MEDIUM VOLTAGE POWER CABLES

25kV Copper Conductor, XLPE Insulated,


Copper Tape Shielded, PVC Jacketed, Single Conductor

Insulation
Jacket Shield
Conductor
Shield

Conductor
Copper Tape
Insulation

Detailed Description or Construction Insulation Levels


100 Percent Level = Cables in this category may
be applied where the system is provided with
Conductor relay protection such that ground faults will be
Compact round stranded copper conductor cleared as rapidly as possible, but in any case
Conductor Shield within 1 minute.
Thermosetting extruded semi-conducting compound 133 Percent Level = This insulation level
Insulation corresponds to that formerly designated for
Cross-linked polyethylene (XLPE) 90°C underground systems. Cables in this category
Insulation Shield
may be applied where the clearing time
Thermosetting extruded semi-conducting compound
Metallic Shield requirements of the 100 percent level category
Copper tape shield cannot be met, and yet there is adequate
Jacket assurance that the faulted section will be de-
Polyvinyl chloride (PVC) energized in a time not exceeding 1 hour.

Reference Standards Application


ICEA S - 93 - 639 Primary power and distribution circuits in
industrial, commercial and power circuit
generating plants. Single conductor cables, 1/0
AWG and larger, can be marked for CT use to be
Voltage Rating installed in ladder cable tray as per NEC 318.
25kV

Temperature Rating Installation


Cables may be installed indoor and outdoor,
Normal Condition
exposed to sunlight, in raceway, conduit, duct or
90°C
aerially supported by a messenger and directly
Emergency Condition
130°C buried as per NEC 250-51.
Short-circuit Condition
250°C

Customer Approval
Executive office: Manufacturing Plant:
2297 2/F BCS Prime Bldg. Pasong Luisita Industrial Park Name
Tamo Ext. Makati City, Philippines San Miguel, Tarlac City Philippines Date
T. (632) 813-2529 T. (6345) 985-1088 to 91
F. (632) 893-4990 Signature
MEDIUM VOLTAGE POWER CABLES
25kV Copper Conductor, XLPE Insulated,
Copper Tape Shielded, PVC Jacketed, Single Conductor

25kV 100%IL
Allowable
Conductor Overall Cable Minimum
Equivalent Minimum Insulation ampacities Standard
Size diameter diameter weight bending
copper size number thickness in free air packing
(approx.) (approx.) (approx.) radius
of wires @ 40°C
mm² AWG / MCM mm mm mm kg / km A mm m / reel
38 1 18 7.6 6.60 29.2 1,164 195 350 500
50 1/0 18 8.5 6.60 30.1 1,297 225 361 500
60 2/0 18 9.6 6.60 31.2 1,470 260 374 500
80 3/0 18 10.8 6.60 32.3 1,676 300 388 500
100 4/0 18 12.1 6.60 33.6 1,926 345 404 500
125 250 35 13.2 6.60 34.8 2,149 380 417 500
150 300 35 14.4 6.60 36.0 2,430 425 432 500
200 400 35 17.6 6.60 39.2 2,972 507 471 500
250 500 35 18.6 6.60 40.2 3,506 580 482 500
300 600 58 20.4 6.60 42.0 4,044 640 504 500
325 650 58 21.2 6.60 44.7 4,491 670 537 500
350 700 58 22.0 6.60 45.5 4,758 700 546 500
375 750 58 22.8 6.60 46.4 5,034 730 556 500
400 800 58 23.6 6.60 47.1 5,291 750 565 300
450 900 58 25.0 6.60 48.5 5,824 802 582 300
500 1000 58 26.3 6.60 49.8 6,321 850 598 300

25kV 133%IL
Allowable
Conductor Overall Cable Minimum
Equivalent Minimum Insulation ampacities Standard
Size diameter diameter weight bending
copper size number thickness in free air packing
(approx.) (approx.) (approx.) radius
of wires @ 40°C
mm² AWG / MCM mm mm mm kg / km A mm m / reel
38 1 18 7.6 8.13 32.2 1,324 195 387 500
50 1/0 18 8.5 8.13 33.1 1,461 225 398 500
60 2/0 18 9.6 8.13 34.2 1,639 260 411 500
80 3/0 18 10.8 8.13 35.4 1,849 300 425 500
100 4/0 18 12.1 8.13 36.7 2,106 345 440 500
125 250 35 13.2 8.13 37.8 2,334 380 454 500
150 300 35 14.4 8.13 39.1 2,620 425 469 500
200 400 35 17.6 8.13 42.3 3,172 507 507 500
250 500 35 18.6 8.13 45.1 3,908 580 542 500
300 600 58 20.4 8.13 47.0 4,462 640 564 500
325 650 58 21.2 8.13 47.8 4,724 670 573 500
350 700 58 22.0 8.13 48.6 4,996 700 583 500
375 750 58 22.8 8.13 49.4 5,275 730 593 500
400 800 58 23.6 8.13 50.1 5,535 750 602 300
450 900 58 25.0 8.13 51.6 6,075 802 619 300
500 1000 58 26.3 8.13 52.9 6,578 850 635 300

+Diagrams of cables are illustrative only and not necessarily to scale. PDP reserves the right to change or vary the construction of any of their products without notice.
While every care has been taken in the preparation of this data sheet, PDP accept no liability of any kind and are not responsible for the results of any actions taken on
the basis of this information or resulting from errors or omissions. This technical data sheet is intended as a guide only; any person using it must make reference to
the appropriate local standards or authorities.