Professional Documents
Culture Documents
Date Commence :
Date Completed :
Ship’s Stamp :
TRAINING INFORMATION
COURSE : BSMarE
Disembarked Date :
ELECTRICAL SYSTEM
Describe the procedure for paralleling the ship’s alternator or generators. Explain how load
sharing is affected.
MAERSK HARMONY
Auxiliary engines can be started directly from the ACONIS. Click “Exit” to leave
the box.
On “Power management System” screen, left click on A/E to be started. On the
dialog box, click “Start” and then click “Confirm”.
Engine will start and come on load automatically.
Local
On the MSB, ensure the generator control mode for the engine you are trying to
start is on “Manual”
Check lube oil level in crankcase, governor & alternator bearings.
Set all lines and check all temperatures and pressures are normal.
Check that lube oil priming pump is running.
Ensure indicator cocks and turbocharger drains are open.
Blow through the engine and shut the indicator cocks and turbocharger drain.
On the LCP, switch to either “On Eng” Position or “Local” position, depending on
where you wish to start from.
Start the engine from the location selected.
Check all parameters, and for leaks and oil levels.
Switch control position to “Remote” on the LCP.
The engine can now be taken on load in any one of 2 ways:
1. AUTO SYNCHRONIZING: On the MSB, switch the control mode switch to
“Auto”. Press “Start” on the Aconis 2000 PMS Unit. The engine will come on
load automatically.
2. MANUAL SYNCHRONIZING: On the MSB, ensure generator control mode
switch is on “Manual”.
a. Switch the “Synchroscope” & “Frequency/Voltmeter” switches to the
engine you want to take on load.
b. Use the governor motor control knob to adjust frequency if required.
c. Before closing the ACB, check that:
i. The Incoming generator has the same voltage as the bus bar.
ii. The Incoming generator has the same frequency as the bus bar.
iii. The Synchroscope needle rotates in the CLOCKWISE direction,
as slowly as possible.
d. Close the ACB using the ACB control switch when:
i. The Synchroscope needle is at the 11 o’clock position.
ii. On the synchronizing lamps, the top lamp is dark and the lower
2 lamps are equally bright.
On the MSB, ensure the generator control mode for the engine you are trying to
start is on “Manual”.
Switch control to “Local” on the LCP.
Press button for Emergency Start on the Main Start Solenoid near the starting air
motor to start the engine. Once engine starts to turn at above 140 RPM, release
button. Engine will start.
Switch control position to “Remote”. The engine can now be taken on load from
the ECR as described before.
STOPPING
2. Each engine can be stopped by activating its Fuel Inlet Quick Closing Valve
from the panel outside the Purifier Room.
The Light Load cancel feature allows for automatic starting of standby engines when
load on the busbar exceeds a certain percentage of the total capacity of the engines on
load, and for automatic stopping of extra engines when load on the busbar drops below
a certain percentage of the total capacity of the engines on load. These settings can be
altered from the “Power management System” screen on the ACONIS.
It is safer to keep the “Light Load Cancel” Feature ON whenever you wish to run
2 or more engines in parallel without the system automatically stopping them if
there is a delay in the load coming online, for example – delays in starting of
cargo compressor.
Engines cannot be offloaded from the ACONIS screen if the “Light Load Cancel”
feature is ON. This feature must be turned OFF before offloading the engine.
A.C. alternators
To parallel alternators the following conditions are required;
More power may be obtained at the bus bars from the incoming alternator only
by supplying more power to its prime mover. This increase of steam or fuel supply is
achieved by altering the governor setting either electrically or manually.
After adjusting the governor the incoming machine takes up its desired amount
of the kW loading and this is recorded on the machines watt meter. However, if the kW
loading is shared equally between two machines it may be found that the Load Current of
the incoming machine is more or less than the other machine. This is fue to the incoming
machine having a different power factor. This may be corrected by adjusting the excitation
of the incoming alternator.
If the alternators have similar load characteristics, once adjusted, the load will continue to
be shared. If the load characteristics of alternators vary, the kW loading and load current
sharing may require readjusting under different load conditions.
Load sharing of alternators
No1 on load
No1 and No2 sharing load after adjusting governor settings, excitation
adjusted to prevent excessive volt drop in No2
No1 and No2 sharing load with balanced power factors by adjusting
excitation
The effects of altering Torque and Excitation on single
phase alternator plant-and by extrapolation a 3-phase
circuit
Before paralleling, by varying Rb, adjust the excitation current in the rotor field
of 'B' until Va=Vb. When in phase and at the same frequency synchronising may take place.
If there was no external load on the bus bars the torque on the prime movers of
A and B is only that required by its own alternator and Ra and Rb are adjusted so that Ea
and Eb are equal.
Relative to the bus bars Ea and Eb are acting in the same direction with each
other making the top bar positive with respect to the bottom bar.
Varying the driving torque
If the driving torque of 'B' is reduced (less fuel supplied) the rotor falls back by
an angle say p.f.(b) giving a resultant e.m.f. of Ez in the closed circuit.
Varying excitation
Consider A and B are exerting the torque required by its alternator and the
generated e.m.f. Ea and Eb are equal. There is no circulating current.
By reducing Rb the excitation current in the field of B can be increased and Eb will increase.
Ez is the resultant difference (Eb - Ea) which will give a circulating current I through the
synchronous impedances of the two alternators. As the machines are similar the impedance
drop in each will be 1/2Ez so the terminal voltage
V1 = Eb - Н Ez = Ea + Н Ez
By increasing Rb the reduction of the field excitation current of B will reduce the terminal
voltage
The worse the power factor the worse the terminal voltage change during load
change.