You are on page 1of 4

Calculation of Power Supply for INDUSTRONIC Systems

Customer: Ramagundam Fertilizers and Chemicals, India


Project: Revival of RFCL
System no: 501-1301-100
Offer no./ order no: P371297
Document no.: PCA-501-1301-100+C2
System information

Power supply unit: PSG- 120/60/69


PSA- 120/60/80 309-799-613
309-799-124 Discharching current - batteries
Install. point power supply: C2 Quiescent current (Imin): 6,4 ADC
Standard: - Full load (Imax): 56,1 ADC
Amplifier connection: AC/DC Typical operation (Ityp): 0,0 ADC
Application: Backup
Batteries: VRLA Calculated rectifier current (60V): 56,9 ADC
: ja/yes
: nein/no Mains input (115V)
Mains voltage: 115V Maximum alternating current (115V): 42,0
046 AAC
System voltage: 60V Power rating: 4830,0
5313,00WW

Calculated battery capacity: 39,0534375


Battery set: 5 NSV 40 225-117-300 Power dissipation (complete system): 1309,68 W 4471,41 BTU/h

Cabinet information

1309,68 W
Cabinet number: C2 Power dissipation:
4471,41 BTU/h
Contains power supply: ja/yes

Included system components

No. Single current Sum current

Basic components
1 DXC xx Exchange control board 2 0,189 ADC 0,378 ADC
3 DCR xx Monitoring board 1 0,015 ADC 0,015 ADC
12 DDL xx Digital line card 5 0,035 ADC 0,175 ADC
4 DAP xx Digital audio processor 1 0,035 ADC 0,035 ADC
12 DFK xx DC fuse kit 5 0,035 ADC 0,175 ADC
10 GW xx DC/DC converter board 2 0,060 ADC 0,120 ADC
Total: 0,369 ADC 0,898 ADC
Intercom stations and other equipment
.. DT/DE/DSS xx Desktop intercom station 3 0,150 ADC 0,450 ADC
.. DA xx/25 Outdoor intercom station with DVA 20 0,810 ADC 16,200 ADC
.. DX xx/25 Ex.-proof intercom station with DVX 37 0,820 ADC 30,340 ADC
Total: 1,780 ADC 46,990 ADC
Accessories
2 FL xx Fan 1 0,334 ADC 0,334 ADC
Total: 0,334 ADC 0,334 ADC
Amplifiers / audio modules
250 DVE xx Dig. amplifier 1 3,000 AAC 3,000 AAC
Total: 3,000 AAC 3,000 AAC

04-OCT-2017
BASU MEHUL (C988)

Page 1 of 4
h a n g e Vi h a n g e Vi
XC e XC e
F- w F- w
PD

PD
er

er
!

!
W

W
O

O
N

N
y

y
bu

bu
to

to
k

k
lic

lic
C

C
w

w
m

m
w w
w

w
o

o
.d o .c .d o .c
c u -tr a c k c u -tr a c k

Calculation of Power Supply for INDUSTRONIC Systems


Customer: Ramagundam Fertilizers and Chemicals, India
Project: Revival of RFCL
System no: Exchange I
Offer no./ order no: P371297
Document no.: PCA-501-1301-100+C1
System information

Power supply unit: PSG-


----- 120/60/160 309-799-617
----- Discharching current - batteries
Install. point power supply: C1 Quiescent current (Imin): 0,0 ADC
Standard: - Full load (Imax): 0,0 ADC
Amplifier connection: AC/DC Typical operation (Ityp): 0,0 ADC
Application: Backup
Batteries: - Calculated rectifier current (60V): 133,8 ADC
N+1 technology: ja/yes
Automatic mains change-over: nein/no Mains input (115V)
Mains voltage: 115V Maximum alternating current (115V): 98,0
3,30 AAC
AAC
System voltage: 60V Power rating: 11270,0
379,50 WW

Calculated battery capacity: -----


Battery set: No battery required ----- Power dissipation (complete system): 2952,97 W 10081,849 BTU/h

Cabinet information

2952,97 W
Cabinet number: C1 Power dissipation:
10081,849 BTU/h
Contains power supply: ja/yes

Included system components

No. Single current Sum current

Basic components
1 DXC xx Exchange control board 2 0,189 ADC 0,378 ADC
3 DCR xx Monitoring board 1 0,015 ADC 0,015 ADC
12 DDL xx Digital line card 13 0,035 ADC 0,455 ADC
4 DAP xx Digital audio processor 1 0,035 ADC 0,035 ADC
16 DCI xx Control unit for I/O modules 1 0,006 ADC 0,006 ADC
3 DRU xx Relay unit 1 0,060 ADC 0,060 ADC
12 DFK xx DC fuse kit 13 0,035 ADC 0,455 ADC
10 GW xx DC/DC converter board 2 0,060 ADC 0,120 ADC
Total: 0,435 ADC 1,524 ADC
Intercom stations and other equipment
.. DT/DE/DSS xx Desktop intercom station 6 0,150 ADC 0,900 ADC
.. DA xx/25 Outdoor intercom station with DVA 35 0,810 ADC 28,350 ADC
.. DX xx/25 Ex.-proof intercom station with DVX 110 0,820 ADC 90,200 ADC
Total: 1,780 ADC 119,450 ADC
Accessories
2 FL xx Fan 2 0,334 ADC 0,668 ADC
Total: 0,334 ADC 0,668 ADC
Amplifiers / audio modules
250 DVE xx Dig. amplifier 1 3,000 AAC 3,000 AAC
Total: 3,000 AAC 3,000 AAC

1. please submit the filled in resolution sheet to EIL comments along with this document.
2. Cable dimension data shall be as per attached sheet

04-OCT-2017
BASU MEHUL (C988)

Page 2 of 4
h a n g e Vi h a n g e Vi
XC e XC e
F- w F- w
PD

PD
er

er
!

!
W

W
O

O
N

N
y

y
bu

bu
to

to
k

k
lic

lic
C

C
w

w
m

m
Core Size (sq mm) OD O/A dia U/A dia
w w
w

w
o

o
.d o .c .d o .c
c u -tr a c k c u -tr a c k

2 185 39 33.8 32.2


3 95 34.5 31 29.4
2P 1.5 16 13.5 10.5
5P 0.9 mm dia 14.9 12.3 9.5

Tolerance shall be +/- 2mm

04-OCT-2017
BASU MEHUL (C988)
No Comments

04-OCT-2017
BASU MEHUL (C988)

Page 4 of 4