3 67.9 1.5/1.8 57.6 3878 1439 863

3x50 8.1 5.5 20.5 67.9 1.5/1.9 60.3 4349 1507 904

3x70 9.6 5.5 22.0 67.9 1.5/2.0 63.6 5097 1591 954

3x95 11.3 5.5 23.7 67.9 1.5/2.0 67.4 6039 1686 1011

3x120 12.8 5.5 25.2 67.9 1.5/2.1 70.8 6922 1770 1062

3x150 14.15 5.5 26.6 67.9 1.5/2.1 73.9 7864 1848 1109

3x185 15.9 5.5 28.3 67.9 1.5/2.2 77.8 9158 1945 1167

3x240 18.1 5.5 30.5 67.9 1.6/2.3 83.0 11006 2074 1244

3x300 20.3 5.5 32.7 67.9 1.7/2.4 87.9 13011 2198 1319

3x400 23.0 5.5 35.4 67.9 1.8/2.6 94.4 15819 2360 1416

3x500 26.0 5.5 38.6 67.9 1.9/2.7 103.0 19428 2576 1545

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

73
Cu 12.7/22kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x35 155 170 115 165 130 5.00 10.0

3x50 190 205 140 195 160 7.15 10.0

3x70 240 255 175 240 195 10.0 10.0

3x95 290 310 215 290 235 13.6 10.0

3x120 335 360 245 330 270 17.1 10.0

3x150 375 405 285 365 305 21.4 10.0

3x185 435 470 325 415 345 26.4 10.0

3x240 510 555 380 485 405 34.3 10.0

3x300 586 640 435 545 455 42.9 10.0

3x400 680 740 500 620 530 57.2 10.0

3x500 775 840 580 700 610 71.5 10.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

74
Cu 12.7/22kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x35 0.524 0.672 0.134 15000 0.157 0.628 31.9 3.62 0.273 2.12 0.0915

3x50 0.387 0.496 0.128 14000 0.172 0.688 34.9 3.46 0.273 1.49 0.0843

3x70 0.268 0.344 0.120 12000 0.195 0.778 39.5 3.29 0.273 1.06 0.0778

3x95 0.193 0.248 0.112 11000 0.216 0.862 43.8 3.16 0.273 1.01 0.0692

3x120 0.153 0.197 0.108 10000 0.236 0.942 47.8 3.07 0.273 0.970 0.0648

3x150 0.124 0.160 0.104 9500 0.254 1.010 51.5 3.00 0.273 0.941 0.0615

3x185 0.0991 0.128 0.101 8700 0.276 1.10 55.9 2.93 0.273 0.916 0.0572

3x240 0.0754 0.0986 0.0973 7900 0.306 1.22 62.0 2.85 0.273 0.894 0.0532

3x300 0.0601 0.0796 0.0949 7200 0.337 1.34 68.2 2.79 0.273 0.877 0.0508

3x400 0.0470 0.0636 0.0917 6400 0.375 1.50 76.0 2.73 0.273 0.864 0.0479

3x500 0.0373 0.0520 0.0891 5900 0.411 1.64 83.3 2.68 0.273 0.856 0.0451

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

75
Al 19/33kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Al conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0

Test voltage (kV) 76 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

76
Al 19/33kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x50 8.1 8 25.5 67.9 1.5/2.1 71.4 4432 1786 1071

3x70 9.6 8 27.0 67.9 1.5/2.1 74.8 4877 1870 1122

3x95 11.3 8 28.7 67.9 1.6/2.3 78.9 5445 1972 1183

3x120 12.8 8 30.2 67.9 1.6/2.3 82.3 5941 2058 1235

3x150 14.15 8 31.6 67.9 1.7/2.4 85.6 6498 2139 1283

3x185 15.9 8 33.3 67.9 1.7/2.5 89.4 7166 2236 1342

3x240 18.1 8 35.5 67.9 1.8/2.6 94.6 8080 2365 1419

3x300 20.3 8 37.7 67.9 1.8/2.7 99.6 9062 2489 1494

3x400 23.0 8 40.4 67.9 1.9/2.8 105.8 10399 2646 1587

3x500 26.0 8 43.6 67.9 2.0/2.9 114.5 12254 2861 1717

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

77
Al 19/33kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x50 150 160 110 150 120 4.73 10.0

3x70 185 200 145 185 155 6.62 10.0

3x95 225 245 175 220 185 8.99 10.0

3x120 260 280 200 255 215 11.4 10.0

3x150 295 315 220 280 235 14.2 10.0

3x185 335 365 255 320 270 17.5 10.0

3x240 400 430 295 375 315 22.7 10.0

3x300 455 495 340 425 355 28.4 10.0

3x400 535 580 410 485 425 37.8 10.0

3x500 620 670 475 555 480 47.3 10.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

78
Al 19/33kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x50 0.641 0.822 0.143 18000 0.134 0.798 60.7 4.04 0.273 2.36 0.0986

3x70 0.443 0.569 0.132 16000 0.148 0.885 67.3 3.81 0.273 1.65 0.0879

3x95 0.320 0.410 0.125 15000 0.164 0.977 74.3 3.62 0.273 1.23 0.0811

3x120 0.253 0.325 0.121 14000 0.176 1.05 79.9 3.50 0.273 1.07 0.0766

3x150 0.206 0.264 0.117 13000 0.189 1.13 85.5 3.40 0.273 1.02 0.0730

3x185 0.164 0.211 0.113 12000 0.202 1.20 91.5 3.31 0.273 0.980 0.0686

3x240 0.125 0.161 0.109 11000 0.222 1.32 101 3.20 0.273 0.941 0.0639

3x300 0.100 0.130 0.106 10000 0.242 1.44 110 3.11 0.273 0.917 0.0606

3x400 0.0778 0.102 0.101 9100 0.267 1.59 121 3.02 0.273 0.896 0.0561

3x500 0.0617 0.0815 0.0969 8100 0.297 1.77 135 2.93 0.273 0.879 0.0520

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

79
Cu 19/33kV
MV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.1

10 9 8 7 6 5 4 3 2 1

Construction:

1 Cu conductor 3 XLPE insulation 5 Semi conductive 8 Non-woven fabric tape


water-blocking tape

2 Conductor screen 4 Insulation screen 6 Cu wire screen 9 PVC inner sheath


and Cu equalising tape

7 Non-hydroscopic filler 10 HDPE outer sheath

Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 19/33 Min. temperature for laying (°C) 0

Test voltage (kV) 76 Min.storage temperature (°C) -10

Max.short-circuit temperature (°C) +250 Colour of insulation Natural

Operating conductor temperature (°C) +90 Colour of inner / outer sheath Client Requirement

Temperature range for handling (°C) -10 up to +90 Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 0.8m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

80
Cu 19/33kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius of bend Radius of bend
diameter thickness over insluation screen area thickness diameter appr. during installation set in position
of PVC/HDPE
sheath
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm)

3x50 8.1 8 25.5 67.9 1.5/2.1 71.4 5295 1786 1071

3x70 9.6 8 27.0 67.9 1.5/2.1 74.8 6092 1870 1122

3x95 11.3 8 28.7 67.9 1.6/2.3 78.9 7130 1972 1183

3x120 12.8 8 30.2 67.9 1.6/2.3 82.3 8126 2058 1235

3x150 14.15 8 31.6 67.9 1.7/2.4 85.6 9136 2139 1283

3x185 15.9 8 33.3 67.9 1.7/2.5 89.4 10491 2236 1342

3x240 18.1 8 35.5 67.9 1.8/2.6 94.6 12421 2365 1419

3x300 20.3 8 37.7 67.9 1.8/2.7 99.6 14523 2489 1494

3x400 23.0 8 40.4 67.9 1.9/2.8 105.8 17389 2646 1587

3x500 26.0 8 43.6 67.9 2.0/2.9 114.5 21111 2861 1717

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

81
Cu 19/33kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond Solid bond (kA) (kA)

3x50 195 205 145 195 160 7.15 10.0

3x70 245 260 190 240 205 10.0 10.0

3x95 295 315 225 290 245 13.6 10.0

3x120 340 365 260 330 280 17.1 10.0

3x150 380 410 290 365 310 21.4 10.0

3x185 440 475 330 420 350 26.4 10.0

3x240 520 560 385 485 410 34.4 10.0

3x300 595 645 440 550 465 42.9 10.0

3x400 685 745 525 625 545 57.2 10.0

3x500 780 850 595 700 615 71.5 10.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

82
Cu 19/33kV

Electrical parameters

No. Conductor Conductor Inductive Insulation Conductor Charging Dielectric Maximum Screen DC Zero Zero
of cores DC resistance AC resistance reactance resistance to screen current loss dielectric resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz at 20 ℃ capacitance per phase per phase stress at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (MΩ.km) (µF/km) (A/km) (W/km) (kV/km) (Ω/km) (Ω/km) (Ω/km)

3x50 0.387 0.496 0.143 18000 0.134 0.801 60.9 4.03 0.273 1.51 0.0977

3x70 0.268 0.344 0.134 16000 0.150 0.896 68.1 3.79 0.273 1.08 0.0902

3x95 0.193 0.248 0.125 15000 0.165 0.984 74.8 3.61 0.273 1.01 0.0801

3x120 0.153 0.197 0.120 14000 0.179 1.07 81.1 3.48 0.273 0.970 0.0757

3x150 0.124 0.160 0.116 13000 0.191 1.14 86.8 3.38 0.273 0.940 0.0722

3x185 0.0991 0.128 0.112 12000 0.207 1.32 97.3 3.28 0.273 0.917 0.0647

3x240 0.0754 0.0986 0.108 11000 0.228 1.36 103 3.17 0.273 0.891 0.0627

3x300 0.0601 0.0796 0.104 9700 0.249 1.48 113 3.08 0.273 0.876 0.0594

3x400 0.0470 0.0636 0.101 8800 0.275 1.64 125 2.99 0.273 0.865 0.0558

3x500 0.0373 0.0515 0.0974 8000 0.300 1.79 136 2.93 0.273 0.855 0.0525

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

83
Al 38/66kV
HV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.2

9 8 7 6 5 4 3 2 1

Construction:

1 Aluminium compact conductor 3 XLPE insulation 5 Semi conductive 7 Semi conductive


or Milliken conductor water-blocking tape water-blocking tape

2 Semi-conductive screen tape 4 Insulation screen 6 Cu wire screen 8 APL sheath


and Extruded conductor screen and Cu equalising tape

9 HDPE outer sheath


and Graphite coat
Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 38/66 Min. temperature for laying (°C) 0

Max.short-circuit temperature (°C) +250 Min.storage temperature (°C) -10

Operating conductor temperature (°C) +90 Colour of insulation Natural

Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement

Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25 ℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 1.0m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

84
Al 38/66kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]

1x120 12.8 13.0 41.6 116.3 0.25/2.6 57.9 3554 1150 900 3.6

1x150 14.2 12.0 41.0 116.3 0.25/2.6 57.3 3560 1150 850 4.5

1x185 15.9 12.0 42.7 116.3 0.25/2.6 59.1 3776 1200 900 5.6

1x240 18.1 12.0 44.9 116.3 0.25/2.7 61.4 4059 1250 950 7.2

1x300 20.3 11.0 45.1 116.3 0.25/2.7 61.6 4186 1250 950 9.0

1x400 23.0 11.0 47.8 116.3 0.25/2.8 64.6 4597 1300 1000 12.0

1x500 26.0 11.0 50.8 116.3 0.25/2.9 67.7 5094 1350 1050 15.0

1x630 29.7 11.0 54.5 116.3 0.25/3.0 71.7 5689 1450 1100 18.9

1x800 34.0 10.0 57.0 116.3 0.25/3.1 74.1 6255 1500 1150 24.0

1x1000 39.5 10.0 64.5 116.3 0.25/3.2 81.6 7476 1650 1250 30.0

1x1200 43.5 10.0 68.5 116.3 0.25/3.3 85.9 8289 1750 1300 36.0

1x1600 49.2 10.0 74.2 116.3 0.25/3.5 92.0 9773 1850 1400 48.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

85
Al 38/66kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x120 305 317 259 245 11.3 16.5

1x150 346 358 286 274 14.2 16.5

1x185 375 390 324 295 17.5 16.5

1x240 427 460 375 340 22.7 16.5

1x300 500 531 421 360 28.4 16.5

1x400 578 601 476 410 37.8 16.5

1x500 656 695 539 465 47.3 16.5

1x630 757 796 601 545 59.5 16.5

1x800 859 906 664 610 75.6 16.5

1x1000 992 1046 757 700 94.5 16.5

1x1200 1085 1148 820 760 113.4 16.5

1x1600 1475 1562 1061 1002 151.2 16.5

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

86
Al 38/66kV

Electrical parameters

No. Conductor Conductor Inductive Conductor Screen DC Zero Zero


of cores DC resistance AC resistance reactance to screen resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz capacitance at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (µF/km) (Ω/km) (Ω/km) (Ω/km)

1x120 0.2530 0.3246 0.188 0.130 0.162 0.473 0.609

1x150 0.2060 0.2644 0.182 0.145 0.162 0.412 0.602

1x185 0.1640 0.2107 0.175 0.155 0.162 0.359 0.595

1x240 0.1250 0.1608 0.166 0.167 0.162 0.309 0.587

1x300 0.1000 0.1289 0.159 0.191 0.162 0.277 0.580

1x400 0.0778 0.1006 0.151 0.208 0.162 0.249 0.572

1x500 0.0605 0.0787 0.144 0.225 0.162 0.227 0.564

1x630 0.0469 0.0616 0.161 0.248 0.162 0.209 0.505

1x800 0.0367 0.0489 0.152 0.295 0.162 0.197 0.497

1x1000 0.0291 0.0378 0.143 0.345 0.162 0.186 0.487

1x1200 0.0247 0.0322 0.137 0.371 0.162 0.180 0.481

1x1600 0.0186 0.0246 0.129 0.407 0.162 0.173 0.473

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

87
Cu 38/66kV
HV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.2

9 8 7 6 5 4 3 2 1

Construction:

1 Copper compact conductor 3 XLPE insulation 5 Semi conductive 7 Semi conductive


or Milliken conductor water-blocking tape water-blocking tape

2 Semi-conductive screen tape 4 Insulation screen 6 Cu wire screen 8 APL sheath


and Extruded conductor screen and Cu equalising tape

9 HDPE outer sheath


and Graphite coat
Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 38/66 Min. temperature for laying (°C) 0

Max.short-circuit temperature (°C) +250 Min.storage temperature (°C) -10

Operating conductor temperature (°C) +90 Colour of insulation Natural

Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement

Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 1.0m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

88
Cu 38/66kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]

1x120 12.8 13.0 41.6 116.3 0.25/2.6 57.9 4281 1158 900 8.4

1x150 14.2 12.0 41.0 116.3 0.25/2.6 57.3 4437 1146 850 10.5

1x185 15.9 12.0 42.7 116.3 0.25/2.6 59.1 4883 1182 900 13.0

1x240 18.1 12.0 44.9 116.3 0.25/2.7 61.4 5503 1228 950 16.8

1x300 20.3 11.0 45.1 116.3 0.25/2.7 61.6 6002 1232 950 21.0

1x400 23.0 11.0 47.8 116.3 0.25/2.8 64.6 6923 1292 1000 28.0

1x500 26.0 11.0 50.8 116.3 0.25/2.9 67.7 8041 1354 1050 35.0

1x630 29.7 11.0 54.5 116.3 0.25/3.0 71.7 9584 1434 1100 44.1

1x800 34.0 10.0 57.0 116.3 0.25/3.1 74.1 11348 1482 1150 56.0

1x1000 39.5 10.0 64.5 116.3 0.25/3.2 81.6 13688 1632 1250 70.0

1x1200 43.5 10.0 68.5 116.3 0.25/3.3 85.9 15738 1718 1300 84.0

1x1600 49.2 10.0 74.2 116.3 0.25/3.5 92.0 19698 1840 1400 112.0

1x2000 55.2 10.0 80.2 116.3 0.25/3.7 98.4 23680 1968 1500 140.0

1x2500 61.5 10.0 86.5 116.3 0.25/3.9 105.1 28579 2102 1600 175.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

89
Cu 38/66kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x120 370 385 325 310 17.2 16.5

1x150 420 435 365 350 21.5 16.5

1x185 480 500 415 400 26.5 16.5

1x240 560 590 480 460 34.3 16.5

1x300 640 680 540 530 42.9 16.5

1x400 740 770 610 600 57.2 16.5

1x500 840 890 690 680 71.6 16.5

1x630 970 1020 770 760 90.2 16.5

1x800 1100 1160 850 840 114.5 16.5

1x1000 1270 1340 970 960 143.1 16.5

1x1200 1390 1470 1050 1030 171.7 16.5

1x1600 1801 1904 1291 1266 229.0 16.5

1x2000 2012 2128 1412 1385 286.2 16.5

1x2500 2220 2347 1525 1496 357.8 16.5

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

90
Cu 38/66kV

Electrical parameters

No. Conductor Conductor Inductive Conductor Screen DC Zero Zero


of cores DC resistance AC resistance reactance to screen resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz capacitance at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (µF/km) (Ω/km) (Ω/km) (Ω/km)

1x120 0.1530 0.1955 0.188 0.130 0.162 0.343 0.609

1x150 0.1240 0.1586 0.182 0.145 0.162 0.307 0.602

1x185 0.0991 0.1270 0.175 0.155 0.162 0.275 0.595

1x240 0.0754 0.0970 0.166 0.167 0.162 0.245 0.587

1x300 0.0601 0.0777 0.159 0.191 0.162 0.226 0.580

1x400 0.0470 0.0613 0.151 0.208 0.162 0.209 0.572

1x500 0.0366 0.0485 0.144 0.225 0.162 0.196 0.564

1x630 0.0283 0.0384 0.161 0.248 0.162 0.186 0.505

1x800 0.0221 0.0311 0.152 0.295 0.162 0.179 0.497

1x1000 0.0176 0.0232 0.143 0.345 0.162 0.171 0.487

1x1200 0.0151 0.0201 0.137 0.371 0.162 0.168 0.481

1x1600 0.0113 0.0156 0.129 0.407 0.162 0.163 0.473

1x2000 0.0090 0.0130 0.122 0.446 0.162 0.161 0.466

1x2500 0.0073 0.0111 0.133 0.487 0.162 0.159 0.423

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

91
Al 76/132kV
HV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.2

9 8 7 6 5 4 3 2 1

Construction:

1 Aluminium compact conductor 3 XLPE insulation 5 Semi conductive 7 Semi conductive


or Milliken conductor water-blocking tape water-blocking tape

2 Semi-conductive screen tape 4 Insulation screen 6 Cu wire screen 8 APL sheath


and Extruded conductor screen and Cu equalising tape

9 HDPE outer sheath


and Graphite coat
Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 76/132 Min. temperature for laying (°C) 0

Max.short-circuit temperature (°C) +250 Min.storage temperature (°C) -10

Operating conductor temperature (°C) +90 Colour of insulation Natural

Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement

Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 1.0m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

92
Al 76/132kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]

1x150 14.2 18.0 53.0 116.3 0.25/3.0 70.1 4701 1400 1050 4.5

1x185 15.9 18.0 54.7 116.3 0.25/3.1 71.9 4952 1450 1100 5.6

1x240 18.1 18.0 56.9 116.3 0.25/3.1 74.3 5282 1500 1150 7.2

1x300 20.3 18.0 59.1 116.3 0.25/3.2 76.6 5639 1550 1150 9.0

1x400 23.0 18.0 61.8 116.3 0.25/3.3 79.5 6115 1600 1200 12.0

1x500 26.0 18.0 64.8 116.3 0.25/3.4 82.7 6681 1650 1250 15.0

1x630 29.7 18.0 68.5 116.3 0.25/3.5 86.6 7362 1750 1300 18.9

1x800 34.0 18.0 72.8 116.3 0.25/3.6 91.2 8256 1850 1400 24.0

1x1000 39.5 18.0 80.5 116.3 0.25/3.8 98.8 9667 2000 1500 30.0

1x1200 43.5 18.0 84.5 116.3 0.25/3.9 103.0 10585 2050 1550 36.0

1x1600 49.2 18.0 90.2 116.3 0.25/4.1 109.1 12222 2200 1650 48.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

93
Al 76/132kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x150 345 358 278 264 14.2 16.5

1x185 380 390 322 300 17.5 16.5

1x240 430 460 373 340 22.7 16.5

1x300 500 535 422 360 28.4 16.5

1x400 580 605 480 410 37.8 16.5

1x500 660 695 540 470 47.3 16.5

1x630 760 800 605 550 59.5 16.5

1x800 860 910 665 610 75.6 16.5

1x1000 995 1050 760 700 94.5 16.5

1x1200 1085 1150 820 770 113.4 16.5

1x1600 1455 1542 1054 989 151.2 16.5

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

94
Al 76/132kV

Electrical parameters

No. Conductor Conductor Inductive Conductor Screen DC Zero Zero


of cores DC resistance AC resistance reactance to screen resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz capacitance at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (µF/km) (Ω/km) (Ω/km) (Ω/km)

1x150 0.2060 0.2644 0.182 0.113 0.162 0.412 0.602

1x185 0.1640 0.2107 0.200 0.119 0.162 0.359 0.544

1x240 0.1250 0.1608 0.192 0.128 0.162 0.309 0.536

1x300 0.1000 0.1289 0.185 0.136 0.162 0.277 0.529

1x400 0.0778 0.1006 0.177 0.147 0.162 0.249 0.521

1x500 0.0605 0.0787 0.169 0.158 0.162 0.227 0.513

1x630 0.0469 0.0616 0.161 0.172 0.162 0.209 0.505

1x800 0.0367 0.0489 0.152 0.188 0.162 0.197 0.497

1x1000 0.0291 0.0378 0.143 0.216 0.162 0.186 0.487

1x1200 0.0247 0.0322 0.155 0.231 0.162 0.180 0.445

1x1600 0.0186 0.0246 0.147 0.251 0.162 0.173 0.437

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

95
Cu 76/132kV
HV cables with Longitudinal Water-Blocking System

Standard AS/NZS 1429.2

9 8 7 6 5 4 3 2 1

Construction:

1 Copper compact conductor 3 XLPE insulation 5 Semi conductive 7 Semi conductive


or Milliken conductor water-blocking tape water-blocking tape

2 Semi-conductive screen tape 4 Insulation screen 6 Cu wire screen 8 APL sheath


and Extruded conductor screen and Cu equalising tape

9 HDPE outer sheath


and Graphite coat
Application:

Cables are designed for fixed installation, for laying in the ground, for indoor applications and in cable ducts.

Properties:

Rated voltage U0/U (kV) 76/132 Min. temperature for laying (°C) 0

Max.short-circuit temperature (°C) +250 Min.storage temperature (°C) -10

Operating conductor temperature (°C) +90 Colour of insulation Natural

Temperature range for handling (°C) -10 up to +90 Colour of inner / outer sheath Client Requirement

Packaging Steel Drums

The current ratings are based on the following operating conditions:

Ambient air temperature 40℃

Ambient soil temperature 25℃

Soil thermal resistivity 1.2K.m/W

Depth of laying 1.0m

In air,shaded,no wind

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

96
Cu 76/132kV

Technical details

No. of cores Conductor Insulation Diameter Approx. Nominal Overall Cable mass Radius Radius Permissable
diameter thickness over insluation screen area thickness diameter appr. of bend of bend pulling force
of APL/HDPE during set
sheath installation in position
(mm2) (mm) (mm) (mm) (mm) (mm) (mm) (kg/km) (mm) (mm) [kN]

1x150 14.2 18.0 53.0 116.3 0.25/3.0 70.1 5579 1400 1050 10.5

1x185 15.9 18.0 54.7 116.3 0.25/3.1 71.9 6058 1450 1100 13.0

1x240 18.1 18.0 56.9 116.3 0.25/3.1 74.3 6726 1500 1150 16.8

1x300 20.3 18.0 59.1 116.3 0.25/3.2 76.6 7456 1550 1150 21.0

1x400 23.0 18.0 61.8 116.3 0.25/3.3 79.5 8440 1600 1200 28.0

1x500 26.0 18.0 64.8 116.3 0.25/3.4 82.7 9628 1650 1250 35.0

1x630 29.7 18.0 68.5 116.3 0.25/3.5 86.6 11257 1750 1300 44.1

1x800 34.0 18.0 72.8 116.3 0.25/3.6 91.2 13349 1850 1400 56.0

1x1000 39.5 18.0 80.5 116.3 0.25/3.8 98.8 15878 2000 1500 70.0

1x1200 43.5 18.0 84.5 116.3 0.25/3.9 103.0 18035 2050 1550 84.0

1x1600 49.2 18.0 90.2 116.3 0.25/4.1 109.1 22148 2200 1650 112.0

1x2000 55.2 18.0 96.2 116.3 0.25/4.3 115.5 26287 2300 1750 140.0

1x2500 61.5 18.0 102.5 116.3 0.25/4.5 122.2 31357 2450 1850 175.0

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

97
Cu 76/132kV

Current ratings

Continuous current-carrying capacity (A)


Fault current carrying
capacity for 1 second
In air In ground
No.
of cores Cond. Scr.

(mm2) Solid bond Solid bond Solid bond Solid bond (kA) (kA)

1x150 425 440 370 355 21.5 16.5

1x185 485 505 414 400 26.5 16.5

1x240 565 590 480 465 34.3 16.5

1x300 645 685 542 532 42.9 16.5

1x400 745 775 616 606 57.2 16.5

1x500 845 895 699 689 71.6 16.5

1x630 970 1020 790 780 90.2 16.5

1x800 1100 1165 880 870 114.5 16.5

1x1000 1280 1350 1000 980 143.1 16.5

1x1200 1400 1480 1080 1055 171.7 16.5

1x1600 1782 1884 1271 1247 229.0 16.5

1x2000 1993 2108 1392 1365 286.2 16.5

1x2500 2201 2327 1505 1476 357.8 16.5

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

98
Cu 76/132kV

Electrical parameters

No. Conductor Conductor Inductive Conductor Screen DC Zero Zero


of cores DC resistance AC resistance reactance to screen resistance sequence sequence
at 20 ℃ at 50Hz at 50Hz capacitance at 20 ℃ resistance react
and 90 ℃ and 90 ℃ at 20 ℃ at 50Hz

(mm2) (Ω/km) (Ω/km) (Ω/km) (µF/km) (Ω/km) (Ω/km) (Ω/km)

1x150 0.1240 0.1586 0.182 0.113 0.162 0.307 0.602

1x185 0.0991 0.1270 0.200 0.119 0.162 0.275 0.544

1x240 0.0754 0.0970 0.192 0.128 0.162 0.245 0.536

1x300 0.0601 0.0777 0.185 0.136 0.162 0.226 0.529

1x400 0.0470 0.0613 0.177 0.147 0.162 0.209 0.521

1x500 0.0366 0.0485 0.169 0.158 0.162 0.196 0.513

1x630 0.0283 0.0384 0.161 0.172 0.162 0.186 0.505

1x800 0.0221 0.0311 0.152 0.188 0.162 0.179 0.497

1x1000 0.0176 0.0232 0.143 0.216 0.162 0.171 0.487

1x1200 0.0151 0.0201 0.155 0.231 0.162 0.168 0.445

1x1600 0.0113 0.0156 0.147 0.251 0.162 0.163 0.437

1x2000 0.0090 0.0130 0.140 0.273 0.162 0.161 0.430

1x2500 0.0073 0.0111 0.133 0.296 0.162 0.159 0.423

All rights reserved. Any unauthorised usage, redistribution or reproduction of part or all of the content in any form will constitute an infringement of copyright. The data is only
indicative and should not be considered a binding representation or warranty from nkt cables concerning a product's properties or usability. The data page is not exhaustive and
should be read in conjunction with nkt cables other product data sheets, whether published or not. nkt cables reserves the right to change the data page. Without prior notice.
This is the 2016 Catalogue.

99
2016
06.2016/Product Catalogue MV and HV Cables Australia/Copyright

nkt cables Australia Pty Limited


Unit 12, 191 Hedley Avenue
Hendra
Queensland
Australia 4011

Tel: +61 7 3320 6600


Fax: +61 7 3868 1340

sales.au@nktcables.com
www.nktcables.com

You might also like