NFS-640 Fire Alarm Control Panel

Disclaimer: These battery calculations are designed exclusively for architects, engineers, consultants and NOTIFIER
authorized distributors to assist in the development of fire alarm equipment quotations. There are no implied warranties or
guarantees in the documents generated by this program other than the standard limited warranty offered by NOTIFIER.
NOTIFIER cannot ensure that any documents generated using this program meet all applicable codes and laws. The user of this
program must be familiar with required codes and laws as well as the requirements of the Authority Having Jurisdiction and
must amend the generated documents as necessary. At some point in time, some of these devices may no longer be available
from NOTIFIER.

This workbook contains battery calculation worksheets that allow you to:

Calculate AC branch current


Calculate system current draw
Determine battery size and select batteries
Create and print a summary of selected devices

Check for Updates Edit Database Help


Version 3.0
AC Branch Current
Select devices using the "Qty" column.
Use yellow cells to enter quantities and current values.
To show only selected devices, select "Show Selected Devices".
To clear selected devices, select "Clear Selections".
Note: These selections only determine the AC branch current. If these devices will affect the battery requirements, you
need to select them on the System Current Draw sheet.

1
120 VAC 220/240 VAC
Device Qty Current Total
Main Power Supply 1 x 3.00 A 3.00 A
AA-30 0 x 1.00 A
AA-120 0 x 1.85 A
ACPS-2406 0 x 2.70 A
APS-6R 0 x 2.50 A
AVPS-24 0 x 1.00 A
CHG-120 0 x 2.00 A
FCPS-24 0 x 2.00 A
FCPS-24S 0 x 3.20 A
MPS-24A 0 x 1.80 A
MPS-24B 0 x 2.40 A
XPIQ 0 x 3.50 A
XRM-24 0 x 1.00 A
ACPS-610 0 x 5.00 A
APS2-6R 0 x 2.90 A
DAA Series 0 x 4.50 A
HPFF8 0 x 3.60 A
HPFF12 0 x 5.00 A
DS-AMP (25V) 0 x 4.10 A
DS-AMP (70V) 0 x 3.55 A
NFC-50/100 0 x 3.50 A
NFC-50DA (25v) 0 x 1.10 A
NFC-50DA (70.7v) 0 x 1.20 A
NFC-125DA 0 x 2.20 A
DAA2-5025 0 x 2.05 A
DAA2-5070 0 x 2.13 A
DAA2-7525 0 x 2.82 A
DAX-5025 0 x 0.50 A
DAX-5070 0 x 0.55 A
DAX-3525 0 x 0.50 A
DAX-3570 0 x 0.55 A
[ ] 0 x 0.00 A
[ ] 0 x 0.00 A

1 AC Branch 3.00 A
Required:
System Current Draw - NFS-640

Total Current Primary Non-Alarm - C1


C1 0.230 A 0.2

C2 0.630 A 0.0 0.6 Power


1.2 Used1.8
(Amps)2.4 3.0
C3 0.230 A
C4 0.630 A

Device
1. System
CPU-640 (includes LCM-320)
KDM-2
System Power Requirements
Notifier NFS-640 Fire Alarm Control Panel

Protected Premises: Date:


Address:
City: State: Zip:

Prepared By: Phone:


Address: Email:
City: State: Zip:

AC Branch Current Requirements 3.00 AMPS @ 120 VAC


Current required by source to power the fire
alarm system.

Primary Standby Load 0.23 Amps


Current load on the primary power supply during
non-alarm conditions.

Primary Alarm Load 0.63 Amps


Current load on the primary power supply during
alarm conditions.

Secondary Load Requirements 6.69 Amp Hours


Total Secondary Load from the calculation table below.

Current Draw Time (hours) Total (AH)


Secondary Standby Load Required Standby Time
x
0.230 A 24 hours 5.52
Secondary Alarm Load Required Alarm Time (hours)
x
0.630 A 0.084 hours 0.05
Total Secondary Load 5.57
Derating factor x 1.2
Secondary Load Requirements (Amp Hours) 6.69 AH

Battery Selection 12 Amp Hours


Select batteries from the list below.
12 AH BAT-12120 Battery (12 volt)
Four (two 12VDC sets in
● Two
parallel)
1

Page 4 of 6
Battery Distribution Chart
Shows amp-hour distribution of your selections.

Spare Battery Capacity

Secondary Alarm Load Secondary Standby Load


1%

Secondary Alarm Load


Spare Battery Capacity
44%
Secondary Standby Load
55%

Comments
1. Batteries will fit in the FACP cabinet.
2. Selected battery size meets secondary load requirements.
3. The selected batteries (12AH) are within the charger range of this power supply (9-60AH).

Spare Battery Capacity 5.31 Battery Selection (AH) - Secondary Load Requirements (AH)
Secondary Standby Load 6.62 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 0.06 Secondary Alarm Load (AH) * Derating Factor

Page 5 of 6
Device Current Draw
NFS-640 Fire Alarm Control Panel
Quantity x [device current draw] = total current draw per device (in amps)
Part Number Qty Primary Non-Alarm Primary Alarm Secondary Non-Alarm
CPU-640 (includes LCM-320) 1 x [0.23000] = 0.23000 x [0.23000] = 0.23000 x [0.23000] = 0.23000
SLC Loop Device Activation Current 1 x [0.00000] = 0.00000 x [0.40000] = 0.40000 x [0.00000] = 0.00000

Total (Amperes): 0.2300 A 0.6300 A 0.2300 A

Part Number Qty Secondary Alarm


Total Primary Alarm Load - C2 1 x [0.63000] = 0.63000

Total (Amperes): 0.6300 A