Professional Documents
Culture Documents
3X Node [Copy for Additional Nodes] 12 User Entries Count On This Sheet 1 Node Counter
Job Name: 0 6 Total SIGA loops this node 0 T4 sounder count
Node No: 0 Total analog loop this node 0 Module Addresses this sheet
Node Name: 0 Serial ports used this node
Battery Calculations 1 System Brand
System Loading
Battery Periods
36 Battery standby supervision period in hours 36 Battery standby time in hours, this node only
15 Battery fire alarm period in minutes 15 Battery fire alarm time in minutes, this node only
Total System Loads
1426 Notification alarm current
99 Remote annunciator standby current, 3-ANN sheets
115 Remote annunciator alarm current, 3-ANN sheets
17 Door holder current required while system is normal
Ex Stby Ex Alm Stby mA Alm mA s a A
Panel NAC #1 113 1541 17
1 Enter 1 if NAC#1 is an Auxiliary Output
1426 Enter notification alarm current for NAC#1 1426 Note: SIGA-CC1s required for signaling devices
99 Enter Remote Annunciator Standby Current connected to AUX #1 99 Ok
115 Enter Remote Annunciator Alarm Current connected to AUX #1 115 Ok
17 Enter door holder supplied by AUX #1 while system is normal 17
14 Enter door holder power standby current connected to AUX #1 14
External Loads 113 1541
CO Loading 0 0
Qty Cat No Description Ex Stby Ex Alm Stby mA Alm mA RailSp DisSp A
System Components
EST3X System Components
1 3X-SFS1B FACP /w CPU, 1 loop, 4 NACs, 10A power supply, bronze 378 482 378 482 3
1 3-SDC1 Signature Driver Module 120 132 120 132
2 3-SDDC1 Signature Dual Driver Controller (LRM) 528 672 264 336 -2 2
1 FSB-PC2 Field Server Bridge for MODBUS, BACKNET reqyuirements 60 95 60 95 -1 1
No Standby Standby Amplifier 0 0
Display/Control Modules
1 4X-24R 24 Red LED Display Module 2 38 2 38 -1
Network and communications
1 3X-NET8 Network option card, RS485, Cl A or B, max 8 nodes 98 98 98 98
Total Panel Current w/o remote mics 1186 1517