You are on page 1of 3

PRODUCT ANNOUNCEMENT

Ref No.: 08GMSPG0606PA014-0 Date: Jun 06, 2008


Subject: BMH18-50 Change new Defrost board

1. Effective model
Size Old model (Set) New model (Set) V/Ph/Hz Old PCB New PCB
18K BMH18R16A-GW BMH18R16A-GWM 208-230/1Ph/60Hz ELECTRA MAJOR
25K BMH25R16A-GW BMH25R16A-GWM 208-230/1Ph/60Hz ELECTRA MAJOR
27K BMH27R16S33-GW BMH27R16S33-GWM 208-230/1Ph/60Hz ELECTRA MAJOR
36K BMH36R16A-GW BMH36R16A-GWM 208-230/1Ph/60Hz ELECTRA MAJOR
36K BMH36R16S33-GW BMH36R16S33-GWM 208-230/1Ph/60Hz ELECTRA MAJOR
50K BMH50R16A-GW BMH50R16A-GWM 208-230/1Ph/60Hz ELECTRA MAJOR
50K BMH50R16S33-GW BMH50R16S33-GWM 208-230/1Ph/60Hz ELECTRA MAJOR

2. Configuration
Change defrost board: Electra to Major

3. Effective date and orders number launch.


- PO 116962, PO 32355

Best Regards,

Kriangkrai Nalao

Kriangkrai Nalao
Senior Technical Engineer
GMSPG

Johnson Controls International (Thailand) Co.,Ltd.


131/54 Moo 9 Sukumvit Road, Tambol Nongprue,
Amphur Banglamung, Chonburi 20150, Thailand
Tel : (038) 377489
Fax : (038) 377282
www.johnsoncontrols.com
Details Function Defrost PCB
Features

A/C starts working and prevents defrosting at the beginning of 45 minutes,after 45


minutes the interface controller will check defrosting condition that illustrate in the chart below.

When any of sensor temperature of compressor <= -6 co the outdoor defrost


operation is activated. All compressors and outdoor fan are turned off. After 30 seconds delay,
all 4 way valves will be turned off,5 seconds later first compressor is turned on and 2 seconds
later the rest of compressor are turned on consecutively.
When any of sensor temperature of compressor =>12 co or 10 minutes has elapsed,
the defrost operation will be terminated. Then all compressors are turned off. After 30
seconds delay, all 4 way valves are turned on, 5 seconds later, outdoor fan and first
compressor are turned on and 2 seconds later the rest of compressor are turned on
consecutively to return to heating operation.

Johnson Controls International (Thailand) Co.,Ltd.


131/54 Moo 9 Sukumvit Road, Tambol Nongprue,
Amphur Banglamung, Chonburi 20150, Thailand
Tel : (038) 377489
Fax : (038) 377282
www.johnsoncontrols.com
Details Picture Defrost PCB

Old Defrost PCB From Electra 2&3 compressors

New Defrost PCB From Major


For 2 compressors For 3 compressors

Johnson Controls International (Thailand) Co.,Ltd.


131/54 Moo 9 Sukumvit Road, Tambol Nongprue,
Amphur Banglamung, Chonburi 20150, Thailand
Tel : (038) 377489
Fax : (038) 377282
www.johnsoncontrols.com