You are on page 1of 1

Model F210R

Riser Checks
Application
The Zurn F210R Fire Riser Check is a zone water
check to prevent system reversal of flow; as
required by systems including sprinkler standpipe
systems and fire department connections. The
F210R Fire Riser Check includes tapped and
plugged drilled holes for use with an optional
Check Trim Kit (sold separately) to complete the
Riser Check. Check Trim Kit includes two gauges,
two isolation valves, fittings and drain valve.

Application
The Zurn F210 Riser Check Valve is a zone water
check to prevent system reversal of flow; as
required by systems including sprinkler standpipe
systems and fire department connections.

4-F210R
Materials Shown with Trim Kit (Sold Separately)
Body Casting ASTM A 536 Ductile Iron
Seat Bronze
Clapper 304 Stainless Steel
Plug 304 Stainless Steel
Gasket EPDM Rubber

Standards Compliance
• UL ® Listed
• C-UL ® Listed
• FM® Approved

Features
Sizes: 2-1/2”, 3”, 4”, 6”, 8”
Maximum Pressure: 300 PSI 212-3-CHECKTRIM

E
Dimensions & Weights (do not include pkg.) DOWNSTREAM
GAUGE
DIMENSIONS (approximate)
SIZE
MODEL A B C D E Weight
in.
in. in. in. in. in. lb.
2 1/2 212-F210R 7.00 5.00 3.25 9.50 3.00 13.9
3 3-F210R 8.00 5.00 3.25 9.50 3.50 18.1 A
4 4-F210R 8.75 5.00 4.25 13.50 4.25 28.4
C
6 6-F210R 10.75 7.00 6.00 14.50 4.75 50.4 MAIN
DRAIN

8 8-F210R 13.00 8.63 7.75 16.13 6.00 85.4


B UPSTREAM
GAUGE
D

Zurn Industries, LLC | Wilkins Rev. C


1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 Date: 03/20
In Canada | Zurn Industries Limited Document No. F210R Riser Check
Product No. Model F210R
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216 
www.zurn.com Page 1 of 1