Professional Documents
Culture Documents
February 2017
Client Details
Contact N/A
Client Name
Address
Zephir Ltd. (ZephIR Lidar), accept no responsibility or liability for any use which is
made of this document other than by the Client for the purpose for which it was
originally commissioned and prepared. The Client shall treat all information in the
document as confidential. No representation is made regarding the completeness,
methodology or current status of any material referred to in this document. All facts
and figures are correct at time of print. All rights reserved. ZephIR® is a registered
trademark of ZephIR Lidar.
This document details the procedure for measuring WYM using a ZephIR DM wind lidar mounted on the nacelle of
a WTG. It covers configuration of the lidar and analysis of the measurement data. Detailed instructions for the
installation of the lidar on the nacelle of the WTG can be found in a separate procedure [1].
If a significant WYM is identified, it is recommended that the operator engages with the maintenance team
responsible for the WTG and/or the manufacturer of the WTG to correct the control system to eliminate the WYM.
Due to the nature of the measurement, this may be an iterative process of measurement, correction, measurement
and correction.
The wind yaw misalignment is defined as the angle between the incoming wind direction and the axis of the WTG.
From the perspective of the lidar, looking forward into the wind, a positive WYM is defined as a wind direction from
the right of the WTG’s axis (see Figure 2.1 and Figure 2.2, below). For the WTG to operate at maximum efficiency
the WYM should be zero.
Figure 2.1: View from above: positive WYM Figure 2.2: View from above: negative WYM
Parameter Notes
Check time zone and timestamp convention.
Time and Date
Timestamp is often end of 10 minute averaging period.
Active Power Used to filter out periods for which the turbine is not active, i.e. when Power < 5 kW
Turbine Operational Flag Used to filter out periods for which the turbine is not operational
Compare time series to wind speed measured by ZephIR to check synchronisation
Nacelle wind speed
of data series
1. Download “Wind10_” ZPH data files from the ZephIR DM and SCADA data from the turbine’s SCADA system.
2. Convert ZPH files to CSV using Waltz or ZPH2CSV software.
3. Synchronise ZephIR and SCADA data, correcting for any difference in time zone and timestamp
– Check by comparing time series of wind speeds measured by nacelle anemometer and ZephIR.
4. Filter out data if any of the following are true:
– Turbine is not operational;
– Active power < 5 kW;
– ZephIR WYM > 9000 (i.e. is error code);
– Normalised Mean Fit Residual (MFR / HWS) > 0.04.
5. Using ZephIR data collected to date (after filtering as above), calculate running estimates of:
– Number of valid measurements (N);
– Mean WYM at the required measurement range (μ);
– Standard deviation about the mean WYM (σ);
– Standard error in the mean WYM (σ / √N).
6. Continue collecting data until the standard error in the mean WYM is reduced below 0.2°.
7. Apply a correction to the turbine control system indicated by the mean WYM measured by the ZephIR DM.
8. Repeat steps 1-7 until the mean WYM is at the required level.
NB: If the power supply to the ZephIR DM is interrupted, measurement data can be split across more than one file.
If gaps are seen in the ZephIR data record, missing measurement files can be downloaded from the ZephIR
DM using the Waltz software.
Figure 5.1: Waltz “Configuration” screen, “Site” tab, showing recommended settings
Figure 5.3: Mean and standard error of measured wind yaw misalignment before correction
This plot shows that the target of 0.2° for the standard error in the mean WYM was reached within 4 days of
measurement. This period would have been longer had the turbine not been operational for 100% of the time. The
running mean WYM after 4 days had converged to a value of about +7°.
Figure 5.5: Mean and standard error of measured wind yaw misalignment after correction
2003 - The first wind lidar to make upwind measurements from a turbine nacelle
2004 - The first and original commercially available lidar for the wind industry
2004 - The first wind lidar to investigate the behaviour of turbine wakes
2005 - The first wind lidar to be deployed offshore on a fixed platform
2007 - The first wind lidar to take measurements from a turbine spinner
2008 - The first wind lidar to be signed off against an industry-accepted validation process
2009 - The first wind lidar to be deployed offshore on a floating platform (SeaZephIR)
2010 - The first wind lidar to re-finance and re-power a wind farm
2011 - The first wind lidar to be proven in a wind tunnel
2012 - The first wind lidar to be used with very short masts and secure project financing
2012 - The first wind lidar to be accredited for use with no or limited on-site anemometry for project financing by DNV GL
2013 - The first wind lidar to provide true dual-mode functionality in one platform (ZephIR DM)
2014 - The first wind lidar to be subjected to more than 170 performance verifications against an IEC compliant test site
2015 - The first wind lidar to be deployed in dual configuration as standard on floating offshore platforms
---
UK
Head Office > England
The Old Barns, Fairoaks Farm
Hollybush, Ledbury HR8 1EU
ENGLAND, UK
zephirlidar.com
sales@zephirlidar.com
No part of this document or translations of it may be reproduced or
transmitted in any form or by any means, electronic or mechanical
including photocopying, recording or any other information storage
and retrieval system, without prior permission in writing from
ZephIR Lidar. All facts and figures correct at time of print.
ZephIR DM Procedure: How to Measure Wind Yaw Misalignment
All rights reserved. © Copyright 2017 February 2017 12