You are on page 1of 15

Extended MAPLA troubleshooting

How to Check the GTS MAPLA – additional information


Warning: At first observe strictly the safety information at the operating instructions.
Beware of high voltage direct current up to 380VDC!
The following instruction refers to the old MAPLA system. If you have an INT = iMAPLA system it
is recommended to read out the MMI error flash code (MMI indications) at first. The
troubleshooting of an iMAPLA system is quite similar to the old MAPLA system.

First see in the operating instructions at page 75 – 4.9 Troubleshooting

If an overload condition occurs (LED No. 5 lights):


For further information you look in the operating instructions at page 75 (troubleshooting procedure). An
overload condition occurs, if the magnet plate is oversized or damaged by taking a too high magnet
current. At first check the resistance of the magnet plate. Ensure that the magnet plate is unplugged.
Check the result with the following resistance table:
Magnet plate resistance for GTS systems (actual MAPLA)
maximum minimum
min. insulation
rated allowed magnet allowed magnet
GTS MAPLA System Watts
Voltage
max. Amps
plate resistance plate resistance
resistance in
Ohms
(minimum load) at 20°C / 68°F

8 KW Magnet System 8.000 230 35 45 7,6 50.000


9 KW Magnet System 9.000 230 39 45 6,8 50.000
11 KW Magnet System 11.000 230 48 45 5,5 50.000
13 KW Magnet System 13.000 230 57 45 4,7 50.000
17 KW Magnet System 17.000 230 74 45 3,6 50.000
20 KW Magnet System 20.000 230 87 23 3,0 50.000
25 KW Magnet System 25.000 230 109 23 2,4 50.000
30 KW Magnet System 30.000 230 130 23 2,0 50.000

If the resistance is undersized, take a smaller magnet plate (with a higher resistance) and connect it to
the generator system. Check the System again and measure the magnet current.
Note: A warm plate has a higher resistance than a plate at 20°C / 68°F.

If the resistance is normal or higher than allowed, check the magnet plate with the high voltage
megaohmmeter. Ensure that the magnet plate is unplugged from the machine. If the resistance between
the case and the active conductor is less than 50 KiloOhms the magnet plate is damaged. The rated
insulation resistance of a new plate is higher than 500 KiloOhms.

If an short circuit condition occurs (LED No. 5 flashes):


For further information you look in the operating instructions at page 75 (troubleshooting procedure). A to
high current (short current) causes a cut-off of the generator immediately. This is necessary to protect
the electronic, the generator and the cables against overloads.
If it is the first time you start up the system, check the pin assignment at output for magnet plate.
black
gray

1 1

2 2

brown
blue

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 1 -
Extended MAPLA troubleshooting

Note: To measure the insulation resistance by an insulation-monitor (optional for MAPLAs available)
the green/yellow wire should be connected to the magnet plate!

Next check the magnet plate resistance (see above at overload condition).

Further you have to check the power cable to the magnet plate against shorts and breaks or insulation
errors.

Perform a reset of the generator/system. If the fault occurs again, unplug the magnet power connector at
the generator (only the connection to the magnet plate) and reset the system again. Start the generator
and activate the magnet with the joystick button. If the LED No. 4 lights after a few seconds the MAPLA
system is alright. If already the error exists (LED No. 5 flashes), the electronic has an internal fault.
Change the electronic case at the generator and try again. You can check the power unit and the rectifier
with a simple circuit analyzer (see below at page 2).

How to check the power unit (amplifier) and the rectifier in the electronic case:
To test the power modules of the MAPLA take a rectifier analyzer to check the forward voltage of the
discrete diodes. The description how to contact the MAPLA is written at page 7 and 8. At first you have
to disconnect all connectors from the generator, the regulator and the magnet plate.
TEST RECTIFIERS TEST IGBT-MODULE

J1 / Pin Ux

J5 / Pin 5 J1 / Pin Vx OUT1


J5 / Pin 5
J1 / Pin Wx OUT2

J1 / Pin Ux OUT1
J6 PIN J6
J6 J1 / Pin Vx OUT2
(in 8-17KW MAPLA)
J1 / Pin Wx

The forward voltage of the rectifier/diode is approx. 0,35V to 0,7V. If you have a breakdown of one diode,
the forward voltage in both directions is 0,0V and so the power-module is damaged.

No power supply voltage for MMI available:

Defect characteristics: The generator is running and active but the power supply LED No.1
at the MMI is off (does not light).

Check the generator speed. The rated speed range of the generator is written in the default value table
(see below at page 6). Build sizes of 132 need a minimum of 2800 rpm. Build sizes of 160 need a
minimum of 2200 rpm.

Check the exciter fuse, connected in row to the exciter line PIN1/F1 connected to the voltage regulators
in the top of the case. Therefore you need only to open the case of the switch-box. If the exciter fuse is
blown, it is recommended to change the voltage regulator and the fuse at the same time. GTS specifies
to use a “Multicomp 3A slow blow 6.3x32mm 250V” type.

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 2 -
Extended MAPLA troubleshooting

Check the connections between the regulator, the generator and the electronic case.

Check the MMI cable. Test the connection of every wire from the electronic case to the MMI. Check also
the fuse of the MMI in the electronic case (see description below at page 7 and 8).
Note: do not twist the fuse, only twist the cover to release the fuse

Check the generator main winding resistance with an Ohmmeter. For it take the connection plan of the
next picture (see below) and the default value table at page 6. If one of the results is out of the range, the
generator could be damaged.

It is also important, to check the insulation resistance of the stator main windings with a high voltage
megohmmeter. Therefore you have to unplug the connector between the generator and the controller
box. Ensure that you have no connection to the electronic case. The pin-connection of the generator is
described at the two pictures below. Measure the insulation resistance with 500V (megohmmeter)
between all connections and the case of the generator. If the resistance is less than 50KiloOhms the
generator is damaged.

The generator could also have lost the remanence (retentivity). If there is no rest of magnetism in the
generator, the remanence voltage of the generator at idle running is less than 10VAC. This case causes
that the regulator could not supply the exciting winding with current to build up the required magnetic
field. Therefore the output voltage at the main machine is too low.
You can check the remanence voltage of the generator. At first ensure that the generator is not rotating
(stop the engine). Then you have to disconnect the connection of the generator to the electronic case.
Ensure, that the regulator is disconnected.
Take a voltmeter and set it to VAC-mode. Measure the voltage between the three phases U / V / W while
you run the generator at the rated speed. The default remanence voltage range is written in table at
page 6.

MAPLA Generator 8KW to 20KW MAPLA Generator 25KW to 30KW

+F1 W1 V1 U1
U
V
F2
+F1 W

F2 W2 V2 U2

If the voltage is less than 10VAC, it is possible to rebuild the remanence. Stop the generator and take a
12V DC-power supply (approx. 10W power). Connect the pin +F1 with the +12V conductor and the –F2
pin with the ground (GND) conductor of the supply. A current of approx. 0,5A rebuilds the remanence in
the generator (if it’s possible drive the generator with approx. 1500rpm). Supply the generator with this
current only for 2-3 seconds. Following, check the remanence voltage between the phases again while
the exciting current is again zero (no regulator connected).

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 3 -
Extended MAPLA troubleshooting

Not enough output voltage at the magnet plate:

Defect characteristics: The generator is running and the output voltage at the magnet
plate is less than 200 VDC (result: not enough power).

Check the generator speed. If the speed is less than the rated values in the default value table (see
below) the generator is not able to supply the electronic with the required power.

Check the connections between the regulator, the generator and the electronic case.

Check the exciting voltage at ST1 between 1F1 & 1F2 (red and grey wire) with a voltmeter set to mode
VDC. Note, that the voltmeter is able to measure “true-RMS”-voltages. Check the result with the default
value table (see below). If the voltage is too high and the exciting current is higher than 2,0A the
generator could be damaged (one of the rotating rectifiers).

Next check the generator main winding resistance with an Ohmmeter. For it take the connection plan
(see above) and the default value table at page 6. If one of the results is out of the range, the generator
could be damaged.

It is also able that one of the rotating diode in the generator is damaged. This causes a loss of exciting
field (rotor) in the main machine of the generator. So we have only a weak magnetic field, which could
not induce the rated voltage at the stator winding (power loss). In this case you can also check the
exciting current of the regulator. If you have in a no load mode (magnet off) at the rated speed a low
output voltage and the exciting current of the regulator is higher than 2,0ADC then it could be possible,
that the exciter or one of the rectifier inside of the generator is damaged. To measure the exciting
current, see the description at page 6.

Too high output voltage at the magnet plate:

Defect characteristics: The generator rotating at rated speed generates a too high output voltage
to the magnet plate. The static voltage is higher than 250 Volt DC.

(Note: The voltage to fast magnetisation is up to 280 Volt DC for


only 3-5 seconds after you have switched-on the magnet.
The too high output voltage for a long time causes also a
overload condition of the MAPLA System displayed with
LED no. 5 at the MMI )

Check the impulse excitation interface ST2 (white wires) to the regulator connected to the MAPLA
electronic. By a contact fault, the output voltage of the generator is constant higher than 275Volt DC.

Check the voltage between the three yellow wires at the regulator connection ST1. Between every
conductor you have to measure the voltage of the three phases from the generator. Check the results
with the default value table at page 6. If there is one phase missing, the measured actual value of the
regulator is wrong. So the regulator set a too high exciting current to the generator. This causes the over
voltage of the system.

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 4 -
Extended MAPLA troubleshooting

Slow system / long drop time:

Defect characteristics: The generator is rotating at rated speed but the load at the magnet plate
falls down very slowly. This causes a long cycle time.

First check the voltage at magnet plate. Ensure that the Mode-Switch is in A-Position (normal mode).
After switch on (push the joystick-button) the magnet voltage should be 280VDC for 2-3 seconds. This
phase is called fast-magnetisation (fast pick-up) with impact excitation. While the magnet is on the output
voltage to the magnet should be 230VDC constant should be after 3 seconds
(rated voltage of the magnet).

If the magnet voltage is never 280VDC for a short time after switch on, check the voltage regulator
contacts an also the connection of the interface ST2 (see pictures at page 7 and 8).

In the drop phase (material falls down) the output voltage at the magnet should be negative for several
times. The polarity of the output voltage is changed 5 times so achieve the elimination of the rest of
magnetism at the magnet plate. If the discharger unit is damaged, the electronic box could not change
the output voltage. This causes a slow drop cycle (takes a long time).

To check the discharger resistances (see the pictures below) take a normal ohmmeter and check the
resistance values.
(20Ohms for every resistance in 8-17KW systems / 5Ohms for every resistance in 20-30KW systems)

MAPLA Generator 8KW to 17KW MAPLA Generator 20KW to 30KW

R1 = 5 Ohm
R4 R2 = 5 Ohm
R2 R3 = 5 Ohm
R1

R3 R3

R1 R1 R1 R2 R3 R2 R3
R2

R1 = 20 Ohm R4
R2 = 20 Ohm Note:
R3 = 20 Ohm in a 20KW system
only two resistors
R4 = 20 Ohm R1 & R2 are connected

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 5 -
Extended MAPLA troubleshooting

Default values of all GTS MAPLA - Systems:

generator (build size 132) 8KW 11KW / 13KW 17KW 20KW


resistance exciting winding at 20°C/68°F [Ohm] 24 Ohms to 26 Ohms
resistance main stator winding U to V [Ohm] approx. 0,5 Ohms approx. 0,5 Ohms approx. 0,4 Ohms approx. 0,4 Ohms
resistance main stator winding V to W [Ohm] approx. 0,5 Ohms approx. 0,5 Ohms approx. 0,4 Ohms approx. 0,4 Ohms
resistance main stator winding W to U [Ohm] approx.0,5 Ohms approx.0,5 Ohms approx. 0,4 Ohms approx. 0,4 Ohms
generator speed range [rpm] 2850 rpm to 4000 rpm
no load running mode value range (measured @ 3000rpm)
regulated generator voltage U to V [VAC] 175V to 185V 174V to 184V 179V to 187V 174V to 184V
regulated generator voltage V to W [VAC] 175V to 185V 174V to 184V 179V to 187V 174V to 184V
regulated generator voltage W to U [VAC] 175V to 185V 174V to 184V 179V to 187V 174V to 184V
remanence voltage between the every phase only if
30V to 70V 30V to 70V 30V to 70V 30V to 70V
the regulator is disconnected @ 3000rpm [VAC]
exciting voltage at ST1 / 1F1 to 1F2 [VDC] 10V to 25V 6V to 20V 4V to 18V 10V to 25V
exciting current of the regulator [ADC] 0,3A to 0,6A 0,2A to 0,5A 0,2A to 0,5A 0,3A to 0,6A
load running mode value range (measured @ 3000rpm)
output voltage at the magnet plate [VDC] 220V to 238V
maximum magnet current [ADC] 35A 47A (11KW) / 56A (13KW) 74A 87A
generator voltage U to V [VAC] 175V to 185V 172V to 184V 172V to 180V 174V to 183V
generator voltage V to W [VAC] 175V to 185V 172V to 184V 172V to 180V 174V to 183V
generator voltage W to U [VAC] 175V to 185V 172V to 184V 172V to 180V 174V to 183V
exciting voltage at ST1 / 1F1 to 1F2 [VDC] 15V to 40V 10V to 35V 10V to 40V 12V to 40V
exciting current of the regulator [ADC] 0,4A to 1,4A 0,3A to 1,4A 0,3A to 1,6A 0,4A to 1,8A

generator (build size 160) 25KW / 30KW


resistance exciting winding at 20°C/68°F [Ohm] 27 Ohms to 28 Ohms
resistance main stator winding U1 to V1 [Ohm] approx. 0,3 Ohms
resistance main stator winding V1 to W1 [Ohm] approx. 0,3 Ohms
resistance main stator winding W1 to U1 [Ohm] approx. 0,3 Ohms
resistance main stator winding U2 to V2 [Ohm] approx. 0,3 Ohms
resistance main stator winding V2 to W2 [Ohm] approx. 0,3 Ohms
resistance main stator winding W2 to U2 [Ohm] approx. 0,3 Ohms
resistance main stator winding U1 to U2 [Ohm] high resistance >1MegaOhm
generator speed range [rpm] 2200 rpm to 3300 rpm
no load running mode value range (measured @ 2300rpm)
regulated generator voltage U to V [VAC] 155V to 170V
regulated generator voltage V to W [VAC] 155V to 170V
regulated generator voltage W to U [VAC] 155V to 170V
remanence voltage between the every phase only if
min. 30V to 70V
the regulator is disconnected @ 2300rpm [VAC]
exciting voltage at ST1 / 1F1 to 1F2 [VDC] 5V to 20V
exciting current of the regulator [ADC] 0,2A to 0,5A
load running mode value range (measured @ 2300rpm)
output voltage at the magnet plate [VDC] 220V to 238V
maximum magnet current [ADC] 109A (25KW) / 130A (30KW)
generator voltage U to V [VAC] 170V to 180V
generator voltage V to W [VAC] 170V to 180V
generator voltage W to U [VAC] 170V to 180V
exciting voltage at ST1 / 1F1 to 1F2 [VDC] 8V to 30V
exciting current of the regulator [ADC] 0,3A to 1,4A

Note: The generator with build size 160 has two separate Y-wired main windings to supply the
MAPLA electronic. The windings are separated with the no. 1 and 2.

To get the exciting current of the regulator, measure the exciting resistance (F1 to F2) and
the exciting voltage at ST1 (see connection plan at page 9 and 10). The current is
calculated by voltage / resistance (divide).

Measuring of exciting voltage is possible only with a “True-RMS-Multimeter”

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 6 -
Extended MAPLA troubleshooting

1 Power supply voltage for MMI available


The system is ON and ready for operation – the generator is running.
2 Magnet plate is on ("lifting")
This LED remains on while the magnet plate is in the on state. If the
magnet plate is switched off, i.e. the load is thrown off, this LED goes
out.
3 Fast demagnetization in progress (“fast drop”)
3 (fast „throwing off“ only in normal mode / A-Mode)
The LED is on during automatic fast demagnetization. The LED goes out
after the demagnetization has been finished completely. This mode is
disabled if inching mode* (optional mode B) is selected.
4 Open magnet connection / Data interface fault
LED on: Open magnet connection / Interruption
The LED light continues, if the connecting cable of the magnet plate is
either not plugged in or interrupted.
LED flashes: Data interface error
The LED flashes, if a communication error has occurred on the data
interface between MAPLA and MMI. Check the MMI data cable against
electrical contact problems.
5 Overload / System failure
LED on: Overload (magnet current limiter at INT-System active)
The LED is on, if the connected magnet plate is oversized for the MAPLA
system. In some cases the magnet plate could be damaged internally. At
the new INT-System, the magnet current limiter is active. The magnet
current is limited to the max. allowed value. The LED could also be light,
if a very cold magnet is connected. After a few minutes while operation,
the LED should be off. Otherwise the magnet should be checked.
LED flashes: System failure (at older non INT-Systems: Short circuit)
This LED flashes, if at an INT-System a system failure has occurred. To
find out the exactly causation of this fault, a flash-code could be
displayed at the 100%-LED and verified with a separate flash-code table.
Bxx INT xxxx At older systems (non INT), the flashing LED means, you have a general
short circuit. The magnet was switched off (cut-off) immediately. The
problem should be checked by an electricity specialist. To reset the fault,
an engine stop is required.
123456 6 Underspeed / Overspeed
LED on: Underspeed generator
The LED is on, if the generator operates at underspeed and thus may no
longer be able to realize its full performance (reduced voltage).
LED flashes: Overspeed generator
Flashing of this LED indicates that the generator operates at overspeed.
version/ The system / magnet is blocked to switch on again. May you need a
max. power reset of the system (stop engine).
type 7 Duty ratio of the magnet plate in percent
in KiloWatts The duty ratio of the magnet plate is the ratio between on-period and
off-period. To protect the magnet plate (against over temperatures), the
variant INT: duty ratio should be less than 80%. Check also the max. allowed value
intelligent for your used magnet. If the 100%-LED is flashing, it is required to take
MAPLA a break period!
( only at newer systems / 4 + 5 + 6 LED flashing Insulation monitor alert
at older systems these The insulation monitor (optional) has detected an insulation error
three letters are missing ) between the magnet plate case and the active conductor (+/-) of the
MAPLA system. If these LEDs are flashing the resistance is less than 25
KiloOhms. It is required to check the system against insulation faults. At
INT-Systems, the magnet is blocked to switch on again (reset required).
4 + 5 + 6 LED on + 7(100%) LED flashes
Over temperature error of electronic / generator
As long as this error is indicated, the magnet plate could not be
switched on again after having thrown off the load. Once
temperature of generator and electronic is within the tolerance
limits again, the indicator will go out automatically. It is recommended
to cool down the system while engine is running in idle mode. Check
the system against dust and a covered or damaged generator fan!

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 7 -
Extended MAPLA troubleshooting

iMAPLA (INT) MMI flash-code only if a system failure occurs.


Only for MMIs labelled with “INT” and INT-Controllers.

LED no. 5 flashes => SYSTEM FAILURE


(switch-on magnet is blocked)
(note: at INT this signal is new defined)

the flash-code at the MMI is displayed at the


100%-duty-ratio-LED if you push and hold
the joystick button for 5 seconds
flash-code short- procedure /
ext. fault description class / category
(counts) description course of action

1 not used --- --- not used


a discharger fault while the fast
drop mode was in progress
internal system internal fault
discharger caused a over voltage and
2 failure enables the security-function;
failure discharger Error
category 1 contact your local dealer
check the discharger and the
resistances
oversized magnet!
ensure, that you are using the
the allowed limiter value of external system right type of magnet (size);
limiter
3 overload
150% has been exceeded failure check the magnet against
(switch-on magnet blocked) category 1 insulation errors or internal
short-circuits
(e.g. damaged windings)
external system simple short-circuit detected;
short circuit difference monitor alert
4 type 1 caused CUT-OFF
failure check the magnet plate and
category 1 the cable
a too high current caused a
external system
short circuit limit value monitor alert short-circuit alert (CUT-OFF);
5 type 2 caused CUT-OFF
failure
check the magnet plate and
category 1 the cable
critical short-circuit detected;
internal system check the magnet plate and
short circuit IGBT desaturation alert
6 type 3 caused CUT-OFF
failure the cable; contact your local
category 2 dealer if you have this
problem further on
weak short-circuit or overload
external system
short circuit undervoltage monitor alert >400% of rated power
7 type 4 caused CUT-OFF
failure
detected; check the magnet
category 2 plate and the cable
internal overvoltage while internal system internal fault
over voltage
8 type 1
magnet was off failure over voltage regulator
(discharger protection) category 2 contact your local dealer
internal over voltage while internal system internal fault
over voltage
9 type 2
magnet was on failure over voltage regulator
(discharger protection) category 2 contact your local dealer
internal system internal fault
over voltage overvoltage while magnet was
10 type 3 off (DC-link protection)
failure over voltage regulator
category 2 contact your local dealer
internal system fault is current not defined
11 system error system fault
failure (not used at present)
no no intelligent the older software-version of the
this function is not available /
flash-code MAPLA MAPLA does not support this ---
(at 100%ED) available MAPLA uprade needed
function
= 3 c o u n ts = 3 c o u n ts

E X A M P L E fo r th e LED on
fla s h c o d e N o .3
L E D o ff 1 2 3 1 2 3
(= 3 L E D c o u n ts ) b re a k
tim e

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 8 -
Extended MAPLA troubleshooting

Testing the MMI-Connections --- MMI LED and button descriptions (actual version)

JP2 Jumper to configure the respective


Only if the jumper JP2 is not set hardware version to the
programmed software of the MMI.
Important: Do not change/set
S1 Joystick test push button.
S1 S2 To test the joystick switch, push
this button and the magnet plate
P1 P2 should be in on mode. Before you
have to select the operational
mode at the switch of the MMI
JP2 (optional function).
S2 Test button to change operational
D16 mode between normal mode and
D35 inching mode*. To test the inching
D17 D34 mode* (mode B) push and hold
this button.
D14 D15 P1 & P2 Potentiometer for optional
functions
J1 Important: Do not twist3
D14 signal LED joystick to J1
Only enabled if JP2 is set.
D15 signal LED main-switch to J1
Only enabled if JP2 is set.
D16 signal LED relay K1 on
The LED D16 lights, if the magnet
is in on mode (“lifting”).
(not on some old
software versions)
D17 signal LED relay K2 on
Only enabled if JP2 is set.
D23 D23 signal LED inching mode* to J1
(only available at new pcb-version
J2 and if JP2 is set)
The LED D23 lights, if the MAPLA
is in inching mode*. The signal
for this configuration is connected
to J1.
J1 Extented interface (optional) is active, if the D34 signal LED joystick to J2
jumper JP2 is set. If the Joystick connected to J2 is
pushed, the LED D34 is on.
J2 Data and power connection between D35 signal LED inching mode* to J2
the MMI and the control system (generator) If the mode-switch (optional) at the
MMI is in inching mode* (mode B),
the LED D35 is on.

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 9 -
Extended MAPLA troubleshooting

Testing the MMI-Connections --- MMI LED and button descriptions (actual version)

JP2 Jumper to configure the respective


Only if the jumper JP2 is set hardware version to the
programmed software of the MMI.
Important: Do not change/remove
S2 Test button to activate the MAPLA
S1 S2 To test the main-switch for the
MAPLA push and hold this button.
P1 P2 S1 Joystick test push button.
To test the Joystick switch, push
this button and the magnet plate
JP2 should be in on mode. Before you
have to activate the system with
D16 the switch S2 or main-switch at the
D35 machine panel.
D17 D34 P1 & P2 Potentiometer for optional
functions
D14 D15 Important: Do not twist3
D14 signal LED joystick to J1
J1 If the joystick button connected to
J1 is pushed, the LED D14 should
be on.
D15 signal LED main-switch on
If the main-switch at the machine
panel is on, the LED D15 should
be on.
D16 signal LED relay K1 on
The LED D16 lights, if the magnet
is in on mode (“lifting”)
D17 signal LED relay K2 on
The LED D17 lights, if the main-
D23 switch at the panel is on.
D23 signal LED inching mode* to J1
J2 (only available at new pcb-version)
The LED D23 lights, if the MAPLA
is in inching mode*. The signal
for this configuration is connected
to J1. For this mode JP2 has to be
set.
J1 Extented interface (optional) is active, if the D34 signal LED joystick to J2
jumper JP2 is set. If the Joystick connected to J2
(optional) is pushed, the LED D34
is on. Important, if JP2 is not set.
J2 Data and power connection between D35 signal LED inching mode* to J2
the MMI and the control system (generator) If the mode-switch (optional) at the
MMI is in inching mode (mode B),
the LED D35 is on.

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 10 -
Extended MAPLA troubleshooting
Connections of the MAPLA-System 8KW to 17KW:

MMI Interface

OUT1
MMI fuse

OUT2

u uu
v vu
v vw J1
www
Uact to ST1

w
2
ST2 1
v
u
ISO Monitor

1
2
3 J5
ISO Monitor

J6 4
J601

4 13
J2 2 2
3 14
Discharger

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 11 -
Extended MAPLA troubleshooting

Connections of the MAPLA-System 20KW to 30KW:

J5
J601
ISO Monitor
ST2 ISO Monitor

R1

OUT1
D ischa rger

+R1 W1 V1 U1
+R2 J1
+R3 W2 V2 U2
R2 J6 OUT2
R3
J2
M M I In te rfac e
M M I fuse

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 12 -
Extended MAPLA troubleshooting

Overview / simple schematic of the iMAPLA–System G1 8KW to 17KW:

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 13 -
Extended MAPLA troubleshooting

Overview / simple schematic of the iMAPLA–System G1 20KW:

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 14 -
Extended MAPLA troubleshooting

Overview / simple schematic of the iMAPLA–System G1 25kW to 30KW:

GTS Generator. Technik. Systeme. GmbH & Co.KG Telefon: +49 (0) 7174 / 898 00%0 eMail: info@gts%generator.com
editor: GTS version date: 17.06.2013 page - 15 -

You might also like