Professional Documents
Culture Documents
FOR
COOLING WATER PUMP
19/10
fahri , 19/10/2020 ,09:39:07
2020
PJW & MFA
Revision Sheet
Table of Content
1. Attachment ............................................................................ 4
Data sheet for three-phase Squirrel-Cage-Motors
Project:
U Δ/Y f P P I n M NOM. EFF at ... load [%] Power factor at ... load IA/IN MA/MN MK/MN IE-CL
[V] [Hz] [kW] [hp] [A] [1/min] [Nm] 4/4 3/4 2/4 4/4 3/4 2/4 II/IN TI/TN TB/TN
96' 400 Δ 50/60 200.00 -/- 360.00 1788 1230.0 95.4 95.6 95.3 0.88 0.86 0.80 6.0 3.2 3.0 IE3
'2/ 400 Δ 50/60 200.00 -/- 345.00 1791 1070.0 96.2 96.2 95.5 0.87 0.84 0.75 6.0 3.5 3.2 IE3
IM B3 / IM 1001 FS 315 L 1190 kg IP65 IEC/EN 60034 IEC, DIN, ISO, VDE, EN
Locked Rotor Time : 40s (Cold), 20s (Hot) Full Load Current : 360 A
No Load Current : 110 A
Frame material cast iron L19 Regreasing device with regreasing nipple M10X1 acc.to DIN 71412-A
Data of anti condensation heating 230 V, 109 W L51 Bearing insulation NDE
Special paint finish, resistant to M2J 400 VD/690 VY; 60Hz, 50-Hz power
Coating (paint finish) salt-laden air C4
Q02 Anti-condensation heating for 230 V (2 terminals)
Color, paint shade RAL7030
Q72 2 Pt100 resistance thermometers in basic configuration for bearings (4 terminals)
(C) 6 PTC thermistors - for alarm and tripping (4
Motor protection terminals) R62 Cast iron auxiliary terminal box (small)
Method of cooling IC416 - separately ventilated, surface cooled S03 Special paint finish in sea air resistant C4
Environmental conditions
Ambient temperature -20 °C - +40 °C
Notes
IA/IN = locked rotor current / current MK/MN = break down torque / nominal torque
MA/MN = locked rotor torque / torque 1) Value is valid only for DOL operation with motor design
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1/1 Version: 2016.10
Generated: 30.07.2020 08:56:13